Plan Review Notes
Plan Review Notes For Permit 08090686
Permit Number 08090686
Review Stop E
Sequence Number 1
Notes
Date Text
2008-10-14 15:15:48 
 ** DENIED REVIEW**
  
  
 1) NOTE: PLEASE SEE FS 527.02 AS THE PRIME CONTRACTOR
 AS APPLIED ON PERMIT APPLICATION IS THE ELECTRICAL
 CONTRACTOR. IF LICENSED TO SELL AND INSTALL GAS
 GENERATORS ETC, PLEASE SUPPLY LICENSE INFORMATION.
 PLEASE VERIFY MULTIPLE LICENSES REQUIRED BY THE
 DEPARTMENT OF AGRICULTURE IN ORDER TO SELL, INSTALL ETC
 GAS APPLIANCES.
 IF NOT LICENSED THE PRIME CONTRACTOR IS REQUIRED TO BE
 THE GAS CONTRACTOR OR OBTAIN LICENSING AS REQUIRED.
  
 2) NOTE: PLEASE COMPLETE RISER WITH ALL CONDUCTORS. THE
 NUMBER OF PARALLEL CONDUCTORS, MISSING EQUIPMENT
 GROUNDING CONDUCTORS, AIC RATINGS FOR ALL NEW
 EQUIPMENT, AND GROUNDING ELECTRIC SYSTEM
 250.50,250.58, 20.56, 110.9, 250.24, 250.110, 250.122
 ETC.
  
 3) NOTE: PLEASE VERIFY WITH FPL THAT ALL METERING AS
 SHOWN NOW ON THE LOAD SIDE OF THE ATS IS PERMITTED.
 PLEASE SEE FPL SERVICE STANDARDS AVAILABLE ON-LINE AT
 FPL.COM.
 A LETTER FROM FPL IS ACCEPTABLE FOR SERVICE AS SHOWN
 WITH NO METERING AS SHOWN ON THE LOAD SIDE OF THE ATS.
 *** IT IS IMPORTANT TO KNOW, AS SHOWN THE CUSTOMER
 WOULD BE PAYING FOR ELECTRICAL BEING FED FROM THE
 GENERATOR EACH TIME THE GENERATOR IS UNDER TEST,
 RUNNING ETC. IF POWER WAS OUT DUE TO AN EVENT SUCH AS A
 HURRICANE, THE OWNER WOULD STILL BE PAYING AN ELECTRIC
 BILL BASED ON THE ELECTRICITY BEING PROVIDED BY THE
 GENERATOR.
  
 4) NOTE: PLEASE KNOW WHEN PLANS FALL UNDER THE
 EXCEPTIONS TO FS 471.003 AND ALLOWS A CONTRACTOR TO
 DESIGN THEIR OWN PROJECTS THAT CONTRACTOR IS STILL
 REQUIRED TO PRINT NAME OF THE COMPANY, ADDRESS, PRINT
 NAME AND SIGNATURE OF SAID DESIGNER OF RECORD TAKING
 RESPONSIBILITY OF SAID PLANS.
 FS 471, 489, FBC 106.5, 106.1.
  
 5) NOTE: NOTES FOR ALL SIGNAGE WILL BE REQUIRED ON
 PLANS AS THE MEANS OF DISCONNECT FOIR ALL FEEDERS ON
 THE LOAD SIAD OF THE ATS IS REQUIRED. 230.2E,
 225.31-225.39, 702.8
  
 6) NOTE: PLEASE INDICATE DEVICES PER 702.7
  
  
  
 ***AS THERE ARE ITEMS NOT YET SHOWN ON PLANS, THERE MAY
 BE NEW COMMENTS ON THE FOLLWOING REVIEW WHICH CAN NOT
 BE MADE AT THIS TIME.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  