| 2008-10-07 10:31:11 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | |
| | SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY |
| | |
| | ____ 1. PROVIDE BUILDING HEIGHT ON THE PLAN. DESIGN |
| | PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE |
| | DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A |
| | DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT |
| | OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| | SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16. |
| | |
| | _XX_ 2. COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR |
| | PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN |
| | ANOTHER FORMAT, FBC*106. TWO SETS REQUIRED. |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | ____ 3. FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | ____ 4. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310. |
| | |
| | ____ 5. PROVIDE A FLOOR PLAN SHOWING WHERE THE SHUTTERS |
| | WILL BE INSTALLED AND PANEL SIZES WHICH CORRELATES WITH |
| | THE INSTALLATION SCHEDULE, ITEM 2 ABOVE. |
| | |
| | ____ 6. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE |
| | FOR EXPOSURE B. NOTE THAT THE DEFINITION FOR EXPOSURE C |
| | HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC |
| | R301.2.1.4. |
| | |
| | |
| | |