Plan Review Notes
Plan Review Notes For Permit 08090755
Permit Number 08090755
Review Stop P
Sequence Number 1
Notes
Date Text
2008-10-10 14:16:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 CITY WPB MUNICIPAL CODE
  
 1. UPON CONVERSATION WITH THE CONTRACTOR, HE INDICATED
 THAT THE BUS WASH FACILITY WAS SELF CONTAINED AND THAT
 IT DID NOT CONNECT TO THE SANITARY SEWER SYSTEM. BUT
 UPON READING THE MANUF. SPECIFICATION SHEETS IN THE 4TH
 SHEET, ENVIRONMENTAL COMPLIANCE EQUIPMENT, WRITTEN
 PROPOSAL, IT STATES THAT THE RESULTING EFFLUENT CAN BE
 DISCHARGED DIRECTLY TO THE SANITARY SEWER AND THE
 SYSTEM FILLED WITH FRESH WATER TO BE RECYCLED. THE
 UTILITY DEPT. INDUSTRIAL PRE-TREATMENT SHALL DETERMINE
 IF AN OIL INTERCEPTOR IS REQUIRED AND SUBMIT A WRITTEN
 DETERMINATION PRIOR TO PERMIT BEING ISSUED. ARTICLE III
 SECTION 90-124(7).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  