Plan Review Notes
Plan Review Notes For Permit 08100109
Permit Number 08100109
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-15 09:01:57PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE "FLORIDA SOLAR ENERGY CENTER, APPROVED SOLAR
 ENERGY SYSTEM" SHEET IS INDICATING TWO DIFFERENT MODEL
 NUMBERS FOR THE TANK MANUFACTURER, PUMP MANUFACTURER,
 AND CONTROLLER MANUFACTURER. CLEARLY INDICATE ON THE
 RESUBMITTAL WHICH MODEL NUMBER TANK, PUMP AND
 CONTROLLER IS BEING USED ON THE PROPOSED SOLAR WATER
 HEATER. PER FBC-2004 CHAPTER 1, (W.P.B.) AS AMENDED
 SECTION 106.1.2 ADDITIONAL DATA.
  
 2. PLEASE CLARIFY ON THE RESUBMITTAL THE LOCATION OF
 THE PROPOSED DOMESTIC SOLAR WATER HEATING SYSTEM. IS
 THE SYSTEM CONNECTING TO THE EXISTING COLD WATER SUPPLY
 AND HOT WATER LINES AT THE EXISTING DOMESTIC WATER
 HEATER LOCATION? PLEASE KNOW THAT IF THE PROPOSED
 DOMESTIC SOLAR WATER HEATING SYSTEM IS NOT AT THE
 EXISTING DOMESTIC WATER HEATER LOCATION THAT A LICENSED
 PLUMBING CONTRACTOR WILL BE REQUIRED TO PIPE THE SYSTEM
 TO A NEW LOCATION. PER FAC 61G4-15.021 CERTIFICATION OF
 SOLAR CONTRACTORS (E) PLUMBING.
  
 3. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR ENGINEER,
 THEN HE OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL,
 SIGNATURE AND DATE TO SAID DRAWINGS, PER FLORIDA
 STATUTES 481 AND 471 RESPECTIVELY.
 *THE CONTRACTOR OF RECORD MAY BE THE DESIGN
 PROFESSIONAL IF EXEMPTIONS UNDER FLORIDA STATUTES
 471.003(H) APPLY.
  
 4. PER FS 713.13 (1) THRU (6): A NOTICE OF COMMENCEMENT
 IS REQUIRED FROM THE - PALM BEACH COUNTY COURTHOUSE -
 4TH FLOOR RECORDING DEPT. 205 N. DIXIE HWY., BEFORE THE
 FIRST INSPECTION. PER FS 713.13 (2): IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS VOID AND OF NO FURTHER EFFECT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]