| 2009-08-10 19:17:44 | REVIEW #: 2ND (PHASE 2) |
| | ACTION: **PASSED WITH PROVISO** |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 2. SUBMITTAL FOR RECIRCULATING SYSTEMS WAS RECEIVED. |
| | HOWEVER, THE COMMERCIAL KITCHEN AREA STILL REQUIRES AN |
| | OVERALL EXHAUST RATE OF 0.7 CFM PER SQ FT IN ACCORDANCE |
| | WITH ASHRAE 62.1-2004 TABLE 6-4. REVISE PLANS |
| | ACCORDINGLY AND RESUBMIT. |
| | |
| | 6. WRITTEN RESPONSE INDICATES WIND RESISTANCE FOR |
| | MECHANICAL APPLIANCES IS A 2007 CODE REQUIREMENT. THIS |
| | IS INCORRECT. THE SAME REQUIREMENTS ARE IN PLACE UNDER |
| | THE 2004 FBC. PROVIDE MANUFACTURERS WIND RESISTANCE |
| | DATA FOR ALL OUTDOOR APPLIANCES IN ACCORDANCE WITH |
| | FBC-M 2004 EDITION SECTION 301.13. |
| | |
| | NOTE: PREVIOUS MECHANICAL PLANS (PAGE M-1 AIR BALANCE |
| | SCHEDULE) SHOWED A MODULATING 100% OUTSIDE AIR |
| | DEHUMIDIFACTION UNIT PROVIDING 9000 CFM OUTSIDE AIR IN |
| | THE SKATING RINK AREA VIA DUCT SOCK. THIS UNIT SHALL |
| | NOT BE CONSIDERED AS ELIMINATED BASED ON THESE |
| | REVISIONS. ELIMINATION OF THIS UNIT WOULD LEAVE THE |
| | RINK AND SPECTATOR AREAS WITHOUT VENTILATION AS |
| | REQUIRED UNDER ASHRAE 62.1-2004. THIS UNIT IS STILL |
| | SHOWN ON PERMIT PLANS ON PAGE M-2-IRB. |
| | |