| 2009-01-06 18:55:07 | DENIED |
| | REFERENCE: FBC-2004 PLUMBIING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | CITY WPB MUNICIPAL CODE |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. THE APPLICATION FOR PERMIT ASKS FOR GROSS SQUARE |
| | FOOTAGE AND WHETHER OR NOT THIS IS A CHANGE OF |
| | OCCUPANCY. PLEASE INDICATE BOTH ON THE APPLICATION. |
| | SECTION 105.1. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 4. OK |
| | |
| | 5. SUBMIT CALCULATIONS FOR MINIMUM FACILITIES PER |
| | TABLES 1004.1.2 & 403.1. PER TABLE 1004.1.2 THE RINK IS |
| | 50 GROSS. (SHOW GROSS SQUARE FOOTAGE FOR THE RINK. |
| | PLEASE INDICATE CALCULATIONS FOR OTHER OCCUPANCIES SUCH |
| | AS BUSINESS & STORAGE. INDICATE THE SQUARE FOOTAGE OF |
| | EACH AREA ON THE FLOOR PLAN AS WELL AS THE DECK AREA |
| | AROUND THE RINK. |
| | ****RESPONSE NOTED, BUT THE NUMBER OF W/C'S FOR THE |
| | WOMEN SHALL BE CHANGED TO 9. (347 DIVIDED BY 40 EQUALS |
| | 8.675 WHICH SHALL BE ROUNDED UP TO 9). PLEASE CORRECT |
| | SHT CV.01. |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | |
| | 9. SHT A.01.1 & A.09 (DETAILS A/A.09, E/A.09, 1/A.09, |
| | 2/A.09, 3/A.09 & 4/A.09). SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | |
| | ___FOR W/C'S: |
| | A. OK |
| | B. OK |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | ****RESPONSE NOTED, BUT DETAIL 9 ON SHT A.09.1 SHOWS |
| | THE FLUSH CONTROLS ON THE WALL SIDE. PLEASE CORRECT. |
| | |
| | ___FOR LAVS: |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | |
| | 10. SHT A.01.1 & A.09 (DETAILS D/A.09, 8/A.09 & |
| | 9/A.09). THE BATHROOM SHALL BE ACCESSIBLE. PLEASE SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | ****RESPONSE NOTED, BUT PLANS MUST SHOW THE BACKING FOR |
| | THE GRAB BARS IN THE SHOWER & W/C, A 5 FOOT TURNING |
| | AREA, W/C TO BE 18" OFF THE WALL TO THE CENTERLINE OF |
| | THE FIXTURE, SHOWER CONTROLS AT THE REQUIRED LOCATION & |
| | A DETAIL FOR THE SHOWER CURB IF INSTALLED TO BE |
| | ADAPTABLE. NO RESPONSE FOR DETAILS 8/A.09 & 9/A.09. |
| | |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | |
| | ***********NEW COMMENTS*********** |
| | 1B. ALL ARCHITECTURAL SHEETS ARE NOT SEALED ONE SET OF |
| | PLANS. SECTION 106.1. |
| | |
| | 2B. SHT A.01 STALL TO BE ACCESSIBLE IN TOILET ROOM AT |
| | JUNCTION OF COL. LINES B & 2. SECTION 11-4.17.3 & FIG |
| | 30E. |
| | |
| | 3B. SHT A.09 NOT SUBMITTED BUT STILL SHOWN ON THE INDEX |
| | OF DRAWINGS. PLEASE CORRELATE. (SHT A.01 REFERENCES |
| | DETAILS FROM SHT A.09) PLEASE CLARIFY. SECTIONS 106.1.1 |
| | & 106.1.3. |
| | |
| | 4B. SHT P-1 FITTING ON SEWER LINE FROM TOILET ROOM ON |
| | THE NORTH SIDE OF THE BUILDING IS SHOWN AGAINST THE |
| | FLOW. PLEASE CORRECT. SECTION 706.3. |
| | |
| | 5B. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE SHOWER IN THE PRIVATE |
| | BATH, AT THE TOILET ROOM BY COL. LINE F/1 AND CLEANOUTS |
| | ADDED TO THE FLOOR PLAN IN THE SEWER LINES ARE NOT |
| | SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1 AND TABLE 710.1.1. |
| | |
| | 6. SHT P-7 SANITARY ISOMETRIC RISER DIAGRAM. THE VENT |
| | FOR THE WASH MACHINE SHALL VENT OFF THE TOP OF THE |
| | STACK, NOT OUT OF THE LAUNDRY BOX AT THE TOP OF THE |
| | STANDPIPE AS SHOWN. SECTION 901.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |