| 2008-11-06 12:00:29 | GAS PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND |
| | WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE |
| | DESGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. "OK" COMMENT ADDRESSED. |
| | |
| | 2. "OK" COMMENT ADDRESSED. |
| | |
| | 3. "OK" COMMENT ADDRESSED. |
| | |
| | 4. "OK" COMMENT ADDRESSED. |
| | |
| | 5. THE SITE PLANS SHOWS THE GENERATOR IN THE |
| | PARKING/DRIVE AREA. PER SECTION 303.4 APPROVED BARRIERS |
| | ARE REQUIRED TO PROTECT THE GAS APPLIANCE. PLEASE |
| | INDICATE ON PLANS. SUBMITA DETAIL FOR THE PROTECTION |
| | METHOD. |
| | |
| | **THE RESUBMITTED GAS ISOMETRIC RISER DIAGRAM STATES |
| | THE FOLLOWING "GENERATOR TO BE PROTECTED FROM TRAFFIC |
| | BY BARRIERS DETAILED, SUPPLIED, AND INSTALLED BY |
| | ELECTRICIAN". PLEASE KNOW THAT THERE IS NO INDICATION |
| | IN THE RESUBMITTAL OF A DETAIL OR A LOCATION OF SAID |
| | BARRIERS. COMMENT HAS NOT BEEN ADDRESSED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |
| | *PLEASE CALL IF THERE ARE ANY QUESTIONS. |
| | |