| Plan Review Notes For Permit 08090611 |
| Permit Number |
08090611 |
|
| Review Stop |
B |
| Sequence Number |
12 |
|
| Notes |
| Date |
Text |
| 2009-08-06 17:38:10 | ****PROVISOS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | NUMBERING FROM PREVIOUS BUILDING REVIEW #11 | | | | | | 4. FBC1024.12, PER BUILDING OFFICIAL, SEATS CANNOT BE | | | REMOVABLE. THIS WILL BE ISSUED WITH PROVISO, ALL SEATS | | | FIXED, REMOVE SEATS AT ACCESSIBLE AREA. | | | | | | 8. VERTICAL ACCESSIBILITY AND ACCESSIBLE SEATING IS | | | REQUIRED TO EAST MEZZANINE AND FIRST FLOOR RAISED | | | SEATING. EITHER PROVIDE A WAIVER OR REVISE PLAN TO SHOW | | | COMPLIANCE. | | | | | | 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON | | | THIS JOB, FAC61G15-31. THIS MAY BE DONE BY LETTER. | | | | | | 10. FBC1023.6, EITHER PROVIDE SAFE DISPERSAL AREA OR | | | ACCESSIBLE ROUTE TO THE PUBLIC WAY (EXIT DISCHARGE). | | | | | | 11. FBC1019.1.4, SEE PROVISO ON PLAN. EAST STAIR HAS | | | OPENINGS WITHIN 10FT; REVISE TO SHOW COMPLIANCE WITH | | | FBC1019.1.4. | | | | | | 13. PROVISO - COMPLY WITH FBC1006.1, MEANS OF EGRESS | | | ILLUMINATION, INCLUDING BLEACHER STAIRS. | | | | | | 14. STATEMENT OF COMPLIANCE FOR THRESHOLD BUILDING | | | REQUIRED, FS553.79(7)(D). | | | | | | 15. IMPACT FEES REQUIRED FOR NEW MEZZANINES, 233-5025. | | | THIS REVISION IS SUBJECT TO RECEIPT OF STAMPED PLANS | | | AND RECEIPT. | | | |
|