2008-11-12 13:15:192004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS. PREVIOUS COMMENT.
  
 3) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL
 BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION (SEE SECTION 202 , REGISTERED
 TERMITICIDE). PREVIOUS COMMENT.
  
 4) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL
 EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE. PREVIOUS COMMENT.
  
 5) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 PREVIOUS COMMENT.
  
 6) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE ROOF
 COVERING MATERIAL, HARDI PLANK SIDING, HURRICANE STRAPS
 AND ANCHORS. FAC RULE 9B-72. PREVIOUS COMMENT.
  
 7) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 AND EVALUATION REPORT FOR THE SLIDING GLASS DOORS AND
 SKYLIGHTS AS REQUIRED BY FAC RULE 9B-72. PREVIOUS
 COMMENT.
  
 8) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE HORIZONTAL SLIDING WINDOWS INCLUDING PAGES 1
 AND 2 OF 8, THAT ARE MISSING FROM THE ONE COPY THAT WAS
 SUBMITTED. FAC RULE 9B-72. PREVIOUS COMMENT.
  
 21) ADDITIONAL PLANS, FEES AND PERMITS WILL BE REQUIRED
 FOR ELECTRICAL. FBC 105.1 AND 108.1* CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW