Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop P
Sequence Number 3
Notes
Date Text
2009-02-07 17:01:40DENIED
 REFERENCE: FBC-2004 PLUMBIING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 CITY WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
  
 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE
 FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF
 OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION.
 SECTION 105.1.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
  
 ***********NEW COMMENTS***********
 1B. ALL ARCHITECTURAL SHEETS ARE NOT SEALED ONE SET OF
 PLANS. SECTION 106.1.
  
 2B. OK
 3B. OK
 4B. OK
  
 5B. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE SHOWER IN THE PRIVATE
 BATH, AT THE TOILET ROOM BY COL. LINE F/1 AND CLEANOUTS
 ADDED TO THE FLOOR PLAN IN THE SEWER LINES ARE NOT
 SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1 AND TABLE 710.1.1.
 ****RESPONSE NOTED, BUT THE PIPING IN THE PRIVATE BATH
 SHOW THE PIPING TO THE LAV INDICATED AT THE WATER
 CLOSET, AND THE PIPING TO THE WATER CLOSET AT THE LAV
 LOCATION. -- THE CLEANOUTS SHOWN ON THE FLOOR PLAN OF
 SHT P-1 ARE STILL NOT SHOWN ON THE SANITARY ISOMETRIC
 RISER DIAGRAM. STILL MISSING ARE THE CLEANOUT ON THE
 NORTH SEWER 100 FEET DOWNSTREAM OF THE TWO WAY CLEANOUT
 NEAR THE JUNCTION OF THE BUILDING DRAIN AND THE
 BUILDING SEWER. THE CLEANOUTS NEAR THE JUNCTIONS OF THE
 BUILDING DRAINS AND THE BUILDING SEWERS, (SECTION
 708.3.5), FOR THE GREASE LINE, THE SANITARY LINE FOR
 THE MECHANICAL FLOOR DRAINS ON THE WEST SIDE, & THE
 SANITARY DRAIN FOR THE MEN'S AND WOMEN'S LOCKER ROOMS.
 ALSO THE CLEANOUTS FOR THE BUILDING SEWER ON THE SOUTH
 SIDE OF THE BUILDING ARE NOT SHOWN, (3). -- NOTE: THE
 CLEANOUT FOR THE NORTH SEWER ON THE FLOOR PLAN SCALES
 OUT OVER 100 FEET ON SHT P-1. PER SECTION 708.3.2
 MAXIMUM 100 FEET BETWEEN CLEANOUTS ON THE BUILDING
 SEWERS.
  
 6B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ********IMPORTANT NOTE:**********
  
 1C. PLEASE SUBMIT ONE SET OF PREVIOUSLY REVIEWED SHEETS
 AS ALL SHEETS HAVE BEEN REPLACED WITH NEW SHEETS AND IF
 THE PREVIOUSLY REVIEWED SHEETS ARE NOT SUBMITTED FOR
 COMPARISON THEN EACH SHEET WILL HAVE TO BE REVIEWED AS
 A NEW SHEET AND MORE/DIFFERENT COMMENTS MAY BE
 FORTHCOMING. PLEASE SEE PREVIOUS NOTE INDICATING THE
 REQUIREMENT FOR ONE SET OF VOIDED SHEETS.
  
 *******************************************
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  