Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop Z
Sequence Number 2
Notes
Date Text
2009-01-02 15:26:20ZONING PLAN REVIEW
  
 PERMIT NO.: 08090611
 ADDRESS: 1590 FLORIDA MANGO ROAD
 CONTRACTOR/CONTACT: NAT HEALY
 TELEPHONE NO.: (561) 635-6935
  
 REVIEW STATUS: FAILED
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 ***FAILED***
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED AS PART OF
 THE RESUBMITTAL:
  
 1) TWO (2) COPIES OF A CURRENT/ACCURATE SURVEY SHALL BE
 INCLUDED.
  
 2) AN EASEMENT CONSENT FORM SHALL BE SUBMITTED TO AND
 APPROVED BY THE CITY'S PUBLIC UTILITIES DEPARTMENT, AND
 THEN INCLUDED IN THE PERMIT PACKAGE, FOR THE
 CONSTRUCTION OF THE NEW FENCE. IF THE FENCE WILL BE
 LOCATED WITHIN AN EASEMENT, AN EASEMENT CONSENT FORM
 SHALL BE PROVIDED FROM ALL PRIVATE UTILITY COMPANIES.
  
 3) PLEASE CORRECT AND PROVIDE AN ACCURATE BUILDING
 FOOTPRINT ON THE SITE PLAN. BE SURE TO SHOW THE
 OUTLINES OF AWNINGS, SHUTTERS, CANOPIES, ETC. ON THE
 EXTERIOR OF THE BUILDING. PLEASE PROVIDE DIMENSIONS OF
 SUCH.
  
 THE FOLLOWING COMMENTS ARE NEW AND HAVE BEEN GENERATED
 DUE TO CHANGES TO THE PLAN UPON RESUBMITTAL:
  
 1) ON SHEET SP-1 THE TRANSFORMER ON THE EAST SIDE OF
 THE BUILDING IS LABELED, BUT NOTHING IS SHOWN.
  
 2) ALL LANDSCAPE AREAS ARE TO BE PROTECTED FROM VEHICLE
 ENCROACHMENT BY A TYPE D CURB AND/OR WHEEL STOPS. THE
 SITE PLAN IS UNCLEAR AS TO WHICH AREAS ARE CURBED,
 WHICH ARE NOT, ETC. PLEASE CLEARLY IDENTIFY THOSE AREAS
 THAT ARE CURBED, ETC.
  
 3) IN THE SITE DATA TABLE, PLEASE INDICATED UNDER
 "ADDITIONAL PARKING REQUIRED" WHAT THE ADDITIONAL
 SQUARE FOOTAGE IS AND WHAT PARKING RATIO IS BEING USED
 TO DETERMINED THE REQUIRED NUMBER OF SPACES (1 PER 250
 SQ. FT.).
  
 4) PARKING DETAIL SHALL BE PROVIDED (SEE ATTACHED).
  
 5) A DETAIL OF THE PROPOSED DUMPSTER ENCLOSURE SHALL BE
 PROVIDED. BE SURE TO DIMENSION THE ENCLOSURE ON THE
 SITE PLAN.
  
 6) THE ELECTRICAL SITE PLAN DOES NOT MATCH SHEET SP-1
 (I.E. PARKING AREAS DON'T MATCH, ETC.). ADDITIONALLY,
 SHEET ES-1 SHOWS THE INSTALLATION OF A GATE ON THE EAST
 ACCESS ROAD. THIS IS A SEPARATE PROPERTY AND
 IMPROVEMENTS SHALL NOT CROSS PROPERTY LINES. IF A GATE
 IS TO BE INSTALLED, A UNITY OF TITLE SHALL BE RECORDED
 FOR BOTH PROPERTIES. IF THIS GATE IS PROPOSED TO BE
 MOTORIZED AND OPEN-ON-DEMAND DURING BUSINESS HOURS,
 THEN AT LEAST 100 FEET OF STACKING SHALL BE PROVIDED.
  
 7) PLEASE CLEARLY IDENTIFY ON SHEET SP-1 WHAT IS
 EXISTING, WHAT IS PROPOSED, ETC (I.E. IS THE 6 FOOT
 WOOD FENCE TO THE SOUTH OF THE DRIVEWAY EXISTING? IS
 THE 6 FOOT FENCE ALONG THE WEST PROPERTY LINE EXISTING?
 IS THE 8 FOOT BLOCK WALL ALONG THE SOUTH PROPERTY LINE
 EXISTING?) SOME THINGS ARE UNCLEAR AS TO WHETHER OR NOT
 THEY ARE EXISTING OR PROPOSED. PLEASE CLARIFY
 ACCORDINGLY.
  
 IMPORTANT: THE SITE PLAN SHOULD CLEARLY SHOW WHAT THE
 FINAL PRODUCT WILL LOOK LIKE. SHEET SP-1 CURRENTLY
 SHOWS EXISTING CURBING AND ASHPALT IN AREAS WHERE
 LANDSCAPING IS TO BE PLACED, YET DOES NOT INDICATE
 THEIR REMOVAL, ETC. IDEALLY, THE SITE PLAN WILL SHOW
 THE FINAL PRODUCT WHILE A DEMOLITION PLAN WOULD SHOW
 WHAT IS BEING REMOVED. AS PROVIDED IN THE COMMENT
 ABOVE, BE SURE THE SITE PLAN CLEARLY IDENTIFIES WHAT IS
 EXISTING, PROPOSED, ETC.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.