2008-10-02 11:59:17GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE AND THE CITY OF
 WEST PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS.
 PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT
 APPLICATION REQUIREMENTS ATTACHED TO THESE COMMENTS TO
 HELP IN FUTURE PERMIT APPLICATIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING
 LENGTHS INDICATED ON THE SUBMITTED GAS ISOMETRIC.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 WITH NO CORRESPONDING LENGTHS AND COMPLY ON THE
 RESUBMITTAL.
  
 2. PLEASE CLEARLY INDICATE THE TYPE OF GAS, (LP OR
 NATURAL) BEING USED ON THE RESUBMITTED GAS ISOMETRIC.
 PER FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: PLEASE REFERENCE COMMENT #1 AND ALSO CLEARLY
 INDICATE THE GAS METER LOCATION ON THE RESUBMITTED
 ISOMETRIC.
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR FOR THE WATER HEATER. PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 5. PLEASE CLEARLY INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2. NATURAL GAS
 SPECIFY .5 PSI OR 2 PSI. LP GAS SPECIFY 10 PSI. PER
 FBC-2004 FUEL GAS CODE SECTION 401.1 SCOPE.
 NOTE: PLEASE KNOW THAT IF THE GAS TYPE IS NATURAL GAS
 AND THE DELIVERY PRESSURE IS 0.5 PSI THE SUBMITTED GAS
 ISOMETRIC PIPING IS SIZED WRONG PER FBC-2004 FUEL GAS
 TABLE 402.4(8). PLEASE REFERENCE THIS GAS TABLE AND THE
 RED LINE CORRECTIONS ON THE GAS ISOMETRIC.
  
 6. CLEARLY INDICATE THE TYPE OF COPPER TUBING BEING
 USED AS BEING EITHER TYPE K OR L. PER FBC-2004 FUEL GAS
 SECTION 403.5.2 COPPER AND BRASS TUBING.
  
 7. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR, MATERIALS AND DESIGN. THE REFERENCED
 MASER PERMIT #08050395 PLANS HAVE NO INDICATION OF ANY
 GAS WORK BEING DONE. THE GAS PERMIT VALUE APPEARS TO BE
 FOR THE PIPING MATERIAL, LABOR AND DESIGN, HOWEVER THE
 COST OF THE WATER HEATER AND STOVE ARE NOT ON THE
 VALUE. PLEASE KNOW THAT THE POOL HEATER WAS APPROVED ON
 POOL PERMIT #08060195 AND ITS VALUE DOES NOT NEED TO BE
 ADDED TO THIS PERMIT JUST THE STOVE AND WATER HEATER.
 PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  