2009-03-03 20:58:31*** PROVISO/ REDLINED PLANS***
  
 1) NOTE: PLEASE TAKE A LOOK AT REVISED SHEET E-6. THE
 NEW LOAD CALCULATIONS WHICH WERE REQUESTED ON PREVIOUS
 REVIEW ARE NOW ADDED TO PLANS. HOWEVER THE 1600AMP LOAD
 CALCULATIONS STATES THE SERVICE IS GOING TO BE
 1200AMPS. THE NOTES AT THE BOTTOM OF THE SAME 1600AMP
 LOAD CALCULATIONS STATES THE SERVICE ENTRANCE
 CONDUCTORS BASED ON THE 1200AMP SERVICE NOT THE 1600AMP
 MAIN SERVICE.
 THE RISER CLEARLY INDICATES 4- SETS OF 600MCM FROM FPL
 TO MAIN AND FROM MAIN TO GUTTER YET THE NOTES ON THE
 BOTTOM OF THE CALCULATIONS STATE 3-SETS OF 600MCM WHICH
 ARE ONLY RATED FOR 1260AMPS. PER 310.16 AND 110.14.
 THIS WOULD ALSO BE IN VIOLATION OF 240.4.C AS DEVICES
 RATED OVER 800AMPS SHALL HAVE CONDUCTORS RATED AT THE
 OVER CURRENT PROTECTION PROVIDED OR ABOVE. THE 4-SETS
 OF CONDUCTORS ON THE RISER AT 420AMPS FOR EACH PARALLEL
 RUN IS ABOVE THE 1600AMPS PER 310.16, 110.14 AND
 240.4C. THE CONDUCTORS ON RISER NOT IN NOTES MUST BE
 INSTALLED.
 AS THE RISER DOES INDICATE THE CORRECT CONDUCTORS THIS
 MUST BE A MISPRINT AND A NEED OF REVISED PLANS AND
 COORDINATION IS REQUIRED.
 PLEASE REVISE PLANS BEFORE ROUGH ELECTRICAL INSPECTION.
 THIS NOTE WILL BE E-MAILED TO THE ENGINEERING FIRM.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved