| Date |
Text |
| 2008-10-02 10:55:47 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SHT C-1 GENERAL NOTES #1 TO INCLUDE 2005, 2006 & |
| | 2007 REVISIONS/AMENDMENTS TO THE 2004 FLORIDA BUILDING |
| | CODE AND THE JURISDICATION OF AUTHORITY IS THE CITY OF |
| | WEST PALM BEACH, NOT ROYAL PALM BEACH. PLEASE UPDATE |
| | GENERAL NOTE #1. SECTION 106.1.3. |
| | |
| | 2. SHT 1.1A EQUIPMENT SCHEDULE. PLEASE CLARIFY THE |
| | FOLLOWING: |
| | ITEM NO. 4 MOP SINK SHOWS NO WATER SUPPLIES NOR DRAIN. |
| | ITEM BETWEEN 9 & 10 SHOWS 1/2" WATER SUPPLIES BUT SHOWS |
| | NO ITEM. |
| | ITEM NO. 15 HAND SINKS SHOWS NO WATER SUPPLIES NOR |
| | DRAIN. |
| | ITEM NO. 30 HAND SINK SHOWS NO WATER SUPPLIES NOR |
| | DRAIN. |
| | ITEM BETWEEN 31 & 32 SHOWS 3/4" INDIRECT WASTE BUT NO |
| | ITEM. |
| | SECTIONS 106.1.1, 601.1 & 701.1. |
| | |
| | 3. SHT 3.0P SANITARY RISER. DISH WASHER SHALL DRAIN |
| | INTO THE SANITARY SYSTEM, NOT THE GREASE SYSTEM. |
| | ARTICLE III SECTION 90-124(7)(B). |
| | |
| | 4. SHT 3.0P SANITARY RISER SHALL BE LABELED AS THE |
| | GREASE RISER DIAGRAM. FIXTURE SHOWN TO THE RIGHT OF THE |
| | TRENCH DRAIN SHALL BE IDENTIFIED, (INDICATED AS |
| | "STUDOR"). |
| | |
| | 5. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY |
| | DEPARTMENT, INDUSTRIAL PRETREATMENT. PLEASE CONTACT |
| | HOLLY MCGRATH LABORATORY SUPERVISOR BY PHONE AT (561) |
| | 822-2271, OR BY FAX AT (561) 822-2279, OR BY E-MAIL AT |
| | [email protected]. A WRITTEN DETERMINATION OR E-MAIL |
| | FROM ENVIRONMENTAL COMPLIANCE IS REQUIRED. ARTICLE III |
| | SECTION 90-124(7). |
| | |
| | 6. SHT P3.0P PLUMBING PLAN. EXPLAIN THE SANITARY LINE |
| | SHOWN PAST THE FLOOR SINK TO THE 3 COMPARTMENT SINK. |
| | SECTIONS 106.1.1, 701.1 & 901.1. |
| | |
| | 7. SHT 3.0P PLUMBING PLAN SHOWS NO WATER SUPPLY PIPING |
| | TO THE 3 COMPARTMENT SINK & SHOWS 2 HOT SUPPLY LINES TO |
| | THE HAND SINK. PLEASE CORRELATE WITH RISER DIAGRAM. |
| | SECTIONS 106.1.1 & 601.1. |
| | |
| | 8. SHT 3.2P WATER RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. THE TOILET ROOM W/C & LAV SHOWN ON THE |
| | RIGHT SIDE OF THE TENANT SUPPLY LINE ON THE PLUMBING |
| | PLAN IS SHOWN ON THE LEFT SIDE OF THE TENANT SUPPLY |
| | LINE ON THE RISER DIAGRAM. THE SUPPLY LINE TO THE W/C |
| | IN THE OTHER TOILET ROOM IS NOT SHOWN ON THE RISER |
| | DIAGRAM. IDENTIFY THE LAV IN THE SECOND BATH. THE HAND |
| | SINK NEXT TO THE WOK SHOWS 2 HOT SUPPLY LINES. THE GATE |
| | VALVE AND SUBMETER INDICATED ON THE RISER DIAGRAM IS |
| | NOT SHOWN ON THE PLUMBING PLAN. PLEASE CORRELATE. |
| | SECTIONS 106.1.1 & 106.1. |
| | |
| | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION FOR PERMIT: |
| | |
| | A. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2 |
| | PSI SYSTEM AND THE .5 PSI SYSTEMS. |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR |
| | THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL |
| | SHALL BE INSTALLED BELOW THE CEILING. |
| | |
| | D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED |
| | THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL. |
| | INDICATE MODEL. |
| | |
| | E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS |
| | INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |