| Plan Review Notes For Permit 08100061 |
| Permit Number |
08100061 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-07 11:02:21 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. THE INSTALLATION SCHEDULE PROVIDED DOES NOT | | | CORRELATE WITH THE PRODUCT APPROVAL. CONCRETE HAS BEEN | | | SPECIFIED, BUT THIS CHART HAS BEEN CROSSED OFF ON THE | | | PRODUCT APPROVAL. ANCHOR SPACING OF 6", 3" EDGE | | | DISTANCE CIRCLED. PLEASE REVISE SO THE TWO ARE | | | CONSISTENT. | | | | | | 2. THE INSTALLATION SCHEDULE, SUBSTRATE, SPECIFIES WOOD | | | FOR OPENINGS 1 THROUGH 6, BUT IN EDGE DISTANCE COLUMN | | | STATES THIS IS WOOD/CONCRETE. PLEASE REVISE SO THAT THE | | | SUBSTRATE INFORMATION IS CORRECT FOR EACH OPENING. CODE | | | COMPLIANCE CANNOT BE DETERMINED DUE TO THE FACT THAT | | | THIS INFORMATION HAS BEEN CROSSED OFF ON SHEET 7 OF THE | | | PRODUCT APPROVAL; IT IS NOT CLEAR IF THE SUBSTRATE IS | | | CONCRETE BLOCK AS INDICATED ON THE PRODUCT APPROVAL, OR | | | WOOD AND CONCRETE AS STATED IN THE EDGE DISTANCE | | | COLUMN, OR WOOD AS STATED IN SUBSTRATE COLUMN. |
|