2008-10-02 09:09:02GAS PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 **THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND
 WITH THE PREVIOUS GAS PLAN REVIEW COMMENTS AS WELL AS
 THE DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY.
 NEW COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS
 REVIEW COMMENTS DUE TO THE REVISED RESUBMITTED GAS
 ISOMETRIC RISER DIAGRAM.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTION OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 WITH NO CORRESPONDING LENGTHS AND COMPLY ON THE
 RESUBMITTAL.
  
 **COMMENT RESPONSE NOTED, HOWEVER THE HAS ONLY BEEN
 PARTIALLY ADDRESSED. PLEASE REFERENCE THE YELLOW HIGH
 LIGHTED PIPE CUT SECTIONS STIIL WITH NO CORRESPONDING
 LENGTHS.
  
 2. "OK", COMMENT ADDRESSED.
  
 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 **COMMENT RESPONSE NOTED, HOWEVER THE RESUBMITTED GAS
 ISOMETRIC RISER DIAGRAM STILL DOES NOT CLEARLY INDICATE
 THE GAS TYPE. PLEASE CORRELATE THE PLANS WITH THE
 PERMIT APPLICATION AND THE COMMENT RESPONSE AND CLEARLY
 INDICATE THE GAS TYPE ON THE RESUBMITTED PLANS.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: PLEASE REFERENCE COMMENT #1 AND COMPLY.
  
 **RESPONSE NOTED, HOWEVER PLEASE REFERENCE COMMENT #1
 AND COMPLY.
  
 5. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATOR, POOL
 HEATER AND GRILLS TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC
 402.2. MANUFACTURE SHEETS SHALL CLEARLY INDICATE THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY SUCH AS
 CSA, AGA, OR UL.
  
 **COMMENT RESPONSE NOTED AND COMMENT WAS PARTIALLY
 ADDRESSED. MANUFACTURE SHEETS FOR THE POOL HEATER AND
 GRILLS ARE STILL REQUIRED.
  
 6. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR, MATERIALS AND THE THREE GAS APPLIANCES.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF A NATIONAL CONSTRUCTION COST ANALYSIS
 (MARSHALL-SWIFT, MEANS, ECT...) ADJUST THE VALUE AT THE
 PERMIT CLERK'S DESK AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
 NOTE: IF APPLIANCES ARE NOT BEING INSTALLED AT THIS
 TIME THEN DESIGNATE THE APPLIANCES AS "FUTURE" AND
 INDICATE THAT THEY WILL BE CAPPED GAS TIGHT PER
 FBC-2004 FUEL GAS SECTION 404.12 OUTLET CLOSERS.
  
 **COMMENT RESPONSE NOTED, HOWEVER IS IT YOUR INTENT TO
 MAKE THE FINAL HOOK UP TO THE APPLIANCES PROVIDED BY
 "OTHERS" WITH THIS PERMIT? THE VALUE OF THE PERMIT
 SHOULD REFLECT THE TOTAL COST OF THE JOB INCLUDING THE
 COST OF THE APPLIANCES NO MATTER WHO THEY ARE SUPPLIED
 BY. PER MARSHALL & SWIFT VALUATION A 400,000 BTU GAS
 POOL HEATER COSTS AROUND $3000.00 AND THATS NOT
 INCLUDING THE COST OF THE TWO GRILLS. THE VALUE
 INDICATED ON YOUR PERMIT APPLICATION ONLY REFLECTS THE
 PIPING LABOR, MATERIAL AND DESIGN COSTS.
 PER (W.P.B. AS AMENDED SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING ALTERATION,
 STRUCTURE, ELECTRIC, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED.
  
 7. "OK", COMMENT ADDRESSED.
  
 **THE FOLLOWING IS A NEW COMMENT DUE TO THE RESUBMITTED
 GAS ISOMETRIC**
  
 8. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  