| 2008-10-17 16:56:19 | 2004 FBC W/2007 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT WILL |
| | BE REQUIRED. FS 713 |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT ENERGY CALCULATIONS FOR THE ADDITION AS |
| | REQUIRED BY FBC 13-600. |
| | |
| | 4) ON SHEET 2, PLEASE REVISE THE INSULATION SPECIFIED |
| | IN THE 2 X 6 FRAME WALLS TO R19 AS REQUIRED BY FBC |
| | 13-602.2.A.3 |
| | |
| | 5) SPECIFY ALL OF THE CONNECTORS THAT WILL BE USED TO |
| | ATTACH THE WALLS TO RAFTERS, WALLS TO FOUNDATION, ETC. |
| | TO PROVIDE A CONTINUOUS LOAD PATH TO TRANSFER WINDLOADS |
| | TO THE FOUNDATION AS REQUIRED BY FBC R301.1. |
| | |
| | 6) ON SHEET 1 THE NOTES INCORRECTLY SPECIFY THE 2006 |
| | IRC. PLEASE CORRECT TO REFERENCE THE 2004 FBC WITH 2007 |
| | REVISIONS. |
| | |
| | 7) SPECIFY THE WINDLOAD PRESSURE AT THE WINDOW, |
| | SKYLIGHTS AND DOOR OPENINGS. FBC R301.2.1 AND TABLE |
| | R301.2(2) |
| | |
| | 8) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE |
| | PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8 |
| | INCH (3.2 MM) MINIMUM TO 1/4 INCH (6.4 MM) MAXIMUM |
| | OPENINGS. |
| | |
| | 9) SHOW COMPLIANCE WITH R320.1 TERMITE PROTECTION SHALL |
| | BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL |
| | APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES |
| | APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE |
| | PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT |
| | TO NEW CONSTRUCTION (SEE SECTION 202 , REGISTERED |
| | TERMITICIDE). |
| | |
| | 10) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED |
| | GRADE. CONCRETE AND MASONRY FOUNDATION WALLS SHALL |
| | EXTEND ABOVE THE FINISHED GRADE ADJACENT TO THE |
| | FOUNDATION AT ALL POINTS A MINIMUM OF 4 INCHES (102 MM) |
| | WHERE MASONRY VENEER IS USED AND A MINIMUM OF 6 INCHES |
| | (152 MM) ELSEWHERE. |
| | |
| | 11) SHOW COMPLIANCE WITH R311.5.3.1 RISER HEIGHT AND |
| | R311.5.3.2 TREAD DEPTH. THE MAXIMUM RISER HEIGHT SHALL |
| | BE 7? INCHES (196 MM). THE RISER SHALL BE MEASURED |
| | VERTICALLY BETWEEN LEADING EDGES OF THE ADJACENT |
| | TREADS. THE MINIMUM TREAD DEPTH, EXCLUSIVE OF NOSING, |
| | SHALL BE NOT LESS THAN 9 INCHES (229 MM). TREADS AND |
| | RISERS OF STAIRS SHALL BE PERMITTED TO BE SO |
| | PROPORTIONED THAT THE SUM OF TWO RISERS AND A TREAD, |
| | EXCLUSIVE OF PROJECTION OF NOSING, IS NOT LESS THAN 24 |
| | INCHES (610 MM) NOR MORE THAN 25 INCHES (635 MM). |
| | |
| | 12) IF LANDING IS MORE THAN 30 INCHES ABOVE THE FLOOR |
| | SHOW COMPLIANCE WITH R312.1 GUARDS REQUIRED. |
| | PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED |
| | MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR GRADE |
| | BELOW SHALL HAVE GUARDS NOT LESS THAN 36 INCHES (914 |
| | MM) IN HEIGHT. OPEN SIDES OF STAIRS WITH A TOTAL RISE |
| | OF MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR |
| | GRADE BELOW SHALL HAVE GUARDS NOT LESS THAN 34 INCHES |
| | (864 MM) IN HEIGHT MEASURED VERTICALLY FROM THE NOSING |
| | OF THE TREADS. |
| | |
| | 13) R312.1 GUARDS REQUIRED. |
| | PORCHES, BALCONIES OR RAISED FLOOR SURFACES LOCATED |
| | MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR GRADE |
| | BELOW SHALL HAVE GUARDS NOT LESS THAN 36 INCHES (914 |
| | MM) IN HEIGHT. OPEN SIDES OF STAIRS WITH A TOTAL RISE |
| | OF MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR OR |
| | GRADE BELOW SHALL HAVE GUARDS NOT LESS THAN 34 INCHES |
| | (864 MM) IN HEIGHT MEASURED VERTICALLY FROM THE NOSING |
| | OF THE TREADS. |
| | |
| | 14) ROOF SHEATHING FASTENING IS REQUIRED TO BE IN |
| | ACCORDANCE WITH SECTION R803.2.3.1 OF 2007 REVISIONS TO |
| | 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL |
| | SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D |
| | RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6 |
| | INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF |
| | RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| | NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND |
| | SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1. SPECIFY |
| | ROOF SHEATHING FASTENING ON THE PLANS. |
| | |
| | 15) ON SHEET 2 OF THE PLANS, BOTH 7/16" AND 9/16" |
| | DRYWALL IS SPECIFIED. PLEASE CLARIFY. |
| | |
| | 16) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 17) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE ROOF |
| | COVERING MATERIAL, HARDI PLANK SIDING, HURRICANE STRAPS |
| | AND ANCHORS. FAC RULE 9B-72. |
| | |
| | 18) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS |
| | AND EVALUATION REPORT FOR THE SLIDING GLASS DOORS AND |
| | SKYLIGHTS AS REQUIRED BY FAC RULE 9B-72. |
| | |
| | 19) SUBMIT TWO COPIES OF THE INSTALLATION INSTRUCTIONS |
| | FOR THE HORIZONTAL SLIDING WINDOWS INCLUDING PAGES 1 |
| | AND 2 OF 8, THAT ARE MISSING FROM THE ONE COPY THAT WAS |
| | SUBMITTED. FAC RULE 9B-72. |
| | |
| | 20) HANDWRITTEN NOTES TO SIGNED AND SEALED PLANS ARE |
| | NOT ALLOWED. PLEASE INCORPORATE THE CHANGES INTO THE |
| | PLANS WHICH HAVE BEEN SIGNED AND SEALED BY THE DESIGNER |
| | OF RECORD AS REQUIRED BY FLORIDA STATUTE FS 471. |
| | |
| | 21) ADDITIONAL PLANS, FEES AND PERMITS WILL BE REQUIRED |
| | FOR ELECTRICAL AND MECHANICAL. FBC 105.1 AND 108.1* |