| Date |
Text |
| 2008-11-18 14:31:25 | |
| | ** FAILED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE COMPLETE THE LIGHTING FIXTURE LEGEND |
| | WITH ALL LIGHTING FIXTURES SPECIFIC TO WATTAGE ETC. |
| | PLANS NEED TO SHOW AT LEAST *MINIMUM* CODE COMPLIANCE |
| | AT TIME OF ISSUANCE. THE FIXTURES CAN ALWAYS BE REVISED |
| | AT A LATER DATE ONCE THE FINAL FIXTURE IS KNOWN. |
| | THIS COMMENT REMAINS MORE SPECIFIC TO TRACK LIGHTING AS |
| | TRACK LIGHTING IS ACTUALLY BLANK ON THE LEGEND. PLEASE |
| | ALSO SEE THAT THERE ARE TWO E FIXTURE DESIGNATIONS. |
| | PLEASE SEE 13-415.2.ABC.1.1,.1.2 FOR TRACK LIGHTING. |
| | THE VA RATING OF THE FIXTURE OR 30VA PER FT WHICH EVER |
| | IS GREATER IS REQUIRED TO BE USED. |
| | |
| | PLEASE CONFIRM ALL AND REVISE. |
| | |
| | 2) NOTE: PLEASE SEE 13-415.1.ABC.1.1,.1.2, .1.3. THE |
| | OCCUPANT IS REQUIRED TO SEE ALL LIGHTING WHICH IS BEING |
| | CONTROLLED. CONTROLS/OVER RIDES ARE REQUIRED AT POINT |
| | OF ENTRANCE INTO ANY ONE AREA/SPACE OR MEET EXCEPTIONS. |
| | PLEASE ADD CONTROL LOCATIONS OR SHOW HOW EXCEPTIONS ARE |
| | MET. |
| | THE NOTE ON SHEET 2.1E STATES KEYPADS REQUIRED HOWEVER |
| | ONLY LOCATED ONE ON PLANS. |
| | |
| | 3) NOTE: THE TERMINATION OF THE TAPPED CONDUCTORS ON |
| | THE SECONDARY SIDE OF THE TRANSFORMER DOES NOT MEET |
| | 240.21. THE PANEL *A* IS TOO FAR AWAY. |
| | PLEASE ADD DISCONNECTING MEANS WITH OVER CURRENT |
| | PROTECTION. DOES NOT MEET 240.21B3, MUST BE WITHIN |
| | 10FT. |
| | |
| | 4) NOTE: NOTE #17 ON PLANS MENTIONS INTERLOCK OF ALL |
| | ELECTRICAL CIRCUITS WITH FIRE SUPPRESSION HOWEVER COULD |
| | NOT LOCATE THE INDICATION OF ANY SHUNT TRIP TYPE |
| | BREAKERS? |
| | NFPA-96 |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO |
| | APPLIED VALUE FOR THE SCOPE OF WORK. THE VALUE ON |
| | PERMIT APPLICATION DID NOT CHANGE. |
| | |
| | 6) NOTE: NEW NOTE: PLEASE SHOW LOCATIONS OF FIRE ALARM |
| | DEVICES FOR MINIMUM DESIGN ON BASE PLANS. EVEN AS THE |
| | FIRE ALARM PERMIT WILL BE SEPARATE PER FS 633 THE BASE |
| | PLANS NEED TO SHOW THE DEVICE LOCATIONS FOR CODE |
| | COMPLIANCE. |
| | PLEASE SHOW LOCATIONS AND LEVELS FOR ADA COMPLIANCE PER |
| | FBC 11-4.2, 11-4.28.1,.2 AND .3. |
| | RESPONSE TO FIRE REVIEW STATES THESE ARE ALL ON REVISED |
| | LIFE SAFETY PLANS HOVE |
| | THIS WAS NOT ON PREVIOUS REVIEW NOTES HOWEVER THIS IS |
| | REQUIRED. |
| | FBC 907.2.1, 303.1 |
| | |
| | 7) NOTE: PLEASE COORDINATE NOTE ON COVER SHEET FOR SIZE |
| | OF ELECTRICAL SERVICE. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |