2008-11-06 12:00:29GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. "OK" COMMENT ADDRESSED.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. "OK" COMMENT ADDRESSED.
  
 4. "OK" COMMENT ADDRESSED.
  
 5. THE SITE PLANS SHOWS THE GENERATOR IN THE
 PARKING/DRIVE AREA. PER SECTION 303.4 APPROVED BARRIERS
 ARE REQUIRED TO PROTECT THE GAS APPLIANCE. PLEASE
 INDICATE ON PLANS. SUBMITA DETAIL FOR THE PROTECTION
 METHOD.
  
 **THE RESUBMITTED GAS ISOMETRIC RISER DIAGRAM STATES
 THE FOLLOWING "GENERATOR TO BE PROTECTED FROM TRAFFIC
 BY BARRIERS DETAILED, SUPPLIED, AND INSTALLED BY
 ELECTRICIAN". PLEASE KNOW THAT THERE IS NO INDICATION
 IN THE RESUBMITTAL OF A DETAIL OR A LOCATION OF SAID
 BARRIERS. COMMENT HAS NOT BEEN ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 *PLEASE CALL IF THERE ARE ANY QUESTIONS.
  