| 2008-10-08 16:01:37 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET PLUMBING ISOMETRIC: PLEASE CORRECT THE |
| | FOLLOWING ITEMS ON THE PLUMBING ISOMETRIC PER THE |
| | FBC-2004 PLUMBING CODE SECTIONS. |
| | |
| | A} THE WASHING MACHINE MUST DRAIN DOWNSTREAM OF THE |
| | HORIZONTAL WET-VENT BATHROOM GROUP. ONLY FIXTURES |
| | WITHIN THE TWO BATHROOM GROUPS LOCATED ON THE SAME |
| | FLOOR SHALL CONNECT TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. PER SECTION 909.1 WET VENT |
| | PERMITTED. |
| | |
| | B} THE WASHING MACHINE TRAP AND FIXTURE DRAIN FOR THE |
| | AUTOMATIC CLOTHES WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER.THE AUTOMATIC CLOTHES WASHER FIXTURE |
| | DRAIN SHALL CONNECT TO A BRANCH DRAIN OR DRAINAGE STACK |
| | A MINIMUM OF 3 INCHES (76MM) IN DIAMETER. PER SECTION |
| | 406.3 WASTE CONNECTIONS. |
| | |
| | C} A STANDPIPE IS REQUIRED FOR THE WASHING MACHINE AND |
| | SHALL BE INDIVIDUALLY TRAPPED. STANDPIPES SHALL EXTEND |
| | A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) ABOVE THE TRAP |
| | WEIR. ACCESS SHALL BE PROVIDED TO ALL STANDPIPES AND |
| | DRAINS FOR RODDING. PER SECTION 802.4 STANDPIPES. |
| | |
| | D} A CLEANOUT IS REQUIRED FOR THE WASHING MACHINE |
| | DRAINAGE STACK. THE CLEANOUT SHALL BE 3 INCH (PER |
| | SECTION 708.7 MINIMUM SIZE) AND IT SHALL BE LOCATED AT |
| | FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER SECTION |
| | 708.9 ACCESS. |
| | |
| | E} PLEASE KNOW THAT A VENT IS REQUIRED FOR THE WASHING |
| | MACHINE. PER SECTION 901.2.1 VENTING REQUIRED. |
| | |
| | F} PLEASE KNOW THAT WATER-SEAL TRAPS ARE REQUIRED FOR |
| | THE SHOWER AND DOUBLE LAVATORY AND MUST BE CLEARLY |
| | INDICATED ON THE RESUBMITTED ISOMETRIC. SECTION 1002.1 |
| | FIXTURE TRAPS. |
| | |
| | G} PLEASE CLEARLY INDICATE THE REQUIRED TWO-WAY |
| | CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND |
| | BUILDING SEWER. PER SECTION 708.3.5 BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION |
| | *106.3.4.3. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |