| Plan Review Notes For Permit 08090701 |
| Permit Number |
08090701 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-07 08:24:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | | | | 1) THE ENERGY CALCULATIONS ARE ON THE WRONG FORM, | | | PLEASE USE FORM 600C-04 R (SOUTH 7 8 9), PER 2004 FBC | | | 13-600.3.C. | | | | | | 2) WHEN RESUBMITTING THE ENERGY CALCULATIONS THEY MUST | | | BE SIGNED BY THE PREPARER AND OWNER/AGENT, PER 2004 FBC | | | 13-103.3. | | | | | | 3) THE ENERGY CALCULATIONS ARE MISSING AND OR HAVE | | | INCORRECT INFORMATION ON THEM (SEE YELLOW HIGH LIGHTS | | | ON THEM), PLEASE CORRECT WHEN RESUBMITTING PER 2004 FBC | | | 13-103.3. | | | | | | 4) SEE MECHANICAL (A/C) PLAN, SOME OF THE DUCTS (FLEX) | | | NEEDS TO BE SIZED (SEE YELLOW HIGH LIGHTS ON PLAN), | | | PLEASE CORRECT PER 2004 FBC/R M1601.1. | | | | | | 5) THEIR APPEARS TO BE A MIXING BOX MISSING AT THE | | | RETURN AIR DUCTS INTERSECTION PLEASE CHECK PLAN AND | | | CORRECT IF NEEDED PER 2004 FBC/R M1601.1. | | | | | | 6) PLEASE SHOW ON MECHANICAL PLAN AND ALL PLANS THE JOB | | | ADDRESS, PRINTED NAME OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN AND THEIR SIGNATURE, PER 2004 WPB AMEND. | | | 106.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|