| Date |
Text |
| 2008-11-19 16:06:35 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE |
| | FOLLOWING: |
| | ITEM NO. 4 OK |
| | ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS |
| | NO ITEM. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | ITEM NO. 15 OK |
| | ITEM NO. 30 OK |
| | ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO |
| | ITEM. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | SECTIONS 106.1.1, 601.1 & 701.1. |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING |
| | TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO |
| | THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM. |
| | SECTIONS 106.1.1 & 601.1. |
| | ****RESPONSE NOTED, BUT COMMENTS NOT ADDRESSED. |
| | |
| | 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. THE HAND SINK NEXT TO THE WOK SHOWS 2 HOT |
| | SUPPLY LINES. |
| | ****RESPONSE NOTED, BUT ALL COMMENTS ADDRESS EXCEPT THE |
| | ONE CONCERNING THE HAND SINK ABOVE. |
| | |
| | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION FOR PERMIT: |
| | |
| | A. OK |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE WOK |
| | DOES NOT REFLECT THE BTU LOAD INDICATED ON THE GAS LOAD |
| | CALCULATIONS. PLEASE INDICATE WHICH MODEL WILL BE USED |
| | AND SHOW THAT THE BTU LOAD REFLECTS THE GAS LOAD |
| | CALCULATIONSL. NO MANUF. SHEETS SUBMITTED FOR THE GAS |
| | WATER HEATER. |
| | |
| | C. OK |
| | |
| | D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED |
| | THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL. |
| | INDICATE MODEL. |
| | ****RESPONSE NOTED, BUT NO LISTING IS INDICATED AND NO |
| | 1-1/2" OUTLET IS INDICATED ON ANY MODEL. INDICATE THE |
| | MODEL NUMBER, (MUST SHOW 1-1/2" OUTLET), AND HIGHLIGHT |
| | THE MAXIMUM CAPACITY FOR THE REGULATOR FOR MULTIPLE |
| | APPLIANCES. |
| | |
| | E. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |