2009-12-02 12:33:28****PROVISO ITEMS FROM PREVIOUS LISTS*****
 ***REVISION, SHEETS T, 001, 212, 222, DOCS FROM DCA***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 4. ADDRESSED - FBC1024.12, PER BUILDING OFFICIAL, SEATS
 CANNOT BE REMOVABLE. THIS WILL BE ISSUED WITH PROVISO,
 ALL SEATS FIXED, REMOVE SEATS AT ACCESSIBLE AREA.
  
 8. ADDRESSED - (VERTICAL ACCESSIBILITY AND ACCESSIBLE
 SEATING IS REQUIRED TO EAST MEZZANINE AND FIRST FLOOR
 RAISED SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN
 TO SHOW COMPLIANCE.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER.
  
 ARCHITECT'S RESPONSE THAT TAVARES IS PHASE 2 EOR, ALI
 IS THRESHOLD INSPECTOR IS ACKNOWLEDGED. ALL "PHASES"
 WERE COMPLETED UNDER ONE PERMIT, ONE STRUCTURE. PLEASE
 HAVE ENGINEERS SEE FAC61G15-31, RESPONSIBILITY RULES
 FOR PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF
 STRUCTURES. THERE IS TO BE ONE ENGINEER OF RECORD FOR
 THE STRUCTURE. THAT ENGINEER SPECIFIES DESIGN CRITERIA,
 AND REVIEWS THE DELEGATED ENGINEERING TO COMFIRM
 CONFORMANCE WITH EOR'S DESIGN CRITERIA. THROUGHOUT THIS
 PROJECT, REVISIONS HAVE BEEN PROCESSED WITH PROVISO
 THAT EOR REVIEW THE DELEGATED ENGINEERING. FOUNDATIONS
 WERE DESIGNED BY ONE ENGINEER, EXTERIOR, MEZZANINES,
 STAIRS, ETC. DESIGNED BY ANOTHER ENGINEER. IT IS NOT
 CLEAR WHICH ENGINEER IS ENGINEER OF RECORD FOR THE
 STRUCTURE, WHICH ENGINEER HAS DELEGATED, WHICH ENGINEER
 IS RESPONSIBLE FOR THE OVERALL DESIGN. PLEASE HAVE THE
 ENGINEERS REVIEW FAC61G15-31 AND CONFIRM THAT EOR HAS
 REVIEWED DELEGATED ENGINEERING (MAY BE DONE BY LETTER).
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS.
  
 10. ADDRESSED - FBC1023.6, EITHER PROVIDE SAFE
 DISPERSAL AREA OR ACCESSIBLE ROUTE TO THE PUBLIC WAY
 (EXIT DISCHARGE).
  
 11. FBC1019.1.4, SEE PROVISO ON PLAN, STAIRS TO COMPLY
 WITH FBC1019.1.4.
  
 SHEET 722 ON HOLD PENDING RECEIPT OF SPRINKLER HEAD
 SPEC SHEETS; UPON RECEIPT THE REQUEST FOR ALTERNATE
 MATERIALS & METHODS TO BE FORWARDED TO BUILDING
 OFFICIAL. PLEASE NOTE THAT SHEET 722 REFERS TO FP3 &
 FP4 WHICH HAVE NOT YET BEEN REVIEWED AND WHICH WERE NOT
 SUBMITTED WITH THIS REVISION. I HAVE TAKEN ONE SET FROM
 THE MECHANICAL/FIRE/ELEC REVISION FOR REFERENCE.
  
 13. ADDRESSED - COMPLY WITH FBC1006.1, MEANS OF EGRESS
 ILLUMINATION, INCLUDING BLEACHER STAIRS.
  
 14. ADDRESSED FOR ARCHITECT; STATEMENT OF COMPLIANCE
 FOR THRESHOLD BUILDING REQUIRED, FS553.79(7)(D).
  
 IS THE ARCHITECT MAKING THIS STATEMENT ON BEHALF OF THE
 ENGINEERS AS WELL, OR WILL THEY PROVIDE THEIR OWN
 STATEMENT IF THIS WAS NOT INCLUDED ON THEIR PLANS?
 PLEASE ADVISE
  
 15. ADDRESSED - EXIT FROM DOOR (FIRST FLOOR) TO PUBLIC
 WAY IS BLOCKED BY LANDSCAPING AND ELECTRIC EQUIPMENT.
 CONTINUOUS PATH REQUIRED FBC10. SITE PLAN 001 REVISED
 TO SHOW BLDG CODE COMPLIANCE
  
  