Plan Review Notes
Plan Review Notes For Permit 08100026
Permit Number 08100026
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-10-16 14:12:10*****DENIED*****
  
 1. THE SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS
 (SCOPE OF WORK LOCATION) IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET. SUITE NUMBER IS MISSING ON SHEETS
 E0.1 THRU E6.1, FA0.1 & FA2.1, M0.1 THRU M2.2 AND P0.1
 & P2.1.
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF THE DAY OR MORE
 FREAUENTLY FOR SAFE OPERATIONS.
  
 4. THE SCOPE OF WORK SHALL NOT HIDER OR INTERFERE WITH
 ACCESS TO / EGRESS FROM OTHER TENANT SPACES ON THE
 FLOOR AND/OR BUILDING.
  
 5. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 6. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR
 THIS TENANT SPACE. NOTE: THESE DEVICES CAN BE SHOWN ON
 THE REFLECTED CEILING PLAN SHEET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved