Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop E
Sequence Number 12
Notes
Date Text
2009-08-26 18:51:09** PROVISO/REDLINED PLANS**
  
 *** THE FOLLOWING ARE SET FORTH AS A PROVISO. SOME
 ITEMS *MUST BE COMPLETED FOR PHASE #1.
  
 1) NOTE: PHASE #1, EM-1 FIXTURES SHALL BE INSTALLED AT
 TEMPORARY EXIT, ENTRANCE ON THE EAST SIDE OF BUILDING
 FOR OCCUPANCY. EM-1 FIXTURES SHALL ALSO BE INSTALLED AT
 THIS TIME ON SOUTH SIDE OF BUILDING WHERE EGRESS FROM
 ICE RINK AREA TO PARKING LOT IS TAKING PLACE. THIS WAS
 CONFIRMED WITH FIRE MARSHAL.
 THIS WAS REVISED ON TCO TO BE DONE AT THIS TIME AS A
 CONDITION.
 NFPA- 101 7.8.1.3, 7.9.1.2, .2.2.
  
 2) NOTE: THE ELECTRICAL LIGHTING AND ANY OTHER POWER
 CROSSING PROPERTY LINE SHALL NOT BE DONE UNTIL
 RE-PLAT/UNITY OF TITLE HAS TAKEN PLACE. THIS WAS NOTED
 ON PREVIOUS REVIEW AND REVIEW BACK ON DECEMBER 25TH
 2008.
 THIS IS FOR PCN 74434329000001230.
 INFORMATION HAS BEEN GIVEN TO ATTORNEY FOR OWNER.
  
 3) NOTE: INFORMATION ON UPS TO PROVIDE BACK UP POWER
 FOR THE *D* TYPE FIXTURES IS STILL NEEDED. PLEASE SEE
 NEC 700.12 FOR ACCEPTABLE MEANS OF BACK UP POWER. THE
 GENERATOR MAY NOT BE USED AS IT IS AN OPTIONAL STAND-BY
 SYSTEM UNDER NEC 702.
  
 ** FIRE ALARM, LOW VOLTAGE SYSTEMS ARE UNDER SEPARATE
 PERMITS.
  
 **** IMPORTANT:
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  