| 2008-12-26 13:51:21 | ** PROVISO** |
| | |
| | 1) NOTE: THE FIXTURE TYPES AND NUMBER OF FIXTURES WILL |
| | BE REQUIRED TO BE REVISED TO COORDINATE WITH ALL |
| | FIXTURES ACTUALLY INSTALLED ONCE DETERMINED. SOME |
| | FIXTURE INFORMATION IS NOT COMPLETED AT THIS TIME. THE |
| | MANUFACTURE, FINAL WATTAGE LOCATIONS ETC SHALL BE |
| | COMPLETED BEFORE FINAL INSPECTIONS. |
| | ALL ALLOWANCES TO BE VERIFIED TO MEET FBC 13-415.2 ON |
| | PLAN REVIEW. |
| | AS SHOWN AT THIS TIME SOME FINAL FIXTURE INFORMATION IS |
| | NOT AVAILABLE EVEN THOUGH THE INFORMATION SHOWN DOES |
| | SHOW COMPLIANCE. |
| | |
| | |
| | 2) NOTE: RISER CONTAINS A NOTE FOR TRANSFORMER TO BE |
| | EXPOSED HOWEVER THE WORDING AT THE ACTUAL TRANSFORMER |
| | LOCATION ON PLANS SEEM TO LEND TO THIS BEING ACCESSIBLE |
| | ABOVE 12FT CEILING. |
| | NO CEILING, NO PROVISIONS FOR CEILING ETC SHALL BE |
| | INSTALLED AT THE TRANSFORMER LOCATION. THERE HAVE BEEN |
| | NUMEROUS INSTALLATIONS DONE AFTER COMPLETION OF |
| | PREVIOUS BUILD OUTS IN THE AREA OF CITY PLACE. |
| | PLEASE SEE 450.13B, 450.9. |
| | |
| | 3) NOTE: PLEASE SEE 600.5, 215.3,230.42 ETC AS ALL |
| | CONTINUOUS LOADS SHALL BE FIGURED AT 125%. THE SIGN |
| | CIRCUIT ON PLANS IS SUCH A LOAD WHICH IS REQUIRED TO BE |
| | SHOWN AT 125%. |
| | |
| | |
| | 4) NOTE: PILOT LIGHTS SHALL BE IDENTIFIED ALONE WITH |
| | SCHEDULE OF LIGHTING PER 13-415.1.ABC.1.1, .1.2 AT |
| | LOCATIONS. NO REVISION ON PLANS IS NEEDED THIS WILL BE |
| | VIEWED IN FIELD. |
| | |
| | *** IF THERE IS ANY OTHER REVISIONS BEFORE ROUGH |
| | INSPECTION PLEASE REVISE PLANS FOR NOTES #1, #2 AND #3 |
| | ABOVE. IF NO OTHER REVISIONS ARE MADE, NOTES #1, #2 AND |
| | #3 ABOVE MAY BE DONE BEFORE FINAL. |
| | PLEASE BE SURE TO SUBMIT REVISED PLANS FOR REVIEW AND |
| | STAMPING IN A SUBSTANTIAL AMOUNT OF TIME BEFORE FINAL |
| | ELECTRICAL INSPECTION IS NEEDED. PLANS NEED TO BE ON |
| | SITE FOR INSPECTION. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |