| 2009-03-03 20:58:31 | *** PROVISO/ REDLINED PLANS*** |
| | |
| | 1) NOTE: PLEASE TAKE A LOOK AT REVISED SHEET E-6. THE |
| | NEW LOAD CALCULATIONS WHICH WERE REQUESTED ON PREVIOUS |
| | REVIEW ARE NOW ADDED TO PLANS. HOWEVER THE 1600AMP LOAD |
| | CALCULATIONS STATES THE SERVICE IS GOING TO BE |
| | 1200AMPS. THE NOTES AT THE BOTTOM OF THE SAME 1600AMP |
| | LOAD CALCULATIONS STATES THE SERVICE ENTRANCE |
| | CONDUCTORS BASED ON THE 1200AMP SERVICE NOT THE 1600AMP |
| | MAIN SERVICE. |
| | THE RISER CLEARLY INDICATES 4- SETS OF 600MCM FROM FPL |
| | TO MAIN AND FROM MAIN TO GUTTER YET THE NOTES ON THE |
| | BOTTOM OF THE CALCULATIONS STATE 3-SETS OF 600MCM WHICH |
| | ARE ONLY RATED FOR 1260AMPS. PER 310.16 AND 110.14. |
| | THIS WOULD ALSO BE IN VIOLATION OF 240.4.C AS DEVICES |
| | RATED OVER 800AMPS SHALL HAVE CONDUCTORS RATED AT THE |
| | OVER CURRENT PROTECTION PROVIDED OR ABOVE. THE 4-SETS |
| | OF CONDUCTORS ON THE RISER AT 420AMPS FOR EACH PARALLEL |
| | RUN IS ABOVE THE 1600AMPS PER 310.16, 110.14 AND |
| | 240.4C. THE CONDUCTORS ON RISER NOT IN NOTES MUST BE |
| | INSTALLED. |
| | AS THE RISER DOES INDICATE THE CORRECT CONDUCTORS THIS |
| | MUST BE A MISPRINT AND A NEED OF REVISED PLANS AND |
| | COORDINATION IS REQUIRED. |
| | PLEASE REVISE PLANS BEFORE ROUGH ELECTRICAL INSPECTION. |
| | THIS NOTE WILL BE E-MAILED TO THE ENGINEERING FIRM. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |