| 2009-08-21 19:50:35 | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | ** THE ELECTRICAL NOTES BELOW WERE GONE OVER WITH |
| | ENGINEER???S OFFICE ON 8/21/09. CHANGES ARE TO BE MADE |
| | AND SHEETS REVISED. |
| | |
| | |
| | |
| | 1) NOTE: ELECTRICAL SITE PLANS NOW ONCE AGAIN INCLUDE |
| | LIGHTING BEING FED FROM THIS BUILDING ACROSS PROPERTY |
| | LINE TO PCN 74434329000001230. SPOKE TO ZONING, |
| | ADDRESSING, ARCHITECT AND ENGINEER???S OFFICE. |
| | RECORDED UNITY OF TITLE OR RE-PLAT OF PROPERTY NEEDS TO |
| | BE PROVIDED. |
| | IF THIS IS NOT DONE, NO LIGHTING, GATES OR OTHER |
| | ELECTRICAL SYSTEMS MAY CROSS THE PROPERTY LINES. |
| | |
| | 2) NOTE: ALL PREVIOUS SUBMITTED ENERGY CALCULATIONS |
| | WERE UNDER METHOD *B*. THE NEW SUBMITTED CALCULATIONS |
| | ARE NOW SUBMITTED UNDER METHOD *A* FOR WHOLE BUILDING |
| | COMPLIANCE. THIS IS NOT A WHOLE BUILDING PER |
| | DEFINITIONS UNDER CHAPTER 2 AND SECTION 202 OF CHAPTER |
| | 13. |
| | PLEASE PROVIDE METHOD B PER 13-400.B.0.4 |
| | SEE DEFINITION OF RENOVATION. |
| | |
| | ** IDR MISSING P-5 FOR EXTERIOR. THIS ALONG WITH FRONT |
| | ENTRANCE IS NOT CONSIDERED A GROSS ERROR PER 13-103.3, |
| | PLEASE UPDATE METHOD. |
| | |
| | 3) NOTE: PLEASE ADJUST LIGHTING CONTROLS TO MEET |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. ALL LIGHTING WITH THE |
| | EXCEPTION OF THE DESIGNATED NIGHT LIGHTS AS GONE OVER |
| | IN MEETING AND ON PHONE ARE REQUIRED TO TURN OFF |
| | AUTOMATICALLY WHEN BUILDING IS NOT OCCUPIED. |
| | |
| | A) RIBBON LIGHTING CONTROLS TO MEET .1.3 OF SECTION |
| | NOTED ABOVE. |
| | |
| | B) G FIXTURES NEED TO HAVE SEPARATE WITH AUTOMATIC SHUT |
| | OFFS. |
| | |
| | C) CONTROLS FOR SECOND FLOOR EAST CORRIDOR LIGHTS NEED |
| | TO MEET SECTION .1.1, .1.2 ABOVE. THE DLT SWITCHES |
| | LOCATED ON FIRST FLOOR NEEDS TO MEET THE REQUIREMENT OF |
| | THE OCCUPANT SEEING THE LIGHTING WHICH IS BEING |
| | CONTROLLED OR MEET EXCEPTIONS. |
| | PER CONVERSATION WITH DESIGNER THESE MAY BE CHANGED TO |
| | OCCUPANCY SENSORS ON FAIL-SAFE OPERATION. |
| | |
| | D) SEE NOTES BELOW WITH RESPECT TO CIRCUITING OF OTHER |
| | EMERGENCY LIGHTING BEING CONTROLLED. FOR EXAMPLE: |
| | CIRCUITS SUCH AS HPA-9, EH1A-16, WHICH ARE THROUGH THE |
| | LIGHTING CONTROL PANEL NEED TO BE * HOT* ALL THE TIME. |
| | |
| | 4) NOTE: PLEASE PROVIDE HOW THE *D* FIXTURES WILL MEET |
| | LIFE SAFETY FOR BACK UP POWER. THE PLANS INDICATE THESE |
| | FIXTURES WILL BE ON TRANSFORMERS HOWEVER THERE ARE NO |
| | UPS SYSTEM(S)/ UNITS ON PLANS FOR THE BACK UP OF THESE |
| | FIXTURES. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9,.1.2, .2.2 AND NFPA-70 |
| | 700.12A, 700.12C, 700.12F ETC |
| | THIS WAS GONE OVER WITH THE DESIGNER. |
| | |
| | 5) NOTE: PLEASE SEE THAT EXIT AREAS LOCATED OUTSIDE |
| | WHERE STEPS ARE PRESENT NEED TO CONTAIN LIGHTING FOR |
| | EGRESS. PLEASE SEE ES-1 AND E2-B, THE SOUTHEAST FIRST |
| | FLOOR EXIT AND THE SOUTH EXIT. THIS WAS GONE OVER ON |
| | PREVIOUS MEETINGS AND WITH DESIGNER ON PHONE. THESE ARE |
| | ALSO TO BE CIRCUITED PER 700.12F. |
| | |
| | 6) NOTE: THE NIGHT-LIGHT CIRCUITS ON PLANS INDICATE |
| | CIRCUITING THROUGH *EH1B-7*, HOWEVER THERE IS NO EH1B |
| | PANEL. THESE WERE GONE OVER WITH DESIGNER AND SHOULD BE |
| | EH1A-15; ALSO PANEL SCHEDULE DESIGNATION STATES ICE |
| | RINK WHEN ACTUALLY THIS IS FIRST AND SECOND FLOOR NIGHT |
| | LIGHTS WEST. |
| | THIS WAS GONE OVER WITH DESIGNER. |
| | PLEASE ALSO SEE CIRCUIT H1B-7 FOR *D* FIXTURES ABOVE IN |
| | NOTE #4 WHICH ARE ACTUALLY BLANK ON PANEL SCHEDULE. |
| | THIS WAS GONE OVER WITH DESIGNER. |
| | |
| | |
| | ** NOTES WERE GONE OVER WITH DESIGNER AND CORRECTIONS |
| | WILL BE BROUGHT IN THE WEEK OF 8/24. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |