| 2009-10-09 14:38:56 | |
| | ** DENIED REVISION ** |
| | |
| | 1) NOTE: PLEASE BE SURE ALL SETS ARE COMPLETE WITH ALL |
| | REVISED SHEETS. ONE SET WAS MISSING A REVISED SHEET |
| | ES-1 |
| | |
| | 2) NOTE: PLEASE SEE SECOND FLOOR CORRIDOR WHERE |
| | OCCUPANCY SENSORS HAVE BEEN REMOVED AS THE METHOD OF |
| | CONTROLS. WHERE ARE THE REQUIRED OVER RIDES IF LIGHTING |
| | IS NOW GOING TO BE CONTROLLED BY TIMED SCHEDULING? |
| | PLEASE TAKE A LOOK AT ROOM 222, 223, WHERE ARE LIGHTING |
| | CONTROLS? |
| | WHAT ABOUT ROOM 125? WHAT TYPE OF CONTROL DEVICE IS |
| | THIS? |
| | CONTROLS IN MAIN ENTRANCE/LOBBY AREAS HAVE HAD CONTROLS |
| | REVISED HOWEVER IT IS NOT CLEAR WHERE ALL LIGHTING IS |
| | BEING CONTROLLED. PLEASE PROVIDE AN ENLARGED LAYOUT FOR |
| | THE COMMON AREAS. PLANS CONTAIN MANY ITEMS AND IT IS |
| | NOT CLEAR WHERE CONTROLS AND OVER RIDES ARE ALL |
| | LOCATED. |
| | 13-415.1.ABC.1.1,.1.2, .1.3 |
| | |
| | 3) NOTE: PLEASE PROVIDE AN ENLARGED LAYOUT FOR NEW |
| | ELECTRICAL IN WAREHOUSE *B* AREA. |
| | PLANS INDICATE AN EXISTING FIRE PUMP HOWEVER IT IS NOT |
| | CLEAR IF THIS IS A LEGALLY REQUIRED FIRE PUMP. IT IS NO |
| | CLEAR OF THE LOCATION IN THE BUILDING IN WHICH THIS |
| | FIRE PUMP IS LOCATED. PLEASE SEE NFPA-70 695 AND |
| | NFPA-20 FOR LOCATIONS AND RATINGS OF WALLS ETC. |
| | |
| | 4) NOTE: PLEASE EXPLAIN HOW PANEL RWB HAS NOW HAD LOAD |
| | INCREASED BY THE EXISTING PANELS AND LOADS BEING ADDED |
| | HOWEVER THE MAIN SERVICE LOAD CALCULATIONS HAVE NOT |
| | BEEN UPDATED. THE LOADS ARE THE SAME AS ON PREVIOUS E-6 |
| | PLANS. |
| | THE SAME COMMENT IS FOR PANEL R1B WHICH NOW HAS REVISED |
| | LOAD FOR NEW PANEL R1BA, YET THE SERVICE LOADS HAVE NOT |
| | CHANGED? |
| | PLEASE SEE NEC 220 IN GENERAL AND UPDATE LOADS. |
| | |
| | 5) NOTE: NO INFORMATION HAS YET BEEN SUBMITTED WITH |
| | RESPECT TO TWO SEPARATE PROPERTIES. NO ELECTRICAL SUCH |
| | AS SITE LIGHTING MAY CROSS PROPERTY LINES. |
| | |
| | 6) NOTE: AS NO INFORMATION WAS SUBMITTED ON THE |
| | EXISTING FIRE PUMP AND JOCKEY PUMP THE NEW UNDER |
| | SERVICE ENTRANCE CONDUCTORS ETC COULD NOT BE VERIFIED |
| | AS BEING CODE COMPLIANT. |
| | ALSO COULD NOT VERIFY BONDING OF SERVICES AS NO |
| | INFORMATION WAS SHOWN. NEW SERVICE FOR FIRE PUMP AND |
| | THE EXISTING/NEW SERVICE NEEDS TO BE BONDED. 250.92,94 |
| | ETC, 250.66 |
| | |
| | |
| | |
| | |
| | |
| | **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |