| 2009-08-07 16:14:05 | 1590 NORTH FLORIDA MANGO |
| | INTERIOR RENOVATION FOR PALM BEACH ICE WORKS ( PHASE II |
| | ) |
| | |
| | 1. CROWD MANAGEMENT TRAINING IS REQUIRED FOR THIS |
| | FACILITY. ONE CROWD MANAGER IS REQUIRED FOR EVERY 250 |
| | OCCUPANTS. PLEASE GO THE MARYLAND STATE FIRE MARSHALS |
| | WEB SITE AND CLICK ON THE ICON FOR THE ON-LINE CROWD |
| | MANAGEMENT PROGRAM. AFTER COMPLETING THE PROGRAM A TEST |
| | NEEDS TO BE TAKEN AND CERTIFICATES SUBMITTED TO THIS |
| | OFFICE. |
| | |
| | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION IS TO |
| | COMPLY WITH NFPA 241. |
| | |
| | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE |
| | SPRINKLER SYSTEM RENOVATION. |
| | |
| | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE |
| | ALARM SYSTEM REMODEL. |
| | |
| | 5. THE DOUBLE PAIRS OF DOORS LEADING FROM ICE RINK INTO |
| | LOBBY 116 SWING IN THE WRONG DIRECTION. THESE DOORS |
| | SHOULD SWING INTO LOBBY 116. DOORS 117 AND DOORS 118. |
| | |
| | 6. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN THE |
| | CORRIDORS TO LEADS PERSONS THROUGH DOORWAYS. |
| | |
| | 7. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS. |
| | |
| | 8. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON THE |
| | SECOND FLOOR TO DIRECT PERSONS THROUGH DOORWAYS. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD, |
| | DUCTS, AND FIRE SUPPRESSION SYSTEMS. THESE SYSTEMS ARE |
| | REQUIRED FOR ANY COOKING THAT PRODUCES SMOKE OR GREASE |
| | LADEN VAPORS. |
| | |
| | 10. PLEASE SUBMIT AN "ALL HAZARDS" EMERGENCY PLAN TO |
| | THIS OFFICE FOR THE FACILITY. |
| | |
| | 11. ALL HANDRAILS AND GUARDRAILS SHALL MEET THE |
| | PRESCRIPTIVE STRENGTH REQUIREMENTS OF THE FBC AND THE |
| | FFPC. |
| | |
| | 12. THE EXTERIOR STAIR DISPLAYED ON PAGE 722 SHALL HAVE |
| | A MINIMUM OF AT LEAST 10' FROM ANY OPENINGS VERTICALLY |
| | OR HORIZONTALLY OF THE STAIRS. |
| | |
| | 13. DUCT SMOKE DETECTORS WHEN ACTIVATED SHALL CAUSE A |
| | GENERAL ALARM. NOTE 11 ON PAGE E-1 IS INCORRECT. |
| | |
| | 14. STORAGE AREAS UNDER BLEACHERS SHALL BE FIRE |
| | SPRINKLER PROTECTED. |
| | |
| | 15. PLEASE ENSURE THAT PROPER EXIT DISCHARGE IS |
| | PROVIDED TO ALL EXITS SERVING THE FACILITY. |
| | |
| | 16. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE FBC AND THE FFPC. |
| | |
| | 17. PLEASE REEVALUATE THE EXIT DISCHARGE DISPLAYED ON |
| | PAGE 110. NEAR THE TEMPORARY PARTITION A DOUBLE DOOR |
| | EXITS INTO A SINGLE DOOR. BOTH LOCATIONS HAVE SEPARATE |
| | OCCUPANT LOADS WHEREBY THE DOUBLE DOORS HAVE A MUCH |
| | HIGHER EXIT CAPACITY THAN THE SINGLE DOOR. |
| | |
| | ON AUGUST 7, 2009, A LETTER IS TO BE PROVIDED REGARDING |
| | THESE COMMENTS EXCEPT # 17 WHICH WAS THE LAST ONE |
| | DOCUMENTED. |
| | |
| | |
| | APPROVED PROVISO |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4774 FAX |