| Plan Review Notes For Permit 08090686 |
| Permit Number |
08090686 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-21 13:40:30 | ***DENIED*** | | | | | | 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003. | | | | | | 2) WORK TO COMPLY WITH NFPA 110, STANDARD FOR EMERGENCY | | | AND STANDBY POWER SYSTEMS 2005. | | | | | | 3) GENERATOR AND ASSOCIATED EQUIPMENT SHALL BE | | | PROTECTED BY BOLLARDS IF THE POSSIBILITY OF MECHANICAL | | | DAMAGE IS ANTICIPATED. | | | | | | 4) WHAT BUILDING EQUIPMENT AND OR LIFE SAFETY SYSTEMS | | | WILL BE TIED INTO THE GENERATOR? | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | |
|