| 2008-10-02 10:59:18 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | 1. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE |
| | FOLLOWING INFORMATION FOR PERMIT: |
| | |
| | A. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). THIS IS REQUIRED FOR THE 2 |
| | PSI SYSTEM AND THE .5 PSI SYSTEMS. |
| | |
| | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | C. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. THIS IS ALSO REQUIRED FOR |
| | THE S.O.V AND REGULATOR. A UNION IS REQUIRED AND ALL |
| | SHALL BE INSTALLED BELOW THE CEILING. |
| | |
| | D. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE |
| | REGULATOR. SHEETS SHALL SHOW A LISTING AND INDICATED |
| | THE TOTAL BTU LOAD APPLICABLE FOR THE REGULATOR MODEL. |
| | INDICATE MODEL. |
| | |
| | E. MINIMUM SIZE 1" REQUIRED TO THE RANGE. 3/4" IS |
| | INDICATED IN GAS LOAD CALCULATIONS. TABLE 402.4(2). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |