2008-10-07 08:24:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) THE ENERGY CALCULATIONS ARE ON THE WRONG FORM,
 PLEASE USE FORM 600C-04 R (SOUTH 7 8 9), PER 2004 FBC
 13-600.3.C.
  
 2) WHEN RESUBMITTING THE ENERGY CALCULATIONS THEY MUST
 BE SIGNED BY THE PREPARER AND OWNER/AGENT, PER 2004 FBC
 13-103.3.
  
 3) THE ENERGY CALCULATIONS ARE MISSING AND OR HAVE
 INCORRECT INFORMATION ON THEM (SEE YELLOW HIGH LIGHTS
 ON THEM), PLEASE CORRECT WHEN RESUBMITTING PER 2004 FBC
 13-103.3.
  
 4) SEE MECHANICAL (A/C) PLAN, SOME OF THE DUCTS (FLEX)
 NEEDS TO BE SIZED (SEE YELLOW HIGH LIGHTS ON PLAN),
 PLEASE CORRECT PER 2004 FBC/R M1601.1.
  
 5) THEIR APPEARS TO BE A MIXING BOX MISSING AT THE
 RETURN AIR DUCTS INTERSECTION PLEASE CHECK PLAN AND
 CORRECT IF NEEDED PER 2004 FBC/R M1601.1.
  
 6) PLEASE SHOW ON MECHANICAL PLAN AND ALL PLANS THE JOB
 ADDRESS, PRINTED NAME OF THE PERSON RESPONSIBLE FOR THE
 DESIGN AND THEIR SIGNATURE, PER 2004 WPB AMEND.
 106.1.3.
  