Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2009-01-03 14:56:26*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE FIRST REVIEW STILL
 NEED TO BE ADDRESSED:
  
 01. THE ADDRESS NUMBER (1590) SHOWN IN THE THE TILE
 BLOCK OF EACH SUBMITTED PLAN SHEET DOES NOT CORRELATE
 WITH THE ADDRESS NUMBER (1600) AS LISTED IN OUR
 COMMUNITYPLUS DATABASE SYSTEM.
  
 04. ONLY ONE FIRE HYDRANT IS SHOWN ON SHEET SP-1, ARE
 ANY ADDITIONAL FIRE HYDRANTS PROPOSED ON THIS
 CAMPUS/SITE? IF NOT, EXPLAIN RATIONALE.
  
 06. IT APPEARS THAT THE BUILDING IS SET OFF OF THE
 ADDRESSED NORTH FLORIDA MANGO ROAD. HOW WILL EMERGENCY
 RESPONDERS AND/OR THE PUBLIC LOCATE THIS STRUCTURE?
  
 12. NFPA 13 2002 EDITION SHALL BE REFERENCED. REVISE
 NOTE 21 ON SHEET FP-1 TO REFLECT AS SUCH.
  
 * THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED:
  
 A.) SOME SHEETS IN ONE OF THE PLAN SETS ARE NOT SEALED
 AS PER FLORIDA STATUTE 481.
  
 B.) PLEASE ADDRESS BUILING EXAMINER'S COMMENT #42 IN
 REFERENCE TO TRAVEL DISTANCES AND OTHER ASSOCIATED
 INFORMATION.
  
 C.) A DICREPANCY STILL EXISTS AS TO WHETHER THERE IS A
 MEZZANINE AREA OR NOT. ALL PLANS SHOULD REFLECT THE
 SAME FLOOR LAYOUT.
  
 D.) IF THERE IS A MEZZANINE AREA FOR THIS PROJECT,
 PROVIDE A LAYOUT OF THE FIRE SPRINKLER DEVICES FOR THIS
 AREA.
  
 E.) IF THE PROPERTY IS TO BE EQUIPPED WITH AN ACCESS
 GATE, FIRE DEPARTMENT EMERGENCY ACCESS SHALL BE
 PROVIDED THROUGH THE USE OF AN APPROVED DEVICE OR
 SYSTEM. FOR MORE INFORMATION, CONTACT WEST PALM BEACH
 FIRE PREVENTION BUREAU AT 561-804-4724.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722