Plan Review Notes
Plan Review Notes For Permit 08090686
Permit Number 08090686
Review Stop G
Sequence Number 1
Notes
Date Text
2008-10-07 11:26:47DENIED
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. GAS RISER DIAGRAM SHOWS TWO SEPARATE GAS LINES FROM
 THE GAS METER. PLEASE CLARIFY. METERS USUALLY HAVE ONE
 INLET AND ONE OUTLET. IF THIS IS THE CASE THEN SHOW THE
 1-1/4" PIPE OUT OF THE METER WITH A 1-1/4" X 1-1/4" X
 1" TEE FOR THE GENERATOR ON THE RISER DIAGRAM. SECTIONS
 106.1.1 & 404.
  
 2. A SHUT OFF VALVE IS REQUIRED UPSTREAM OF THE GAS
 REGULATOR TO THE EXISTING GAS SYSTEM. SECTION 409.4. A
 UNION IS REQUIRED DOWNSTREAM OF THE SHUT OFF VALVE.
  
 3. THE RISER DIAGRAM INDICATES THE BTU LOAD FOR THE
 GENERATOR AT 630,000 BTU'S, BUT THE MANUF.
 SPECIFICATIONS SHOW THE LOAD AT 100% AT 1,374,000 CU FT
 HR. PLEASE CORRELATE RISER INFORMATION WITH MANUF.
 INFORMATION. TOTAL BTU'S SHALL ALSO BE INDICATED.
 SECTION 106.1.1 & TABLE 402.4(3).
  
 4. MANUF. SPECIFICATIONS FOR THE REGULATOR INDICATES
 THE CAPACITY TABLE FOR THE MODEL B42 RESIDENTIAL
 REGULATOR MODELS N, R HAVE A MAXIMUM 820 SCHF. THE
 GENERATOR REQUIRES 1,374,000 BTU'S. PLEASE SUBMIT A
 REGULATOR THAT SHOWS THE CAPACITY REQUIRED FOR THE
 GENERATOR.
  
 5. THE SITE PLAN SHOWS THE GENERATOR IN THE
 PARKING/DRIVE AREA. PER SECTION 303.4 APPROVED BARRIERS
 ARE REQUIRED TO PROTECT THE GAS APPLIANCE. PLEASE
 INDICATE ON PLANS. SUBMIT A DETAIL FOR THE PROTECTION
 METHOD.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  