| Date |
Text |
| 2008-10-09 14:45:06 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE FS 471.023, FAC 61G15-23.002. THE |
| | SCOPE OF WORK AS SHOWN IS REQUIRED TO BE DONE BY AN |
| | ENGINEER. ANY FIRMS PROVIDING THAT SERVICE IS REQUIRED |
| | TO HAVE AN ENGINEERING BUSINESS LICENSE NUMBER ALSO |
| | KNOWN AS A CERTIFICATE OF AUTHORIZATION NUMBER. THIS IS |
| | THE SAME AS AN ARCHITECTURAL FIRM PROVIDING |
| | ARCHITECTURAL SERVICES. METRO DESIGN GROUP NOW SHOWS |
| | THE ARCHITECTURAL FIRM LICENSE NUMBER ON PLANS HOWEVER |
| | NOT INDICATE THE ENGINEERING BUSINESS LICENSE NUMBER. |
| | PLEASE INCLUDE AS REQUIRED. |
| | ** THIS WAS CONFIRMED WITH THE STATE BOARD OF ENGINEER |
| | WHEN PROVIDING ENGINEERING SERVICES. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER SHOWS A NEUTRAL FROM |
| | PANEL *H* TO TRANSFORMER WHICH IS NOT PERMITTED AS THIS |
| | IS A SEPARATELY DERIVED SYSTEM. |
| | 250.6.250.24, 250.20, 250.30, 250.50, 250.66 ETC |
| | |
| | 3) NOTE: PLEASE PROVIDE THE GROUNDING ELECTRODE SYSTEM |
| | AND ATTACHMENT FOR NEW TRANSFORMER PER THE SAME CODE |
| | SECTIONS NOTED IN NOTE #2 ABOVE. |
| | |
| | 4) NOTE: PLEASE 450.13 AS THE 75KVA TRANSFORMER AS |
| | SHOWN IS NOT PERMITTED ABOVE THE CEILING AS NOTED ON |
| | RISER. |
| | |
| | 5) NOTE: PLEASE INDICATE THE SIZE OF THE EXISTING |
| | SERVICE WITH THE CURRENT EXISTING LOADS WITH NEW LOADS |
| | BEING ADDED. |
| | NEC 220.87, 220 PART II, III, IV. |
| | |
| | 6) NOTE: PLEASE SEE 220.43A FOR SHOWS WINDOWS AND THE |
| | AMOUNT OF LOAD REQUIRED FOR SERVICE. THE LOAD SHOWN ON |
| | PANEL SCHEDULE IS THE LOADS PER 220.14G WHICH IS THE |
| | BRANCH CIRCUIT. |
| | |
| | 7) NOTE: PLEASE COMPLETE PLANS/PANEL SCHEDULE FOR |
| | SHUNT/SHUT DOWN OF ALL ELECTRICAL UNDER HOOD. NFPA-96 |
| | FOR EXAMPLE: PLEASE SEE THE HOOD LIGHTS DO NOT INDICATE |
| | SHUNT BREAKER? |
| | |
| | 8) NOTE: PLEASE SUBMIT A COMPLETE LIGHTING CONTROL |
| | SYSTEM SHOWING ALL OVER RIDE LOCATIONS AND ALL OVER |
| | RIDE DEVICES FOR GENERAL LIGHTING AS WELL AS OTHER |
| | ACCENT/DECRETIVE LIGHTING ETC. |
| | PLEASE BE SURE TO ALSO SEE THE SECTION FOR EXTERIOR |
| | LIGHTING CONTROLS. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | EXTERIOR PER 13-415.1.ABC.1.4. |
| | |
| | 9) NOTE: PLEASE SUBMIT A COMPLETED LIGHTING FIXTURE |
| | LEGEND. PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE KNOW THE FIXTURE SCHEDULE MUST BE COMPLETE AT |
| | THIS TIME FOR LIGHTING PERFORMANCE VERIFICATION. |
| | ** AREAS AND ROOMS NOTED ON THE LIGHTING CONTROL PANEL |
| | DOES NOT COORDINATE WITH ANY ROOMS DESIGNATED ON PLANS. |
| | |
| | 10) NOTE: PLEASE SEE THE CODES NOTED ON PLANS SHALL BE |
| | CODES ADOPTED BY THE FBC 2004 W/2007 REVISION PER FS |
| | 553.73. |
| | PLEASE SEE THE JURISDICTION FOR EXAMPLE NOTES ROYAL |
| | PALM BEACH HOWEVER JOB LOCATION IS IN THE CITY OF WEST |
| | PALM BEACH. (MISPRINT). |
| | |
| | 11) NOTE: PLEASE SEE THE APPLIED VALUE SHALL INCLUDE |
| | ALL LABOR, MATERIALS, EQUIPMENT, DEISGN COSTS ETC PER |
| | FBC 108.3 EVEN IF ANY OF THESE ITEMS ARE OWNER |
| | SUPPLIED. THE VALUE FOR SCOPE OF WORK AS SHOWN IS LOW. |
| | |
| | |
| | |
| | ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE SOME |
| | ITEMS NOT YET SUBMITTED OR SHOWN FOR REVIEW THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |