2008-10-08 16:01:37PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET PLUMBING ISOMETRIC: PLEASE CORRECT THE
 FOLLOWING ITEMS ON THE PLUMBING ISOMETRIC PER THE
 FBC-2004 PLUMBING CODE SECTIONS.
  
 A} THE WASHING MACHINE MUST DRAIN DOWNSTREAM OF THE
 HORIZONTAL WET-VENT BATHROOM GROUP. ONLY FIXTURES
 WITHIN THE TWO BATHROOM GROUPS LOCATED ON THE SAME
 FLOOR SHALL CONNECT TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. PER SECTION 909.1 WET VENT
 PERMITTED.
  
 B} THE WASHING MACHINE TRAP AND FIXTURE DRAIN FOR THE
 AUTOMATIC CLOTHES WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER.THE AUTOMATIC CLOTHES WASHER FIXTURE
 DRAIN SHALL CONNECT TO A BRANCH DRAIN OR DRAINAGE STACK
 A MINIMUM OF 3 INCHES (76MM) IN DIAMETER. PER SECTION
 406.3 WASTE CONNECTIONS.
  
 C} A STANDPIPE IS REQUIRED FOR THE WASHING MACHINE AND
 SHALL BE INDIVIDUALLY TRAPPED. STANDPIPES SHALL EXTEND
 A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM) ABOVE THE TRAP
 WEIR. ACCESS SHALL BE PROVIDED TO ALL STANDPIPES AND
 DRAINS FOR RODDING. PER SECTION 802.4 STANDPIPES.
  
 D} A CLEANOUT IS REQUIRED FOR THE WASHING MACHINE
 DRAINAGE STACK. THE CLEANOUT SHALL BE 3 INCH (PER
 SECTION 708.7 MINIMUM SIZE) AND IT SHALL BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER SECTION
 708.9 ACCESS.
  
 E} PLEASE KNOW THAT A VENT IS REQUIRED FOR THE WASHING
 MACHINE. PER SECTION 901.2.1 VENTING REQUIRED.
  
 F} PLEASE KNOW THAT WATER-SEAL TRAPS ARE REQUIRED FOR
 THE SHOWER AND DOUBLE LAVATORY AND MUST BE CLEARLY
 INDICATED ON THE RESUBMITTED ISOMETRIC. SECTION 1002.1
 FIXTURE TRAPS.
  
 G} PLEASE CLEARLY INDICATE THE REQUIRED TWO-WAY
 CLEANOUT AT THE JUNCTION OF THE BUILDING DRAIN AND
 BUILDING SEWER. PER SECTION 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 FBC-2004 CHAPTER 1, (W.P.B. AS AMENDED) SECTION
 *106.3.4.3.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]