Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop E
Sequence Number 3
Notes
Date Text
2009-02-08 12:57:21** DENIED 3RD REVIEW **
  
 ** THERE ARE ITEMS WHICH ARE STILL IN NEED OF
 ADDRESSING FROM THE PREVIOUS REVIEWS.
  
  
 1) NOTE: THE ARCHITECT'S TITLE BLOCKS HAVE STILL NOT
 BEEN REVISED. AS NOTED ON PREVIOUS REVIEW PLEASE SEE
 FAC 61G1-16.004. THIS IS REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY ANY OTHER TRADES. THIS COMMENT IS
 FOR THE ARCHITECT.
 PLEASE SEE SECTION ABOVE AS THE PRINTED NAME AND
 PRINTED LICENSE NUMBER IS REQUIRED ON EACH AND EVERY
 SHEET WHICH CONTAINS THE ARCHITECTS INFORMATION
 THE OTHER OPTION IS TO REMOVE ARCHITECT'S INFORMATION
 FROM TRADE SHEETS.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEWS AS THE MANUFACTURE
 SPECS/CUT SHEETS WERE REQUESTED FOR THE NEW PROPOSED
 ATS. THE PREVIOUS PLANS CONTAINED THE INFORMATION
 HOWEVER AS THE PRINTING WAS NOT CLEAR IT WAS ASKED FOR
 THE SHEETS TO BE SUBMITTED OR TO CLEAR UP THE
 INFORMATION NOTED ON PLANS. THE PLANS NOW DO NOT SHOW
 THE INFORMATION AND COULD NOT LOCATE THIS IN THE
 PACKAGE.
 110.3, 702.6, 90.7
 FBC 106.1.2, 106.1.1 FOR INFORMATION, CLARITY ETC
  
 4) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO SYSTEMS SUCH AS LIGHTING AND GATES WHICH ARE
 STILL BEING SHOWN ON PLANS BEING FED FROM THIS
 PROPERTY. THIS IS NOT PERMITTED. THESE PROPERTIES WOULD
 BE REQUIRED TO CONTAIN A UNITY OF TITLE. PLEASE SEE
 LANDSCAPE PLANS AND BE SURE ALL PLANS COORDINATE.
 NEC 230.2 ETC
 FBC TABLE 601
 THIS NEEDS TO BE COORDINATED WITH ALL TRADES SUCH AS
 ZONING, BUILDING ETC.
  
 5) NOTE: PLEASE SEE ALL NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO FBC CHAPTER 13. COMPLIANCE FOR MINIMUM HAS
 NOT BEEN MET.
  
 THE SQUARE FOOTAGE ON PLANS AND CALCULATIONS SUBMITTED
 DO NOT COORDINATE.
  
 THE IDENTIFICATION OF THE SPACES DOES NOT COORDINATE.
 FOR ONE IS THE METHOD *C* SUBMITTED FOR WAREHOUSE
 STATES UNIT *A* HOWEVER UNIT *A* BASED ON THE
 ARCHITECTURAL PLANS IS THE ICE RINK AREA.
  
 THE PLANS CONTAINS A METHOD *B* TABLE CALCULATION FOR
 SPACE BY SPACE. IT IS NOT PERMISSIBLE TO MIX METHODS OF
 CALCULATIONS. PLEASE SEE 13-415.2.ABC.1
  
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT
 ALSO NEEDS TO COORDINATE WITH THE SUBMITTED PLANS. THE
 INPUT DATA REPORT WILL BE NOTED AS IDR ON THE REMAINDER
 OF THIS COMMENT.
 THERE ARE STILL LIGHTING FIXTURES ON PLANS WHICH ARE
 NOT IN THE IDR OR FIXTURE WATTAGES WHICH DO NOT
 COORDINATE.
  
 FOR EXAMPLE: PLEASE SEE INTERIOR LIGHTING OF THE IDR.
 PLEASE SEE THE PLANS WHICH INDICATE THE *A* FIXTURES
 ALONG WITH OTHERS AS 648 WATTS. THE IDR INDICATES 324.
 BASED ON THE WATTAGE OF THE ACTUAL FIXTURE THE DOES NOT
 SEEM TO BE POSSIBLE.
  
 FOR EXAMPLE: PLEASE SEE OTHER FIXTURES SUCH AS AE1, AND
 H.
 THIS IS ONLY TWO BEING NOTED WHICH ARE NOT IN THE IDR
 AT ALL.
  
 FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING SUBMITTED
 ON THE IDR. THE ONLY FIXTURE WATTAGE LISTED IS THE 250W
 FIXTURES. THIS IS NOT POSSIBLE WHEN FIXTURES ON THE
 PLANS SUCH AS SHEET ESP-1 STATES 250W AND 400WATT
 FIXTURES.
 WHAT ABOUT OTHER FIXTURES SUCH AS EXTERIOR LIGHTING
 FIXTURE *H* WHICH IS SHOWN ON PLANS ON SHEET E-2B YET
 THESE ARE NOT ON THE IDR.
  
 FOR EXAMPLE: INTERIOR LIGHTING ON PLANS IS GREATER THAN
 THE AMOUNT AND TYPE OF FIXTURES ON THE IDR. SEE LOCKERS
 AS ONE LOCATION FOR MEN, WOMEN, AT ALL LOCATIONS.
  
  
 *** THESE ARE SOME EXAMPLES ONLY GIVEN AS A BENEFIT TO
 HELP. THESE MAY NOT BE ALL ITEMS.
 PLEAS BE SURE TO GO OVER AND CALL WITH ANY COMMENTS OR
 QUESTIONS FOR COORDINATION.
 13-415.2,13-415.2.ABC.1.1,.1.2 AND .1.3.
  
 6) NOTE: PLEASE COORDINATE SHEET E-4 AND E-6. ALL MAINS
 SEEM TO COME FROM THE SAME GUTTER, HOWEVER BASED ON
 SHEET E-4 THE OTHER METER AND MAIN FOR THE HOUSE PANEL
 IS ON THE OTHER SIDE OF THE OPENING FOR THE ICE PT
 DOOR.
 THIS CONFLICTS WITH THE REVISED RISER.
 THIS IS A NEW COMMENT AS THE RISER HAS BEEN COMPLETELY
 REVISED.
  
 7) NOTE: WHERE IS THE LOAD CALCULATIONS ON THE NEW
 1600AMP MAIN?
 NEC 220
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 8) NOTE: PLANS MAKE NOTE FOR FLOATING NEUTRAL AS GONE
 OVER IN MEETING HOWEVER THIS IF FOR THE METERS ON THE
 SECONDARY SIDE OF THE 1600AMP MAIN. THIS COULD BE
 REDLINED TO INDICATE THIS FOR THE METERS. IT SEEMS TO
 BE PART OF THE FEEDERS SHOWN ON RISER.
 250.6, 250.24 ETC
  
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  