| 2008-12-25 11:26:08 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | THERE ARE ALSO SOME NEW COMMENTS AS THERE ARE SEVERAL |
| | ASPECTS OF DESIGN CHANGING ALONG WITH NEW ITEMS WHICH |
| | WERE NOT PART OF THE PREVIOUS REVIEW. |
| | |
| | |
| | 1) NOTE: THE ARCHITECTURAL PLANS SUBMITTED CONTAIN A |
| | SIGNATURE AND DATE HOWEVER NONE OF THE SHEETS CONTAIN |
| | THE RAISED SEAL AS REQUIRED BY FLORIDA STATUTES |
| | 481.221. |
| | THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWERS |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: LANDSCAPE ARCHITECTURAL PLANS ARE MISSING |
| | INFORMATION REQUIRED ON THE TITLE BLOCKS. PLEASE SEE |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA |
| | STATUTES 481.219. |
| | MISSING CERTIFICATE OF AUTHORIZATION NUMBER. |
| | MISSING PRINTED NAME OF SAID DESIGNER. |
| | MISSING PRINTED LICENSE NUMBER OF ARCHITECT. |
| | |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE ANY |
| | OTHER TRADE OR THE LANDSCAPE REVIEWER. |
| | |
| | 3) NOTE: IN PREVIOUS MEETINGS HELD IT WAS DISCUSSED |
| | WHETHER OR NOT THE BUILDING WAS GOING TO BE ADJUSTED TO |
| | SEPARATE INTO MORE THAN ONE BUILDING BY DEFINITION. BY |
| | THE RESPONSE FROM THE ARCHITECT THE INTENT AS SHOWN AND |
| | NOTED IS THIS IS A SEPARATE BUILDING. HOWEVER BY |
| | DEFINITION IN CHAPTER 2 OF THE FLORIDA BUILDING CODE |
| | WHICH WILL DIRECT YOU TO 702.1 FOR FIRE RESISTIVE |
| | CONSTRUCTION DEFINITIONS. THIS IS ALSO IN THE |
| | DEFINITIONS IN CHAPTER 13 SECTION 202 OF THE SAME CODE. |
| | THIS WOULD REQUIRE A ** RATED FIRE WALL*. PLEASE SEE |
| | THE DEFINITION OF A FIRE WALL. THE FOLLOWING TEXT IS |
| | EXTRACTED DIRECTLY FROM THE CODE. |
| | |
| | **** |
| | FIRE WALL. FIRE-RESISTANT WALL, HAVING PROTECTIVE |
| | OPENINGS, WHICH RESTRICTS THE SPREAD OF FIRE AND |
| | EXTENDS CONTINUOUSLY FROM THE FOUNDATION TO OR THROUGH |
| | THE ROOF, WITH SUFFICIENT STRUCTURAL STABILITY UNDER |
| | FIRE CONDITIONS TO ALLOW COLLAPSE OF CONSTRUCTION ON |
| | EITHER SIDE WITHOUT COLLAPSE OF THE WALL.**** |
| | |
| | PLEASE BE SURE TO SEE THE SECOND PART OF THE SENTENCE |
| | WHICH THE CONSTRUCTION WILL ALLOW THE COLLAPSE OF THE |
| | CONSTRUCTION ON EITHER SIDE WITHOUT THE COLLAPSE OF THE |
| | WALL. |
| | A 2HR RATED DEMISING WALL DOES NOT MEET THIS |
| | REQUIREMENT. THIS WILL AFFECT OTHER ASPECTS OF THE |
| | STRUCTURE AND BUILDING. SEE OTHER COMMENTS BELOW. |
| | THIS COMMENT IS ENTIRELY BASED ON THE DECLARED SQ FT ON |
| | PLANS AND CALCULATIONS WHICH DO NOT COORDINATE WITH THE |
| | ACTUAL BUILDING. |
| | PLEASE ALSO SEE SHEET SP-1 WHICH ALSO DECLARES THREE |
| | SEPARATE BUILDINGS WHICH BASED ON STRUCTURAL AND |
| | ARCHITECTURAL PLANS IS NOT THE CASE. |
| | WHAT IS THE INTENT OF DESIGN? ELECTRICAL PLANS HAVE |
| | BEEN REVISED HOWEVER NOW SHOWING THREE SEPARATE |
| | SERVICES BEING PROPOSED, ONE FOR EACH TENANT SPACE. SEE |
| | ELECTRICAL COMMENTS BELOW AS THREE SERVICES ARE NOT |
| | PERMITTED TO THIS ONE BUILDING AS SHOWN. |
| | COORDINATION OF UNITS NEEDS TO BE DONE ON PLANS. |
| | WHERE A SHEETS INDICATE WAREHOUSE *B*, THE ELECTRICAL |
| | SHEETS INDICATE WAREHOUSE *A*> ETC |
| | |
| | 4) NOTE: PLEASE SEE THE NEW SUBMITTED METHOD *C* FLA |
| | COM FORM DOES NOT CORRELATE WITH PLANS. PLEASE SEE THE |
| | SQ FT FOR BUILDING AREA ON PLANS IS SUBSTANTIALLY |
| | GREATER THAN THAT ON THE CALCULATIONS SUBMITTED. |
| | PLEASE ALSO SEE THE FOLLOWING TEXT FOR BUILDING WITH |
| | MULTIPLE OCCUPANCY USE IN AREAS. ONLY WHEN THE |
| | ADDITIONAL AREAS ARE LESS THAN 5% MAY THE MAJORITY AREA |
| | USE BE PERMITTED. |
| | METHOD *C* IS FOR BUILDING AREA, YET THERE ARE SEVERAL |
| | AREAS WHICH THE OCCUPANCY IS GREATER THAN 5% OF THE |
| | MAIN USE. |
| | PLEASE ADJUST. THE FOLLOWING TEXT IS TAKEN DIRECTLY |
| | FROM THE FLORIDA BUILDING CODE. |
| | |
| | **** |
| | 13-101.1.4 BUILDINGS WITH MULTIPLE OCCUPANCY TYPES. |
| | WHEN A BUILDING CONTAINS MORE THAN ONE OCCUPANCY TYPE, |
| | EACH PORTION OF THE BUILDING SHALL CONFORM TO THE |
| | REQUIREMENTS FOR THE OCCUPANCY HOUSED THEREIN. |
| | EXCEPTIONS: |
| | 1. WHERE MINOR OCCUPANCY USE DOES NOT OCCUPY MORE THAN |
| | 5 PERCENT OF THE FLOOR AREA OF THE BUILDING, THE MAJOR |
| | USE SHALL BE CONSIDERED THE BUILDING OCCUPANCY. **** |
| | |
| | 5) NOTE: PLEASE BE SURE ALL INFORMATION ON PLANS WITH |
| | RESPECT TO BUILDING COMPONENTS AND LIGHTING CORRELATE |
| | WITH THE PLANS. ONE EXAMPLE GIVEN IS THE EXTERIOR |
| | LIGHTING WHICH DOES NOT CORRELATE. |
| | ** ONE EXAMPLE IS THE INFORMATION ON THE LIGHTING |
| | FIXTURE LEGEND IS NOT CLEAR. WATTAGES, TYPES ETC SHOWN. |
| | NO DETERMINATION FOR CODE COMPLIANCE AND COORDINATION |
| | OF THE IDR CAN BE DONE. |
| | ** ANOTHER EXAMPLE: |
| | THE SUBMITTED PLANS FOR EXTERIOR LIGHTING NOTE 100W |
| | FIXTURES, THE IDR INDICATES 250WATT FIXTURES AND THE |
| | FIXTURE LEGEND DOES NOT INDICATE ANY SPECIFIC TYPE OF |
| | EXTERIOR FIXTURES DETERMINATION FOR CODE COMPLIANCE CAN |
| | NOT BE ACHIEVED. |
| | 13-415.2, 13-415.2.ABC.1.3, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | REQUIRED LIGHTING CONTROLS PER FBC 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE PROVIDE MORE INFORMATION ON THE LIGHTING CONTROL |
| | PANEL. THE SYMBOL LEGEND STATES THE OVER RIDE SHALL BE |
| | HIGH BAY OCCUPANCY SENSORS WITH AN OVER RIDE TIME OF |
| | 4HRS. |
| | THIS IS NOT CLEAR HOW THIS IS POSSIBLE WHEN EVERY KNOWN |
| | OCCUPANCY SENSOR DEVICE TO THIS OFFICE FROM MOST |
| | MANUFACTURES IS MAXIMUM 30MINS AFTER THE LAST SENSING |
| | OF THE OCCUPANT. PLEASE SEE SECTION 13-415.1.ABC.1.1 OF |
| | THE FBC WHICH DOES NOT PERMIT AN OVER RIDE OF MORE THAN |
| | 30MINS WITH THE USE OF OCCUPANCY SENSORS AS OVERRIDES. |
| | PLEASE ALSO SEE PLANS WHICH INDICATE A *S* WHICH BY THE |
| | SYMBOL LEGEND IS A SINGLE POLE SINGLE THROW SWITCH. |
| | THIS TYPE OF DEVICE WILL NOT MEET THE MINIMUM |
| | REQUIREMENTS OF THE FBC SECTIONS GIVEN NOR WILL IT |
| | PROVIDE AUTOMATIC SHUT OFF DURING AN OVER RIDE. |
| | THERE MAY BE SOME SORT OF MISPRINT WITH THE WORDING ON |
| | SYMBOL LEGEND. |
| | PLEASE SEE THERE ARE ROOMS AND AREAS WHICH ARE MISSING |
| | LIGHTS AND CONTROLS PER SECTIONS GIVEN. ARCHITECTURAL |
| | PLANS INDICATE LIGHTS NEXT TO AHU ROOM YET NO |
| | INFORMATION ON ELECTRICAL PLANS IN FACT THIS ROOM IS |
| | BLANK. |
| | IN MEETING HELD BEFORE PLANS WERE SUBMITTED IT WAS |
| | REQUESTED TO SUPPLY THE MANUFACTURES SPECS/CUT SHEETS |
| | ON THE PROPOSED LIGHTING CONTROL PANEL(S) AND ALL |
| | EQUIPMENT. THE SHEETS SUBMITTED DO NOT PROVIDE |
| | INFORMATION ON REQUIRED LIGHTING CONTROLS PER SECTIONS |
| | OF THE CODE GIVEN ABOVE. IN FACT THE SHEETS EXPAND ON |
| | THE DIMMING POSSIBILITIES WHICH IS OK HOWEVER DOES NOT |
| | PROVIDE INFORMATION ON CONTROLS OF LIGHTS TO MEET |
| | MINIMUM SHUT OFF REQUIREMENTS OF THE FLORIDA BUILDING |
| | CODE FOR ENERGY EFFICIENCY. |
| | ALSO AS GONE OVER IN MEETING PLEASE BE SURE DOCUMENTS |
| | CONTAIN A LISTING FROM ONE OF THE ADOPTED NATIONALLY |
| | RECOGNIZED TESTING LABORATORIES. ( NRTL) PER 110.3. |
| | IE: UL, ETL< MET< TUV< TUV AMERICA< CSA ETC. |
| | |
| | 7) NOTE: THE PLANS NOW SHOW NEW ELECTRICAL GATE AND |
| | LIGHT POLE OUTSIDE THE PROPERTY LING BASED ON SURVEY |
| | AND SITE PLANS. THIS IS NOT PERMITTED. THE MAY BE FED |
| | FROM A SEPARATE OFF THE PROPERTY HOWEVER IT MAY NOT |
| | CROSS THE PROPERTY. THE PROPOSED GATE IS ALSO NOT PART |
| | OF THE SHOWN PROPERTY AND IS NOT INCLUDED. |
| | PLEASE KNOW THIS INFORMATION WILL BE ROUTED TO FIRE |
| | MARSHAL, ZONING AND BUILDING REVIEWERS. |
| | 230, FBC SEE NOTES FROM OTHER TRADES. |
| | |
| | 8) NOTE: PLEASE SEE NEC 230.2. THE RISER NOW SHOWS A |
| | PROPOSED THREE SEPARATE SERVICES WHICH CAN NOT BE |
| | GRANTED BASE ON 230.2. THE SERVICE SIZE, VOLTAGE, |
| | OCCUPANCY ETC DOES NOT MEET ALLOWANCE FOR OTHER TWO |
| | ADDITIONAL SERVICES. THIS IS ONE BUILDING BY ALL |
| | DEFINITIONS LISTED ABOVE IN THE FLORIDA BUILDING CODE. |
| | PLEASE ALSO SEE 2005 NEC HANDBOOK DIAGRAM. BY |
| | ILLUSTRATIONS THIS IS ONE BUILDING AND BY RISER THESE |
| | ARE THREE SEPARATE SERVICES. |
| | PLEASE REVISE RISER. |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTES AND IN MEETING HELD |
| | BEFORE PLANS WERE RESUBMITTED IT WAS DISCUSSED THAT ANY |
| | CONTROLS FOR EGRESS LIGHTING SHALL BE FAIL SAFE ON PER |
| | NFPA-101 7.8.1.2.2, FBC 1006.1.2 |
| | |
| | 10) NOTE: PLEASE KNOW THERE MAY ALSO BE NEW COMMENTS |
| | WITH RESPECT TO AREA ABOVE OFFICES. THIS AREA IS SHOWN |
| | TO CONTAIN A NEW 42 INCH HIGH WALL HOWEVER CLEAR STAIRS |
| | ARE SHOWN TO AREA YET NO OTHER INFORMATION IS SHOWN. IN |
| | FACT THE ARCHITECTURAL PLANS DO NOT SHOW OR NOTE ANY |
| | STAIRS THEY IN FACT INDICATE THIS SAME ROOM AS *STORAGE |
| | AREA*. THE ELECTRICAL PLANS CLEARLY NOTE THIS SAME ROOM |
| | AS STAIR WITH LIGHTING TO ABOVE. HOWEVER THEY DO NOT |
| | SHOW THE ACTUAL STAIRS. |
| | ELECTRICAL PLANS ALSO INDICATE FUTURE ELEVATOR YET |
| | INFORMATION ON OTHER PLANS AND SHEETS DO NOT SHOW ANY |
| | OF THESE ITEMS. |
| | PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR EGRESS AREAS. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2 WITH RESPECT TO MORE |
| | THAN ONE FLOOR. SEE FBC FOR FLOOR DEFINITIONS. |
| | AS SPECIFICALLY NOTED ON PREVIOUS REVIEW TO PROVIDE |
| | EGRESS LIGHTING FOR STAIRS THE RESPONSE FROM DESIGNER |
| | WAS THIS WAS PREVIOUSLY SUBMITTED. THE PHOTO-METRICS |
| | SUBMITTED TO NOT SHOW LEVELS FOR EITHER STAIRS. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.1, .2.2. |
| | SEE SHEET E-2B WHICH INDICATES TO LIGHTS ABOVE FOR |
| | CONTROLS ETC HOWEVER THERE IS NO 2ND FLOOR LIGHTING OR |
| | POWER PLANS FOR THIS END OF THE BUILDING. |
| | SEE COMMENTS FROM OTHER TRADES AND BE AWARE OF NOTED |
| | REQUIREMENTS FOR EGRESS, LIGHTING CONTROLS ETC. |
| | PLEASE SEE FBC13-415.1.ABC.1, FOR AREAS CONSIDERED |
| | SEPARATE FLOORS. |
| | |
| | ** ONE SET OF THE PLANS WILL BE RETAINED. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE GROUNDING ELECTRODE |
| | SYSTEMS AS SHOWN. RISER INDICATES ALL GOING TO FOOTER |
| | STEEL. THIS IS AN EXISTING BUILDING AND IF THERE IS NOT |
| | CURRENTLY A BOND TO FOOTER STEEL NEW ONES WILL NOT BE |
| | REQUIRED INTO EXISTING FOOTING STEEL. THIS IS ONLY |
| | NOTED AS ALL NEW FOOTER STEEL IS REQUIRED TO BE BONDED. |
| | ** NOTED FOR INFORMATION ONLY. |
| | |
| | 12) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO |
| | MINIMUM REQUIREMENTS OF DEVICES FOR FIRE ALARM SYSTEM. |
| | RESPONSE MENTIONS CANDELA LEVELS AND HEIGHTS ARE ON ICE |
| | RINK PLANS HOWEVER BASED ON THE PLANS SUBMITTED ONLY |
| | THE CD LEVELS AND HEIGHTS IN RINK ARE SHOWN. PLEASE SEE |
| | SECTIONS 11-4.28.1, .2 AND .3. ALL LOCATIONS FOR ADA |
| | ARE REQUIRED TO BE MET; ALL PULL STATION HEIGHTS, |
| | STROBE HEIGHTS, ETC. |
| | PLEASE KNOW THERE ARE MORE THAN THE ICE RINK AREAS |
| | WHICH REQUIRE DEVICES. |
| | SEE COMMENTS FROM FIRE REVIEW FOR MINIMUM NFPA-72 |
| | REQUIREMENTS AS FULL PROTECTION OF ANY FIRE ALARM |
| | SYSTEM MAY NOT ONLY BE RINK AREA. |
| | |
| | 13) NOTE: PLEASE SEE 210.70 FOR MISSING LIGHTING |
| | REQUIRED IN AHU ROOM. |
| | PLEASE SEE 210.63, 210.8 FOR SERVICE RECEPTACLE. |
| | |
| | 14) NOTE: THE AIC RATINGS AND FAULT CURRENTS ARE SHOWN |
| | HOWEVER THE RATINGS AT MAINS NEED TO BE SHOWN. |
| | 110.9 |
| | THE ANALYSIS SUBMITTED IS FOR MAINS AT EACH UNIT. IF 42 |
| | K IS THE RATING FOR SBA, THE RATING FOR THE MAIN WILL |
| | BE SUBSTANTIALLY HIGHER AND NO INFORMATION FOR ANY OF |
| | THE MAINS IS SHOWN. |
| | |
| | 15) NOTE: PLANS INDICATE HWB WHICH IS NOTED FOR HOUSE |
| | ELECTRICAL SITE LIGHTING ETC YET THIS PANEL IS IN ONE |
| | OF THE TENANT SPACES. |
| | THE WAREHOUSE SPACE *B* IS CURRENTLY OCCUPIED HOW CAN |
| | IT POSSIBLE THE PANELS ARE BLANK WITH NO CIRCUITING? |
| | HOUSE POWER/SITE LIGHTING MAY NOT BE FED FROM PANEL IN |
| | TENANT SPACE. |
| | |
| | 16) NOTE: PLEASE ADJUST DESIGNATIONS OF FUTURE BACK UP |
| | POWER PANELS. THESE ARE NOT *EMERGENCY* BACK UP |
| | SYSTEMS. PLEASE SEE DEFINITIONS IN NEC 700, 701 AND |
| | 702. |
| | THESE PANELS ARE OPTIONAL STAND-BY. |
| | |
| | 17) NOTE: PLEASE COORDINATE THE LOADS FOR THE WATER |
| | HEATERS ON THE LOAD CALCULATIONS WITH THAT OF THE LOADS |
| | ON THE PANELS. THE LOADS ON PANELS FAR EXCEED THAT OF |
| | THE LOAD ON CALCULATIONS. ONE WATER HEATER ALONE |
| | EXCEEDS LOAD SHOWN FOR ALL THREE. |
| | PLEASE ALSO SEE 422.13 FOR THE 2005 NEC AS THE LOAD IS |
| | A CONTINUOUS LOAD AND SHALL BE FIGURED AT 125%. |
| | |
| | 18) NOTE: PLEASE SEE FBC 3006.2 FOR FUTURE ELEVATOR |
| | LIFT. |
| | |
| | 19) NOTE: PLEASE SEE 620.22,23 AND 24 FOR FUTURE |
| | ELEVATOR EQUIPMENT ROOM. THIS IS NOTED AS COMMENTS FROM |
| | OTHER REVIEWS AND USE OF SECOND FLOOR AREA HAS NOT BEEN |
| | DETERMINED AT THIS TIME AS VERTICAL ACCESSIBILITY MAY |
| | BE REQUIRED AT THIS TIME. |
| | |
| | 20) NOTE: PLEASE SEE PREVIOUS REVIEW AS IT WAS |
| | REQUESTED TO SUBMIT THE MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE PROPOSED ATS. THIS WAS GONE OVER IN MEETING |
| | ALSO. THE PLANS NOW SHOW THIS PROPOSED ATS ON SHEET E-6 |
| | HOWEVER THE INFORMATION IS NOT CLEAR AND VERY FAINT AND |
| | BLURRY. |
| | PLEASE SUBMIT SEPARATE SHEETS OR IMPROVE ON PRINTED |
| | SHEET. |
| | 110.3, 90.7 |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION, |
| | CLARITY ETC. |
| | |
| | 21) NOTE: PLEASE SUBMIT/SHOW SCHEDULE FOR SBA AS OTHER |
| | PANELS ARE SHOWN GIVING THE SPECIFIC INFORMATION FOR |
| | EQUIPMENT. |
| | 408.4, 110.9, 90.7 ETC |
| | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION, |
| | CLARITY AND COORDINATION. |
| | |
| | 22) NOTE: PLEASE PROVIDE VOLTAGE DROP CALCULATIONS FOR |
| | FEEDERS/BRANCH CIRCUITS PER 13-413.1ABC.1. |
| | VOLTAGE DROP. |
| | 13-413.1.ABC.1.1 FEEDERS. |
| | FEEDER CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE |
| | DROP OF 2 PERCENT AT DESIGN LOAD. |
| | 13-413.1.ABC.1.2 BRANCH CIRCUITS. |
| | BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM |
| | VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD. |
| | |
| | ** SUBMITTED FOR WAREHOUSE A AND B, HOWEVER NEED SITE |
| | BRANCH CIRCUIT(S) |
| | |
| | 23) NOTE: PLEASE BE SURE THE FOLLOWING IS LISTED ON |
| | ELECTRICAL PLANS. THIS IS TAKEN FROM THE FBC SECTIONS. |
| | **13-413.1.ABC.2.1 DRAWINGS. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 |
| | DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDED |
| | TO THE BUILDING OWNER, INCLUDING: |
| | 1. A SINGLE-LINE DIAGRAM OF THE BUILDING ELECTRICAL |
| | DISTRIBUTION SYSTEM AND |
| | 2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR |
| | ALL DISTRIBUTION. |
| | 13-413.1.ABC.2.2 MANUALS. |
| | CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING |
| | MANUAL AND MAINTENANCE MANUAL BE PROVIDED TO THE |
| | BUILDING OWNER. THE MANUALS SHALL INCLUDE, AT A |
| | MINIMUM, THE FOLLOWING: |
| | 1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED |
| | OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING |
| | MAINTENANCE. |
| | 2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH |
| | PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED |
| | ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY |
| | IDENTIFIED. |
| | 3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED |
| | SERVICE AGENCY. |
| | |
| | 24) NOTE: PLEASE BE SURE PANEL SCHEDULES ARE COMPLETE |
| | WITH LOADS AND SPECIFIC APPLIANCES. FOR EXAMPLE: R1B8 |
| | WHICH BY THE PANEL SCHEDULE ONLY LIST VIEWING ROOM |
| | RECEPTACLES LOOKS TO BE A HALF SWITCH RECEPTACLE UNDER |
| | THE SINK WHICH WOULD LEND TO A DISPOSAL. DISPOAL WOULD |
| | BE REQUIRED TO BE ON A SEPARATE CIRCUIT WITH LOADS |
| | FIGURED. |
| | PLEASE ALSO VERIFY LOAD SHOWN FOR WASHER AS THIS IS |
| | NOTED A 1KVA. |
| | THE PLANS APPEAR TO SHOW A REFRIGERATOR FOR CIRCUIT |
| | R1B20 YET THE PANEL SCHEDULE DOES NOT INDICATE ANY |
| | CIRCUIT. IN FACT THE SCHEDULE IS BLANK FOR THIS |
| | LOCATION. |
| | |
| | PLEASE COORDINATE ALL, THESE ARE A FEW EXAMPLES AND ARE |
| | NOT ALL. |
| | PLEASE SEE 408.4,240.4,310.16, AND 220. |
| | |
| | |
| | 25) NOTE: ** IT IS IMPORTANT TO KNOW THAT AS THERE IS A |
| | SUBSTANTIAL AMOUNT OF INFORMATION NOT YET CLEAR FOR |
| | USE, OCCUPANCY, FLOORS, LIGHTING ETC THERE MAY VERY |
| | WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN |
| | NOT BE MADE AT THIS TIME. |
| | PLEASE ALSO BE AWARE OF FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY NOTED |
| | AT THIS TIME AS THERE WERE SOME CODE SECTIONS REPEATED |
| | FROM PREVIOUS REVIEW WHICH WAS NOT ADDRESSED. |
| | ** ONE COMPLETE SET OF PLANS WILL BE RETAINED BY THIS |
| | OFFICE ALONG WITH ENERGY CALCULATIONS. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |