Plan Review Notes
Plan Review Notes For Permit 08090638
Permit Number 08090638
Review Stop G
Sequence Number 1
Notes
Date Text
2008-09-26 11:07:26GAS PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE
 CORRESPONDING LENGTHS TO ALL CUT SECTION OF PIPE.
 PLEASE REFERENCE THE YELLOW HIGH LIGHTED CUT SECTIONS
 WITH NO CORRESPONDING LENGTHS AND COMPLY ON THE
 RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
 *NOTE: THE SUBMITTED ISOMETRIC DOES NOT CLEARLY
 INDICATE THE ABOVE GROUND PIPING MATERIAL TO ALL CUT
 SECTIONS OF PIPE.
  
 3. CLEARLY INDICATE THE TYPE OF GAS, (LP OR NATURAL)
 BEING USED. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 *NOTE: PLEASE REFERENCE COMMENT #1 AND COMPLY.
  
 5. SUBMIT MANUFACTURE SHEETS FOR THE MP REGULATOR, POOL
 HEATER AND GRILLS TO VERIFY COMPLIANCE WITH STANDARDS
 NFPA 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC
 402.2. MANUFACTURE SHEETS SHALL CLEARLY INDICATE THE
 MAKE, MODEL NUMBER, BTU LOAD CAPACITY, AND A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY SUCH AS
 CSA, AGA, OR UL.
  
 6. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR, MATERIALS AND THE THREE GAS APPLIANCES.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF A NATIONAL CONSTRUCTION COST ANALYSIS
 (MARSHALL-SWIFT, MEANS, ECT...) ADJUST THE VALUE AT THE
 PERMIT CLERK'S DESK AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING. PER (W.P.B. AS AMENDED) SECTION
 108.3 BUILDING PERMIT VALUATION.
 NOTE: IF APPLIANCES ARE NOT BEING INSTALLED AT THIS
 TIME THEN DESIGNATE THE APPLIANCES AS "FUTURE" AND
 INDICATE THAT THEY WILL BE CAPPED GAS TIGHT PER
 FBC-2004 FUEL GAS SECTION 404.12 OUTLET CLOSERS.
  
 7. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 *NOTE: PLEASE CLEARLY PRINT THE NAME OF THE PERSON WHO
 IS TAKING RESPONSIBILITY OF THE ISOMETRIC WHOSE
 SIGNATURE APPEARS ON THE PLANS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]