Plan Review Notes
Plan Review Notes For Permit 08090682
Permit Number 08090682
Review Stop P
Sequence Number 2
Notes
Date Text
2008-11-19 16:06:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE
 FOLLOWING:
 ITEM NO. 4 OK
 ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS
 NO ITEM.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ITEM NO. 15 OK
 ITEM NO. 30 OK
 ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO
 ITEM.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 SECTIONS 106.1.1, 601.1 & 701.1.
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING
 TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO
 THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM.
 SECTIONS 106.1.1 & 601.1.
 ****RESPONSE NOTED, BUT COMMENTS NOT ADDRESSED.
  
 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. THE HAND SINK NEXT TO THE WOK SHOWS 2 HOT
 SUPPLY LINES.
 ****RESPONSE NOTED, BUT ALL COMMENTS ADDRESS EXCEPT THE
 ONE CONCERNING THE HAND SINK ABOVE.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION FOR PERMIT:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE WOK
 DOES NOT REFLECT THE BTU LOAD INDICATED ON THE GAS LOAD
 CALCULATIONS. PLEASE INDICATE WHICH MODEL WILL BE USED
 AND SHOW THAT THE BTU LOAD REFLECTS THE GAS LOAD
 CALCULATIONSL. NO MANUF. SHEETS SUBMITTED FOR THE GAS
 WATER HEATER.
  
 C. OK
  
 D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED
 THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL.
 INDICATE MODEL.
 ****RESPONSE NOTED, BUT NO LISTING IS INDICATED AND NO
 1-1/2" OUTLET IS INDICATED ON ANY MODEL. INDICATE THE
 MODEL NUMBER, (MUST SHOW 1-1/2" OUTLET), AND HIGHLIGHT
 THE MAXIMUM CAPACITY FOR THE REGULATOR FOR MULTIPLE
 APPLIANCES.
  
 E. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved