Plan Review Notes
Plan Review Notes For Permit 08100026
Permit Number 08100026
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-09 11:37:33PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE CLEARLY INDICATE THE BUILDING CLASSIFICATION
 AND OCCUPANCY LOAD ON THE PLANS.
 PER FBC BUILDING SECTION 302.1 GENERAL. STRUCTURES OR
 PORTIONS OF STRUCTURES SHALL BE CLASSIFIED WITH RESPECT
 TO OCCUPANCY IN ONE OR MORE OF THE GROUPS LISTED BELOW.
  
 A} ASSEMBLY (SEE SECTION 303): GROUPS A-1, A-2, A-3,
 AND A-5
  
 B} BUSSINESS (SEE SECTION 304): GROUP B
  
 C} EDUCATIONAL (SEE SECTION 305): GROUP E
  
 D} FACTORY AND INDUSTRIAL (SEE SECTION 306): GROUPS F-1
 AND F-2
  
 E} HIGH HAZARD (SEE SECTION 307) GROUPS H-1, H-2, H-3,
 H-4, AND H-5
  
 F} INSTITUTIONAL (SEE SECTION 308): GROUP I-1, I-2, AND
 I-3
  
 G} MERCANTILE (SEE SECTION 309): GROUP M
  
 H} RESIDENTIAL (SEE SECTION 310): GROUPS R-1, R-2, R-3
 AS APPLICABLE IN SECTION 101.2, AND R-4
  
 I} STORAGE (SEE SECTION 311): GROUPS S-1 AND S-2
  
 J} UTILITY AND MISCELLANEOUS (SEE SECTION 312): GROUP U
  
 K} DAY CARE (SEE SECTION 313): GROUP D
  
 2. CLEARLY INDICATE THE CODE CYCLE ON THE PLANS. PER
 CITY OF WPB AMENDMENTS TO CHAPTER 1, (W.P.B. AS
 AMENDED) SECTION 106.5 RETENTION OF CONSTRUCTION
 DOCUMENTS.
 THE CURRENT CODE CYCLE FOR THE PLANS IS "FBC-2004 WITH
 2007 REVISIONS".
  
 3. DECLARE THE LEVEL OF ALTERATION, PER FBC-2004
 EXISTING BUILDING CHAPTER 3.
  
 4. SHEET A-4.01.3, BREAK AREA ELEVATION: CLEARLY
 INDICATE THE FOLLOWING REQUIREMENTS TO THE BREAK AREA
 SINK PER THE FBC-2004 CHAPTER 11, FLORIDA ACCESSIBILITY
 CODE SECTIONS.
  
 A} SECTION 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH,
 30" WIDE, AND 19" DEEP.
  
 B} SECTION 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND
 CLEAR FLOOR SPACE SHALL EXTEND A MAXIMUM OF 19"
 UNDERNEATH THE SINK.
  
 C} SECTION 11-4.24.6 EXPOSED PIPES AND SURFACES.
 INSULATE TO PROTECT AGAINST CONTACT.
  
 5. SHEET A-1.00-1 FLOOR PLAN: CLEARLY INDICATE THE
 REQUIRED TURNING SPACE FOR PEOPLE IN WHEELCHAIRS FOR
 THE BREAK AREA ROOM #103. PER THE FBC-2004 CHAPTER 11,
 FLORIDA ACCESSIBILITY CODE SECTION 11-4.22.3 CLEAR
 FLOOR SPACE. WHEELCHAIR TURNING SPACE SHALL BE
 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR SPACE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  