| Date |
Text |
| 2009-02-07 17:01:40 | DENIED |
| | REFERENCE: FBC-2004 PLUMBIING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE |
| | FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF |
| | OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION. |
| | SECTION 105.1. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | ******RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | |
| | ***********NEW COMMENTS*********** |
| | 1B. ALL ARCHITECTURAL SHEETS ARE NOT SEALED ONE SET OF |
| | PLANS. SECTION 106.1. |
| | |
| | 2B. OK |
| | 3B. OK |
| | 4B. OK |
| | |
| | 5B. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE SHOWER IN THE PRIVATE |
| | BATH, AT THE TOILET ROOM BY COL. LINE F/1 AND CLEANOUTS |
| | ADDED TO THE FLOOR PLAN IN THE SEWER LINES ARE NOT |
| | SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1 AND TABLE 710.1.1. |
| | ****RESPONSE NOTED, BUT THE PIPING IN THE PRIVATE BATH |
| | SHOW THE PIPING TO THE LAV INDICATED AT THE WATER |
| | CLOSET, AND THE PIPING TO THE WATER CLOSET AT THE LAV |
| | LOCATION. -- THE CLEANOUTS SHOWN ON THE FLOOR PLAN OF |
| | SHT P-1 ARE STILL NOT SHOWN ON THE SANITARY ISOMETRIC |
| | RISER DIAGRAM. STILL MISSING ARE THE CLEANOUT ON THE |
| | NORTH SEWER 100 FEET DOWNSTREAM OF THE TWO WAY CLEANOUT |
| | NEAR THE JUNCTION OF THE BUILDING DRAIN AND THE |
| | BUILDING SEWER. THE CLEANOUTS NEAR THE JUNCTIONS OF THE |
| | BUILDING DRAINS AND THE BUILDING SEWERS, (SECTION |
| | 708.3.5), FOR THE GREASE LINE, THE SANITARY LINE FOR |
| | THE MECHANICAL FLOOR DRAINS ON THE WEST SIDE, & THE |
| | SANITARY DRAIN FOR THE MEN'S AND WOMEN'S LOCKER ROOMS. |
| | ALSO THE CLEANOUTS FOR THE BUILDING SEWER ON THE SOUTH |
| | SIDE OF THE BUILDING ARE NOT SHOWN, (3). -- NOTE: THE |
| | CLEANOUT FOR THE NORTH SEWER ON THE FLOOR PLAN SCALES |
| | OUT OVER 100 FEET ON SHT P-1. PER SECTION 708.3.2 |
| | MAXIMUM 100 FEET BETWEEN CLEANOUTS ON THE BUILDING |
| | SEWERS. |
| | |
| | 6B. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | ********IMPORTANT NOTE:********** |
| | |
| | 1C. PLEASE SUBMIT ONE SET OF PREVIOUSLY REVIEWED SHEETS |
| | AS ALL SHEETS HAVE BEEN REPLACED WITH NEW SHEETS AND IF |
| | THE PREVIOUSLY REVIEWED SHEETS ARE NOT SUBMITTED FOR |
| | COMPARISON THEN EACH SHEET WILL HAVE TO BE REVIEWED AS |
| | A NEW SHEET AND MORE/DIFFERENT COMMENTS MAY BE |
| | FORTHCOMING. PLEASE SEE PREVIOUS NOTE INDICATING THE |
| | REQUIREMENT FOR ONE SET OF VOIDED SHEETS. |
| | |
| | ******************************************* |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |