| 2009-09-29 16:42:01 | ****PROVISOS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | NUMBERING FROM PREVIOUS BUILDING REVIEW #11 |
| | |
| | 4. FBC1024.12, PER BUILDING OFFICIAL, SEATS CANNOT BE |
| | REMOVABLE. THIS WILL BE ISSUED WITH PROVISO, ALL SEATS |
| | FIXED, REMOVE SEATS AT ACCESSIBLE AREA. |
| | |
| | 8. VERTICAL ACCESSIBILITY AND ACCESSIBLE SEATING IS |
| | REQUIRED TO EAST MEZZANINE AND FIRST FLOOR RAISED |
| | SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN TO SHOW |
| | COMPLIANCE. |
| | |
| | 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON |
| | THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER. |
| | |
| | 10. FBC1023.6, EITHER PROVIDE SAFE DISPERSAL AREA OR |
| | ACCESSIBLE ROUTE TO THE PUBLIC WAY (EXIT DISCHARGE). |
| | |
| | 11. FBC1019.1.4, SEE PROVISO ON PLAN. EAST STAIR HAS |
| | OPENINGS WITHIN 10FT; REVISE TO SHOW COMPLIANCE WITH |
| | FBC1019.1.4. |
| | |
| | 13. PROVISO - COMPLY WITH FBC1006.1, MEANS OF EGRESS |
| | ILLUMINATION, INCLUDING BLEACHER STAIRS. |
| | |
| | 14. STATEMENT OF COMPLIANCE FOR THRESHOLD BUILDING |
| | REQUIRED, FS553.79(7)(D). |
| | |
| | 15. REVISE SHEET LP1 AS DISCUSSED - EXIT FROM DOOR |
| | (FIRST FLOOR) TO PUBLIC WAY IS BLOCKED BY LANDSCAPING |
| | AND ELECTRIC EQUIPMENT. CONTINUOUS PATH REQUIRED FBC10 |