| Plan Review Notes For Permit 08090617 |
| Permit Number |
08090617 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-10-09 14:13:41 | RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW | | | CHECKLIST. | | | REVIEW UNDER 2004 FLORIDA RESIDENTIAL CODE WITH 2007 | | | REVISIONS. | | | | | | 1- A) ENGINEER'S DRAWING FOR THE SKYLIGHT ATTACHMENT TO | | | THE ROOF PANEL NEEDS TO HAVE ORIGINAL ENGINEER'S SEAL | | | AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTE AND SEC. 61G15-23.002 OF FLORIDA ENGINEERS | | | ADMINISTRATIVE CODE. THIS DRAWING IS NOT PART OF THE | | | PRODUCT APPROVAL SUBMITTED. THEREFORE, ORIGINAL | | | SIGNATURE AND SEAL IS REQUIRED. | | | | | | B) PLEASE MAKE SURE ENGINEER INFORMATION, INCLUDING | | | LICENSE NUMBER IS LEGIBLE. | | | | | | 2- ACCORDING TO SKYLIGHT PRODUCT APPROVAL FL2442 | | | SKYLIGHT MODELS SF ARE REQUIRED TO HAVE A MINIMUM ROOF | | | PITH OF 3:12.. SKYLIGHT FL2442.13 SPECIFIED BY THE | | | ENGINEER IS A SF MODEL. SPECIFY ROOF PITCH ON PLANS TO | | | VERIFY COMPLIANCE WITH THIS PRODUCT APPROVAL | | | REQUIREMENT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|