Plan Review Notes
Plan Review Notes For Permit 08100099
Permit Number 08100099
Review Stop B
Sequence Number 1
Notes
Date Text
2008-10-17 16:56:192004 FBC W/2007 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL
 BE REQUIRED. FS 713
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT ENERGY CALCULATIONS FOR THE ADDITION AS
 REQUIRED BY FBC 13-600.
  
 4) ON SHEET 2, PLEASE REVISE THE INSULATION SPECIFIED
 IN THE 2 X 6 FRAME WALLS TO R19 AS REQUIRED BY FBC
 13-602.2.A.3
  
 5) SPECIFY ALL OF THE CONNECTORS THAT WILL BE USED TO
 ATTACH THE WALLS TO RAFTERS, WALLS TO FOUNDATION, ETC.
 TO PROVIDE A CONTINUOUS LOAD PATH TO TRANSFER WINDLOADS
 TO THE FOUNDATION AS REQUIRED BY FBC R301.1.
  
 6) ON SHEET 1 THE NOTES INCORRECTLY SPECIFY THE 2006
 IRC. PLEASE CORRECT TO REFERENCE THE 2004 FBC WITH 2007
 REVISIONS.
  
 7) SPECIFY THE WINDLOAD PRESSURE AT THE WINDOW,
 SKYLIGHTS AND DOOR OPENINGS. FBC R301.2.1 AND TABLE
 R301.2(2)
  
 8) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 9) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL
 BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION (SEE SECTION 202 , REGISTERED
 TERMITICIDE).
  
 10) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL
 EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE
 FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM)
 WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES
 (152 MM) ELSEWHERE.
  
 11) SHOW COMPLIANCE WITH R311.5.3.1 RISER HEIGHT AND
 R311.5.3.2 TREAD DEPTH. THE MAXIMUM RISER HEIGHT SHALL
 BE 7? INCHES (196 MM). THE RISER SHALL BE MEASURED
 VERTICALLY BETWEEN LEADING EDGES OF THE ADJACENT
 TREADS. THE MINIMUM TREAD DEPTH, EXCLUSIVE OF NOSING,
 SHALL BE NOT LESS THAN 9 INCHES (229 MM). TREADS AND
 RISERS OF STAIRS SHALL BE PERMITTED TO BE SO
 PROPORTIONED THAT THE SUM OF TWO RISERS AND A TREAD,
 EXCLUSIVE OF PROJECTION OF NOSING, IS NOT LESS THAN 24
 INCHES (610 MM) NOR MORE THAN 25 INCHES (635 MM).
  
 12) IF LANDING IS MORE THAN 30 INCHES ABOVE THE FLOOR
 SHOW COMPLIANCE WITH R312.1 GUARDS REQUIRED.
 PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR GRADE
 BELOW SHALL HAVE GUARDS NOT LESS THAN 36 INCHES (914
 MM) IN HEIGHT. OPEN SIDES OF STAIRS WITH A TOTAL RISE
 OF MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR
 GRADE BELOW SHALL HAVE GUARDS NOT LESS THAN 34 INCHES
 (864 MM) IN HEIGHT MEASURED VERTICALLY FROM THE NOSING
 OF THE TREADS.
  
 13) R312.1 GUARDS REQUIRED.
 PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED
 MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR GRADE
 BELOW SHALL HAVE GUARDS NOT LESS THAN 36 INCHES (914
 MM) IN HEIGHT. OPEN SIDES OF STAIRS WITH A TOTAL RISE
 OF MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR
 GRADE BELOW SHALL HAVE GUARDS NOT LESS THAN 34 INCHES
 (864 MM) IN HEIGHT MEASURED VERTICALLY FROM THE NOSING
 OF THE TREADS.
  
 14) ROOF SHEATHING FASTENING IS REQUIRED TO BE IN
 ACCORDANCE WITH SECTION R803.2.3.1 OF 2007 REVISIONS TO
 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL
 SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D
 RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6
 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1. SPECIFY
 ROOF SHEATHING FASTENING ON THE PLANS.
  
 15) ON SHEET 2 OF THE PLANS, BOTH 7/16" AND 9/16"
 DRYWALL IS SPECIFIED. PLEASE CLARIFY.
  
 16) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 17) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE ROOF
 COVERING MATERIAL, HARDI PLANK SIDING, HURRICANE STRAPS
 AND ANCHORS. FAC RULE 9B-72.
  
 18) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 AND EVALUATION REPORT FOR THE SLIDING GLASS DOORS AND
 SKYLIGHTS AS REQUIRED BY FAC RULE 9B-72.
  
 19) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS
 FOR THE HORIZONTAL SLIDING WINDOWS INCLUDING PAGES 1
 AND 2 OF 8, THAT ARE MISSING FROM THE ONE COPY THAT WAS
 SUBMITTED. FAC RULE 9B-72.
  
 20) HANDWRITTEN NOTES TO SIGNED AND SEALED PLANS ARE
 NOT ALLOWED. PLEASE INCORPORATE THE CHANGES INTO THE
 PLANS WHICH HAVE BEEN SIGNED AND SEALED BY THE DESIGNER
 OF RECORD AS REQUIRED BY FLORIDA STATUTE FS 471.
  
 21) ADDITIONAL PLANS, FEES AND PERMITS WILL BE REQUIRED
 FOR ELECTRICAL AND MECHANICAL. FBC 105.1 AND 108.1*
 CITY AMENDMENTS
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]