| 2008-09-29 14:15:01 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE A COMPLETE INSTALLATION SCHEDULE AS REQUIRED |
| | BY THE CITY IMPLEMENTATION STANDARD FOR WIND-BORNE |
| | DEBRIS IMPACT PROTECTION. SEE ATTACHED SAMPLE. |
| | |
| | 2- PROPERTY IS LOCATED ON EXPOSURE AS REQUIRED BY SEC. |
| | R301.2.1.4(3) OF 2004 FLORIDA RESIDENTIAL CODE. TAKE |
| | THIS INTO CONSIDERATION WHEN CALCULATING THE DESIGN |
| | PRESSURES FOR EACH OPENING (NOTE: YOU MAY USE THE |
| | FOLLOWING DESIGN PRESSURES +42.7 AND -57.1, WHICH ARE |
| | TAKEN FROM TABLE R301.2.(3) OF 2004 FLORIDA RESIDENTIAL |
| | CODE. OTHERWISE PROVIDE CALCULATIONS FOR EACH OPENING). |
| | |
| | 3- ANCHOR SCHEDULE ON PRODUCT APPROVAL SUBMITTED TAKES |
| | INTO CONSIDERATION ANCHOR INSTALLATION AT EDGE DISTANCE |
| | OF 3 1/2". SEE CHART ON SHEET 14 OF DRAWINGS SUBMITTED. |
| | IF EDGE DISTANCE IS LESS THAN 3 1/2", THEN ANCHOR |
| | SPACING MUST BE REDUCED ACCORDING TO THIS CHART. |
| | NOTE: SHUTTER SPAN COLUMN AND EDGE DISTANCE COLUMN OF |
| | CITY INSTALLATION SCHEDULE SAMPLE MUST BE COORDINATED. |
| | BLADE LENGTH SHOWN ON THE MEASURE FORM DOESN'T PROVIDE |
| | ENOUGH LENGTH TO GET THE 3 1/2" EDGE DISTANCE. REVISE |
| | AS REQUIRED. |
| | |
| | 4- ANCHOR SPACING HIGHLIGHTED ON SHEET 13 OF SHUTTERS |
| | IS INCORRECT. THE ANCHOR SPACING THAT CORRESPONDS TO |
| | THE TAPCON ANCHOR IS 7" NOT 10". REVISE AS REQUIRED. |
| | |