Plan Review Notes
Plan Review Notes For Permit 08090682
Permit Number 08090682
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-18 14:31:25 
 ** FAILED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE COMPLETE THE LIGHTING FIXTURE LEGEND
 WITH ALL LIGHTING FIXTURES SPECIFIC TO WATTAGE ETC.
 PLANS NEED TO SHOW AT LEAST *MINIMUM* CODE COMPLIANCE
 AT TIME OF ISSUANCE. THE FIXTURES CAN ALWAYS BE REVISED
 AT A LATER DATE ONCE THE FINAL FIXTURE IS KNOWN.
 THIS COMMENT REMAINS MORE SPECIFIC TO TRACK LIGHTING AS
 TRACK LIGHTING IS ACTUALLY BLANK ON THE LEGEND. PLEASE
 ALSO SEE THAT THERE ARE TWO E FIXTURE DESIGNATIONS.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2 FOR TRACK LIGHTING.
 THE VA RATING OF THE FIXTURE OR 30VA PER FT WHICH EVER
 IS GREATER IS REQUIRED TO BE USED.
  
 PLEASE CONFIRM ALL AND REVISE.
  
 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3. THE
 OCCUPANT IS REQUIRED TO SEE ALL LIGHTING WHICH IS BEING
 CONTROLLED. CONTROLS/OVER RIDES ARE REQUIRED AT POINT
 OF ENTRANCE INTO ANY ONE AREA/SPACE OR MEET EXCEPTIONS.
 PLEASE ADD CONTROL LOCATIONS OR SHOW HOW EXCEPTIONS ARE
 MET.
 THE NOTE ON SHEET 2.1E STATES KEYPADS REQUIRED HOWEVER
 ONLY LOCATED ONE ON PLANS.
  
 3) NOTE: THE TERMINATION OF THE TAPPED CONDUCTORS ON
 THE SECONDARY SIDE OF THE TRANSFORMER DOES NOT MEET
 240.21. THE PANEL *A* IS TOO FAR AWAY.
 PLEASE ADD DISCONNECTING MEANS WITH OVER CURRENT
 PROTECTION. DOES NOT MEET 240.21B3, MUST BE WITHIN
 10FT.
  
 4) NOTE: NOTE #17 ON PLANS MENTIONS INTERLOCK OF ALL
 ELECTRICAL CIRCUITS WITH FIRE SUPPRESSION HOWEVER COULD
 NOT LOCATE THE INDICATION OF ANY SHUNT TRIP TYPE
 BREAKERS?
 NFPA-96
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO
 APPLIED VALUE FOR THE SCOPE OF WORK. THE VALUE ON
 PERMIT APPLICATION DID NOT CHANGE.
  
 6) NOTE: NEW NOTE: PLEASE SHOW LOCATIONS OF FIRE ALARM
 DEVICES FOR MINIMUM DESIGN ON BASE PLANS. EVEN AS THE
 FIRE ALARM PERMIT WILL BE SEPARATE PER FS 633 THE BASE
 PLANS NEED TO SHOW THE DEVICE LOCATIONS FOR CODE
 COMPLIANCE.
 PLEASE SHOW LOCATIONS AND LEVELS FOR ADA COMPLIANCE PER
 FBC 11-4.2, 11-4.28.1,.2 AND .3.
 RESPONSE TO FIRE REVIEW STATES THESE ARE ALL ON REVISED
 LIFE SAFETY PLANS HOVE
 THIS WAS NOT ON PREVIOUS REVIEW NOTES HOWEVER THIS IS
 REQUIRED.
 FBC 907.2.1, 303.1
  
 7) NOTE: PLEASE COORDINATE NOTE ON COVER SHEET FOR SIZE
 OF ELECTRICAL SERVICE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  