2009-07-20 20:06:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. 100% OUTSIDE AIR UNIT AHU-3 SHALL BE PROVIDED WITH A
 MOTORIZED VOLUME DAMPER IN THE OUTSIDE AIR INTAKE DUCT
 IN ACCORDANCE WITH FBC-B 13-409.AB 3.3.
  
 2. CONCESSION AREA REQUIRES COMMERCIAL KITCHEN EXHAUST
 HOOD IF COMMERCIAL COOKING IS TO OCCUR IN THIS AREA IN
 ACCORDANCE WITH FBC-M 507.2. PROVIDE SEPARATE PLANS AND
 PERMIT APPLICATION FOR COMMERCIAL HOOD AND HOOD
 SUPPRESSION SYSTEMS.
  
 3. EF-2 IN ZAMBONI ROOM IS NOT SERVING AS AN EXHAUST
 FAN, BUT AS A SUPPLY FAN. SMOKE DETECTORS SHALL BE
 INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY
 GREATER THAN 2,000 CFM IN ACCORDANCE WITH FBC-M
 606.2.1.
  
 4. SHOW HOW MINIMUM CONTINUOUS VENTILATION RATE OF 0.05
 CFM PER SQ. FT. IS TO BE PROVIDED IN ZAMBONI STORAGE
 ROOM PER FBC-M 404.2.
  
 5. PAGE M-2B SHOWS A 4 INCH VENT TO WALL CAP AND
 REFERENCES A DETAIL ON PAGE M-4. NO SUCH DETAIL COULD
 BE FOUND ON PAGE M-4. PLEASE CLARIFY.
  
 6. ALL OUTDOOR APPLIANCES SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE. PROVIDE DATA FROM
 OUTDOOR APPLIANCE MANUFACTURER(S) SHOWING THE OUTDOOR
 APPLIANCES ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.13.
  
 NOTE: THE PHASING ASPECT OF THIS PROPOSED SCOPE OF WORK
 IS NOT CLEAR. SOME AREAS INDICATE THEY ARE EXISTING
 UNDER SEPARATE PERMIT BUT THIS SCOPE IS SUBMITTED AS A
 REVISION TO EXISTING PERMIT WHICH IS STILL OPEN. ANY
 DUPLICATIVE REVIEW OF EXISTING SYSTEMS IS A RESULT OF
 THIS LACK OF CLARITY.
  