Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop B
Sequence Number 4
Notes
Date Text
2009-03-04 17:07:56****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS REVIEWS:
  
  
 37. SEE ENERGY CALCS; NO DOORS SHOWN, ICE RINK FLOOR IS
 SHOWN AS CARPET. PLEASE REVISE THESE ITEMS AND CHECK
 ALL INFORMATION ON THE ENERGY CALC INPUT DATA REPORT.
  
 2ND REVIEW, THIS HAS BEEN ADDRESSED. HOWEVER, PLEASE
 EXPLAIN THE ROOF R VALUE; R19 BATT INSULATION IS SHOWN
 (MULTIPLIED BY BTU) THAT IT HAS AN R VALUE OF 30.
 PLEASE CLARIFY HOW R30.3 WILL BE ACHIEVED.
 3RD REVIEW, THIS HAS NOT BEEN REVISED OR EXPLAINED.
 FEEL FREE TO CONTACT ME VIA EMAIL OR TELEPHONE TO
 CLARIFY THIS NUMBER (R30). ALSO PLEASE NOTE THAT DOORS
 AND WINDOWS HAVE NOW BEEN REMOVED FROM THE ENERGY
 CALCS. PLEASE CONFIRM THAT ALL BUILDING DATA IS CORRECT
 PRIOR TO RESUBMITTING.
  
 CALLED ENGINEER; WILL BRING NEW CALCS
  