Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop E
Sequence Number 13
Notes
Date Text
2009-10-09 14:38:56 
 ** DENIED REVISION **
  
 1) NOTE: PLEASE BE SURE ALL SETS ARE COMPLETE WITH ALL
 REVISED SHEETS. ONE SET WAS MISSING A REVISED SHEET
 ES-1
  
 2) NOTE: PLEASE SEE SECOND FLOOR CORRIDOR WHERE
 OCCUPANCY SENSORS HAVE BEEN REMOVED AS THE METHOD OF
 CONTROLS. WHERE ARE THE REQUIRED OVER RIDES IF LIGHTING
 IS NOW GOING TO BE CONTROLLED BY TIMED SCHEDULING?
 PLEASE TAKE A LOOK AT ROOM 222, 223, WHERE ARE LIGHTING
 CONTROLS?
 WHAT ABOUT ROOM 125? WHAT TYPE OF CONTROL DEVICE IS
 THIS?
 CONTROLS IN MAIN ENTRANCE/LOBBY AREAS HAVE HAD CONTROLS
 REVISED HOWEVER IT IS NOT CLEAR WHERE ALL LIGHTING IS
 BEING CONTROLLED. PLEASE PROVIDE AN ENLARGED LAYOUT FOR
 THE COMMON AREAS. PLANS CONTAIN MANY ITEMS AND IT IS
 NOT CLEAR WHERE CONTROLS AND OVER RIDES ARE ALL
 LOCATED.
 13-415.1.ABC.1.1,.1.2, .1.3
  
 3) NOTE: PLEASE PROVIDE AN ENLARGED LAYOUT FOR NEW
 ELECTRICAL IN WAREHOUSE *B* AREA.
 PLANS INDICATE AN EXISTING FIRE PUMP HOWEVER IT IS NOT
 CLEAR IF THIS IS A LEGALLY REQUIRED FIRE PUMP. IT IS NO
 CLEAR OF THE LOCATION IN THE BUILDING IN WHICH THIS
 FIRE PUMP IS LOCATED. PLEASE SEE NFPA-70 695 AND
 NFPA-20 FOR LOCATIONS AND RATINGS OF WALLS ETC.
  
 4) NOTE: PLEASE EXPLAIN HOW PANEL RWB HAS NOW HAD LOAD
 INCREASED BY THE EXISTING PANELS AND LOADS BEING ADDED
 HOWEVER THE MAIN SERVICE LOAD CALCULATIONS HAVE NOT
 BEEN UPDATED. THE LOADS ARE THE SAME AS ON PREVIOUS E-6
 PLANS.
 THE SAME COMMENT IS FOR PANEL R1B WHICH NOW HAS REVISED
 LOAD FOR NEW PANEL R1BA, YET THE SERVICE LOADS HAVE NOT
 CHANGED?
 PLEASE SEE NEC 220 IN GENERAL AND UPDATE LOADS.
  
 5) NOTE: NO INFORMATION HAS YET BEEN SUBMITTED WITH
 RESPECT TO TWO SEPARATE PROPERTIES. NO ELECTRICAL SUCH
 AS SITE LIGHTING MAY CROSS PROPERTY LINES.
  
 6) NOTE: AS NO INFORMATION WAS SUBMITTED ON THE
 EXISTING FIRE PUMP AND JOCKEY PUMP THE NEW UNDER
 SERVICE ENTRANCE CONDUCTORS ETC COULD NOT BE VERIFIED
 AS BEING CODE COMPLIANT.
 ALSO COULD NOT VERIFY BONDING OF SERVICES AS NO
 INFORMATION WAS SHOWN. NEW SERVICE FOR FIRE PUMP AND
 THE EXISTING/NEW SERVICE NEEDS TO BE BONDED. 250.92,94
 ETC, 250.66
  
  
  
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717