Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop P
Sequence Number 9
Notes
Date Text
2009-07-30 18:45:32REVISION DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CAHPTER 11
  
 1. SHTS P-1 & P-1B INDICATE WHERE THE SANITARY BUILDING
 DRAIN CONNECTS TO THE BUILDING SEWER FOR THE FIXTURES
 AT THE EQUIPMENT SANITARY. SECTION 701.3.
  
 2. SHTS P-1 & P-1B FITTING FOR FLOOR DRAIN DOWS NOT
 ALLOW THE SEWAGE/WASTE TO BE GUIDED IN THE DIRECTION OF
 FLOW. SECTION 706.3.
  
 3. SHTS P-1 & P-1A GREASE EATING BACTERIA. PLEASE
 SUBMIT MANUF. SPECIFICATION ON SYSTEM. SECTION 106.1.2,
 (MORE INFORMATION REQUIRED).
  
 4. SHT P-1 3 INCH SANITARY FROM 2ND FLOOR TO DRYWELL IS
 PROHIBITED. SECTION 301.3.
  
 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER
 TABLES 1004.1.1, (BLDG) & 403.1, (PLMG). INDICATE THE
 SQUARE FOOTAGE & OCCUPANCY LOAD FOR ALL OCCUPANCIES,
 ASSEMBLY, BUSINESS, STORAGE ETC. INDICATE THE TOTAL
 OCCUPANCY INCLUDING ALL NEW SEATING. ALSO SHOW POTTY
 PARITY AS REQUIRED IN SECTION 403.1.1.
  
 6. SHT 310 DETAIL #6 BATHROOM TO BE ADAPTABLE. SUBMIT
 INFORMATION ON DETAIL SHOWING ALL BACKING FOR REQUIRED
 GRAB BARS IN THE SHOWER AND AT THE WATER CLOSET
 SECTIONS 11-4.16.4 & 11-4.21.4. INDICATE THE W/C TO BE
 18" OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. (FIG
 28). SHOW THE REQUIRED TURNING AREA IN THE BATHROOM.
 11-4.23.3.
  
 7. SHT P-1A DETAIL 3. INCOMPLETE INFORMATION ON THE
 LEFT SIDE OF DETAIL. PLEASE CLARIFY. SECTIONS 106.1.1 &
 106.1.2.
  
 8. SHT P-2B INDICATE WHERE THE WATER HEATER PAN DRAIN
 LINE TERMINATES. SECTION 504.7.2.
  
 9. SHT P-3A THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE.
 PLEASE ADDRESS THE FOLLOWING:
 - THE CLEANOUTS REQUIRED BY SECTIONS 708.3.2 & 708.3.5
 SHOWN ON THE FLOOR PLAN ARE MISSING ON THE RISER.
 - THE FITTING AT THE JUNCTION OF THE BUILDING DRAIN &
 THE BUILDING SEWER AT THE N.W. CORNER OF THE BUILDING
 DOES NOT GUIDE THE SEWAGE/WASTE IN THE DIRECTION OF
 FLOW. SECTION 706.3.
 - PIPING TO THE W/C & LAV IN THE MEN'S LOCKER ROOM DOES
 NOT REFLECT THE FLOOR PLAN. SECTION 701.1.
 - THE VENT IS MISSING IN ONE GANG SHOWER BUT IS SHOWN
 ON THE FLOOR PLAN. SECTION 901.1.
 - FLOOR DRAINS IN THE GANG BATH ON THE SECOND FLOOR ARE
 SHOWN BETWEEN THE LAST W/C & THE NEXT TO LAST W/C ON
 THE FLOOR PLAN, BUT AFTER ALL W/C'S ON THE RISER
 DIAGRAM. SECTION 701.1. PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  