| 2008-10-06 09:31:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | |
| | 1) SHOW ON THE SURVEYS THE PURPOSED LOCATION OF THE |
| | GENERATOR. |
| | |
| | NOTICE; PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT |
| | PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL |
| | COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| | WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA |
| | 37. |
| | |
| | NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| | ENGINES & GAS TURBINES: 4.1.4 ENGINES (GENERATORS) |
| | LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS |
| | IN WALLS (DOORS AND WINDOWS) & AT LEAST 5 FT FROM |
| | STRUCTURES HAVING COMBUSTIBLE WALLS. A MINIMUM |
| | CLEARANCE IS NOT REQUIRED WHEN (1) THE ADJACENT WALL |
| | HAS A MINIMUM FIRE RESISTANCE RATING OF 1 HOUR OR (2) |
| | THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF |
| | NON-COMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED |
| | THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE |
| | COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| | INFORMATIVE: A.8.2.3.1 EXHAUST SYSTEMS SHOULD NOT |
| | TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT |
| | BE DRAWN INTO THE VENTILATION INTAKES. |
| | |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS LOCATED |
| | BELOW AN ADJACENT ROOF STRUCTURE, THE TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF STRUCTURE. |
| | |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL EQUIPMENT |
| | TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, GENERATORS |
| | SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED CLEARANCES |
| | TO THE ADJACENT PROPERTY STRUCTURES, I.E. FENCE, |
| | BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND |
| | EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS AT THE JOBSITE FOR THE FIELD |
| | INSPECTOR. |
| | |