Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop M
Sequence Number 3
Notes
Date Text
2009-02-13 08:00:32REVIEW #: 3RD
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLANS HAVE BEEN REVIEWED FOR CODE COMPLIANCE AND
 STAMPED. HOWEVER, REVIEW WILL REMAIN IN FAIL STATUS
 PENDING RESOLUTION OF THE FOLLOWING:
  
 ENERGY CALCULATIONS: A SYSTEM SIZING SUMMARY HAS BEEN
 PROVIDED IN LIEU OF COOLING LOAD CALCULATIONS. THIS IS
 ACCEPTABLE BUT THE SYSTEM SIZING SUMMARY MUST BE SIGNED
 AND SEALED IN ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 ENERGY CALCULATIONS: PLEASE SEE BUILDING AND ELECTRICAL
 COMMENTS. THIS REVIEW WILL REMAIN IN FAIL STATUS UNTIL
 ENERGY CALCULATIONS PASS ALL REVIEWS.
  
 DRYER EXHAUST: DRYER MODEL NUMBER HAS BEEN SHOWN ON
 PLANS AND INSTALLATION INSTRUCTIONS HAVE BEEN PROVIDED.
 DRYER INSTALLATION IS CODE COMPLIANT. HOWEVER, PLEASE
 RPOVIDE THREE COPIES OF THE DRYER SPECS AND
 INSTRUCTIONS TO BE INCLUDED WITH THE THREE PERMIT SETS
 OF PLANS AND SUBMITTALS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]