Plan Review Notes
Plan Review Notes For Permit 08090682
Permit Number 08090682
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-11-25 14:06:11***DENIED***
  
 SOME COMMENTS HAVE NOT BEEN ADDRESSED FROM THE FIRST
 FIRE REVIEW:
  
 2) THERE STILL APPEARS TO BE CONFLICTING INFORMATION
 REGARDING THE OCCUPANT LOAD. SHEET 1.2A, NOTE #11
 INDICATES MAXIMUM OCCUPANT LOAD OF 229 WHICH DIFFERS
 FROM TOTAL INSIDE OCCUPANCY OF 68. PLEASE CONTACT THE
 BUREAU OF FIRE PREVENTION AT (561) AT 804-4724 FOR
 ASSISTANCE WITH OCCUPANT LOAD CALCULATION. AN OCCUPANT
 LOAD SIGN WILL BE REQUIRED PRIOR TO FINAL LICENSE
 INSPECTION.
  
 4) A NOTE REGARDING FIRE ALARM WORK HAS BEEN ADDED TO
 SHEET 1.2A BUT THE LAYOUT AS REQUESTED FROM THE FIRST
 FIRE REVIEW IS STILL MISSING.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756