| 2009-01-03 14:56:26 | *****DENIED***** |
| | |
| | *THE FOLLOWING COMMENTS FROM THE FIRST REVIEW STILL |
| | NEED TO BE ADDRESSED: |
| | |
| | 01. THE ADDRESS NUMBER (1590) SHOWN IN THE THE TILE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET DOES NOT CORRELATE |
| | WITH THE ADDRESS NUMBER (1600) AS LISTED IN OUR |
| | COMMUNITYPLUS DATABASE SYSTEM. |
| | |
| | 04. ONLY ONE FIRE HYDRANT IS SHOWN ON SHEET SP-1, ARE |
| | ANY ADDITIONAL FIRE HYDRANTS PROPOSED ON THIS |
| | CAMPUS/SITE? IF NOT, EXPLAIN RATIONALE. |
| | |
| | 06. IT APPEARS THAT THE BUILDING IS SET OFF OF THE |
| | ADDRESSED NORTH FLORIDA MANGO ROAD. HOW WILL EMERGENCY |
| | RESPONDERS AND/OR THE PUBLIC LOCATE THIS STRUCTURE? |
| | |
| | 12. NFPA 13 2002 EDITION SHALL BE REFERENCED. REVISE |
| | NOTE 21 ON SHEET FP-1 TO REFLECT AS SUCH. |
| | |
| | * THE FOLLOWING NEW COMMENTS ARE TO BE ADDRESSED: |
| | |
| | A.) SOME SHEETS IN ONE OF THE PLAN SETS ARE NOT SEALED |
| | AS PER FLORIDA STATUTE 481. |
| | |
| | B.) PLEASE ADDRESS BUILING EXAMINER'S COMMENT #42 IN |
| | REFERENCE TO TRAVEL DISTANCES AND OTHER ASSOCIATED |
| | INFORMATION. |
| | |
| | C.) A DICREPANCY STILL EXISTS AS TO WHETHER THERE IS A |
| | MEZZANINE AREA OR NOT. ALL PLANS SHOULD REFLECT THE |
| | SAME FLOOR LAYOUT. |
| | |
| | D.) IF THERE IS A MEZZANINE AREA FOR THIS PROJECT, |
| | PROVIDE A LAYOUT OF THE FIRE SPRINKLER DEVICES FOR THIS |
| | AREA. |
| | |
| | E.) IF THE PROPERTY IS TO BE EQUIPPED WITH AN ACCESS |
| | GATE, FIRE DEPARTMENT EMERGENCY ACCESS SHALL BE |
| | PROVIDED THROUGH THE USE OF AN APPROVED DEVICE OR |
| | SYSTEM. FOR MORE INFORMATION, CONTACT WEST PALM BEACH |
| | FIRE PREVENTION BUREAU AT 561-804-4724. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |