2009-08-07 16:14:051590 NORTH FLORIDA MANGO
 INTERIOR RENOVATION FOR PALM BEACH ICE WORKS ( PHASE II
 )
  
 1. CROWD MANAGEMENT TRAINING IS REQUIRED FOR THIS
 FACILITY. ONE CROWD MANAGER IS REQUIRED FOR EVERY 250
 OCCUPANTS. PLEASE GO THE MARYLAND STATE FIRE MARSHALS
 WEB SITE AND CLICK ON THE ICON FOR THE ON-LINE CROWD
 MANAGEMENT PROGRAM. AFTER COMPLETING THE PROGRAM A TEST
 NEEDS TO BE TAKEN AND CERTIFICATES SUBMITTED TO THIS
 OFFICE.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO
 COMPLY WITH NFPA 241.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM RENOVATION.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 ALARM SYSTEM REMODEL.
  
 5. THE DOUBLE PAIRS OF DOORS LEADING FROM ICE RINK INTO
 LOBBY 116 SWING IN THE WRONG DIRECTION. THESE DOORS
 SHOULD SWING INTO LOBBY 116. DOORS 117 AND DOORS 118.
  
 6. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN THE
 CORRIDORS TO LEADS PERSONS THROUGH DOORWAYS.
  
 7. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS.
  
 8. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE
 SECOND FLOOR TO DIRECT PERSONS THROUGH DOORWAYS.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCTS, AND FIRE SUPPRESSION SYSTEMS. THESE SYSTEMS ARE
 REQUIRED FOR ANY COOKING THAT PRODUCES SMOKE OR GREASE
 LADEN VAPORS.
  
 10. PLEASE SUBMIT AN "ALL HAZARDS" EMERGENCY PLAN TO
 THIS OFFICE FOR THE FACILITY.
  
 11. ALL HANDRAILS AND GUARDRAILS SHALL MEET THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS OF THE FBC AND THE
 FFPC.
  
 12. THE EXTERIOR STAIR DISPLAYED ON PAGE 722 SHALL HAVE
 A MINIMUM OF AT LEAST 10' FROM ANY OPENINGS VERTICALLY
 OR HORIZONTALLY OF THE STAIRS.
  
 13. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE A
 GENERAL ALARM. NOTE 11 ON PAGE E-1 IS INCORRECT.
  
 14. STORAGE AREAS UNDER BLEACHERS SHALL BE FIRE
 SPRINKLER PROTECTED.
  
 15. PLEASE ENSURE THAT PROPER EXIT DISCHARGE IS
 PROVIDED TO ALL EXITS SERVING THE FACILITY.
  
 16. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL COMPLY WITH THE FBC AND THE FFPC.
  
 17. PLEASE REEVALUATE THE EXIT DISCHARGE DISPLAYED ON
 PAGE 110. NEAR THE TEMPORARY PARTITION A DOUBLE DOOR
 EXITS INTO A SINGLE DOOR. BOTH LOCATIONS HAVE SEPARATE
 OCCUPANT LOADS WHEREBY THE DOUBLE DOORS HAVE A MUCH
 HIGHER EXIT CAPACITY THAN THE SINGLE DOOR.
  
 ON AUGUST 7, 2009, A LETTER IS TO BE PROVIDED REGARDING
 THESE COMMENTS EXCEPT # 17 WHICH WAS THE LAST ONE
 DOCUMENTED.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION