2009-08-10 19:17:44REVIEW #: 2ND (PHASE 2)
 ACTION: **PASSED WITH PROVISO**
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 2. SUBMITTAL FOR RECIRCULATING SYSTEMS WAS RECEIVED.
 HOWEVER, THE COMMERCIAL KITCHEN AREA STILL REQUIRES AN
 OVERALL EXHAUST RATE OF 0.7 CFM PER SQ FT IN ACCORDANCE
 WITH ASHRAE 62.1-2004 TABLE 6-4. REVISE PLANS
 ACCORDINGLY AND RESUBMIT.
  
 6. WRITTEN RESPONSE INDICATES WIND RESISTANCE FOR
 MECHANICAL APPLIANCES IS A 2007 CODE REQUIREMENT. THIS
 IS INCORRECT. THE SAME REQUIREMENTS ARE IN PLACE UNDER
 THE 2004 FBC. PROVIDE MANUFACTURERS WIND RESISTANCE
 DATA FOR ALL OUTDOOR APPLIANCES IN ACCORDANCE WITH
 FBC-M 2004 EDITION SECTION 301.13.
  
 NOTE: PREVIOUS MECHANICAL PLANS (PAGE M-1 AIR BALANCE
 SCHEDULE) SHOWED A MODULATING 100% OUTSIDE AIR
 DEHUMIDIFACTION UNIT PROVIDING 9000 CFM OUTSIDE AIR IN
 THE SKATING RINK AREA VIA DUCT SOCK. THIS UNIT SHALL
 NOT BE CONSIDERED AS ELIMINATED BASED ON THESE
 REVISIONS. ELIMINATION OF THIS UNIT WOULD LEAVE THE
 RINK AND SPECTATOR AREAS WITHOUT VENTILATION AS
 REQUIRED UNDER ASHRAE 62.1-2004. THIS UNIT IS STILL
 SHOWN ON PERMIT PLANS ON PAGE M-2-IRB.
  