| 2009-12-02 12:33:28 | ****PROVISO ITEMS FROM PREVIOUS LISTS***** |
| | ***REVISION, SHEETS T, 001, 212, 222, DOCS FROM DCA*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 4. ADDRESSED - FBC1024.12, PER BUILDING OFFICIAL, SEATS |
| | CANNOT BE REMOVABLE. THIS WILL BE ISSUED WITH PROVISO, |
| | ALL SEATS FIXED, REMOVE SEATS AT ACCESSIBLE AREA. |
| | |
| | 8. ADDRESSED - (VERTICAL ACCESSIBILITY AND ACCESSIBLE |
| | SEATING IS REQUIRED TO EAST MEZZANINE AND FIRST FLOOR |
| | RAISED SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN |
| | TO SHOW COMPLIANCE. |
| | |
| | 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON |
| | THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER. |
| | |
| | ARCHITECT'S RESPONSE THAT TAVARES IS PHASE 2 EOR, ALI |
| | IS THRESHOLD INSPECTOR IS ACKNOWLEDGED. ALL "PHASES" |
| | WERE COMPLETED UNDER ONE PERMIT, ONE STRUCTURE. PLEASE |
| | HAVE ENGINEERS SEE FAC61G15-31, RESPONSIBILITY RULES |
| | FOR PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF |
| | STRUCTURES. THERE IS TO BE ONE ENGINEER OF RECORD FOR |
| | THE STRUCTURE. THAT ENGINEER SPECIFIES DESIGN CRITERIA, |
| | AND REVIEWS THE DELEGATED ENGINEERING TO COMFIRM |
| | CONFORMANCE WITH EOR'S DESIGN CRITERIA. THROUGHOUT THIS |
| | PROJECT, REVISIONS HAVE BEEN PROCESSED WITH PROVISO |
| | THAT EOR REVIEW THE DELEGATED ENGINEERING. FOUNDATIONS |
| | WERE DESIGNED BY ONE ENGINEER, EXTERIOR, MEZZANINES, |
| | STAIRS, ETC. DESIGNED BY ANOTHER ENGINEER. IT IS NOT |
| | CLEAR WHICH ENGINEER IS ENGINEER OF RECORD FOR THE |
| | STRUCTURE, WHICH ENGINEER HAS DELEGATED, WHICH ENGINEER |
| | IS RESPONSIBLE FOR THE OVERALL DESIGN. PLEASE HAVE THE |
| | ENGINEERS REVIEW FAC61G15-31 AND CONFIRM THAT EOR HAS |
| | REVIEWED DELEGATED ENGINEERING (MAY BE DONE BY LETTER). |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS. |
| | |
| | 10. ADDRESSED - FBC1023.6, EITHER PROVIDE SAFE |
| | DISPERSAL AREA OR ACCESSIBLE ROUTE TO THE PUBLIC WAY |
| | (EXIT DISCHARGE). |
| | |
| | 11. FBC1019.1.4, SEE PROVISO ON PLAN, STAIRS TO COMPLY |
| | WITH FBC1019.1.4. |
| | |
| | SHEET 722 ON HOLD PENDING RECEIPT OF SPRINKLER HEAD |
| | SPEC SHEETS; UPON RECEIPT THE REQUEST FOR ALTERNATE |
| | MATERIALS & METHODS TO BE FORWARDED TO BUILDING |
| | OFFICIAL. PLEASE NOTE THAT SHEET 722 REFERS TO FP3 & |
| | FP4 WHICH HAVE NOT YET BEEN REVIEWED AND WHICH WERE NOT |
| | SUBMITTED WITH THIS REVISION. I HAVE TAKEN ONE SET FROM |
| | THE MECHANICAL/FIRE/ELEC REVISION FOR REFERENCE. |
| | |
| | 13. ADDRESSED - COMPLY WITH FBC1006.1, MEANS OF EGRESS |
| | ILLUMINATION, INCLUDING BLEACHER STAIRS. |
| | |
| | 14. ADDRESSED FOR ARCHITECT; STATEMENT OF COMPLIANCE |
| | FOR THRESHOLD BUILDING REQUIRED, FS553.79(7)(D). |
| | |
| | IS THE ARCHITECT MAKING THIS STATEMENT ON BEHALF OF THE |
| | ENGINEERS AS WELL, OR WILL THEY PROVIDE THEIR OWN |
| | STATEMENT IF THIS WAS NOT INCLUDED ON THEIR PLANS? |
| | PLEASE ADVISE |
| | |
| | 15. ADDRESSED - EXIT FROM DOOR (FIRST FLOOR) TO PUBLIC |
| | WAY IS BLOCKED BY LANDSCAPING AND ELECTRIC EQUIPMENT. |
| | CONTINUOUS PATH REQUIRED FBC10. SITE PLAN 001 REVISED |
| | TO SHOW BLDG CODE COMPLIANCE |
| | |
| | |