| Plan Review Notes For Permit 08100026 |
| Permit Number |
08100026 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-16 14:12:10 | *****DENIED***** | | | | | | 1. THE SUITE NUMBER SHALL BE INCLUDED IN THE ADDRESS | | | (SCOPE OF WORK LOCATION) IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. SUITE NUMBER IS MISSING ON SHEETS | | | E0.1 THRU E6.1, FA0.1 & FA2.1, M0.1 THRU M2.2 AND P0.1 | | | & P2.1. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF THE DAY OR MORE | | | FREAUENTLY FOR SAFE OPERATIONS. | | | | | | 4. THE SCOPE OF WORK SHALL NOT HIDER OR INTERFERE WITH | | | ACCESS TO / EGRESS FROM OTHER TENANT SPACES ON THE | | | FLOOR AND/OR BUILDING. | | | | | | 5. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 6. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR | | | THIS TENANT SPACE. NOTE: THESE DEVICES CAN BE SHOWN ON | | | THE REFLECTED CEILING PLAN SHEET. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|