Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop E
Sequence Number 11
Notes
Date Text
2009-08-21 19:50:35 
  
  
 ** DENIED REVIEW **
  
 ** THE ELECTRICAL NOTES BELOW WERE GONE OVER WITH
 ENGINEER???S OFFICE ON 8/21/09. CHANGES ARE TO BE MADE
 AND SHEETS REVISED.
  
  
  
 1) NOTE: ELECTRICAL SITE PLANS NOW ONCE AGAIN INCLUDE
 LIGHTING BEING FED FROM THIS BUILDING ACROSS PROPERTY
 LINE TO PCN 74434329000001230. SPOKE TO ZONING,
 ADDRESSING, ARCHITECT AND ENGINEER???S OFFICE.
 RECORDED UNITY OF TITLE OR RE-PLAT OF PROPERTY NEEDS TO
 BE PROVIDED.
 IF THIS IS NOT DONE, NO LIGHTING, GATES OR OTHER
 ELECTRICAL SYSTEMS MAY CROSS THE PROPERTY LINES.
  
 2) NOTE: ALL PREVIOUS SUBMITTED ENERGY CALCULATIONS
 WERE UNDER METHOD *B*. THE NEW SUBMITTED CALCULATIONS
 ARE NOW SUBMITTED UNDER METHOD *A* FOR WHOLE BUILDING
 COMPLIANCE. THIS IS NOT A WHOLE BUILDING PER
 DEFINITIONS UNDER CHAPTER 2 AND SECTION 202 OF CHAPTER
 13.
 PLEASE PROVIDE METHOD B PER 13-400.B.0.4
 SEE DEFINITION OF RENOVATION.
  
 ** IDR MISSING P-5 FOR EXTERIOR. THIS ALONG WITH FRONT
 ENTRANCE IS NOT CONSIDERED A GROSS ERROR PER 13-103.3,
 PLEASE UPDATE METHOD.
  
 3) NOTE: PLEASE ADJUST LIGHTING CONTROLS TO MEET
 13-415.1.ABC.1.1, .1.2 AND .1.3. ALL LIGHTING WITH THE
 EXCEPTION OF THE DESIGNATED NIGHT LIGHTS AS GONE OVER
 IN MEETING AND ON PHONE ARE REQUIRED TO TURN OFF
 AUTOMATICALLY WHEN BUILDING IS NOT OCCUPIED.
  
 A) RIBBON LIGHTING CONTROLS TO MEET .1.3 OF SECTION
 NOTED ABOVE.
  
 B) G FIXTURES NEED TO HAVE SEPARATE WITH AUTOMATIC SHUT
 OFFS.
  
 C) CONTROLS FOR SECOND FLOOR EAST CORRIDOR LIGHTS NEED
 TO MEET SECTION .1.1, .1.2 ABOVE. THE DLT SWITCHES
 LOCATED ON FIRST FLOOR NEEDS TO MEET THE REQUIREMENT OF
 THE OCCUPANT SEEING THE LIGHTING WHICH IS BEING
 CONTROLLED OR MEET EXCEPTIONS.
 PER CONVERSATION WITH DESIGNER THESE MAY BE CHANGED TO
 OCCUPANCY SENSORS ON FAIL-SAFE OPERATION.
  
 D) SEE NOTES BELOW WITH RESPECT TO CIRCUITING OF OTHER
 EMERGENCY LIGHTING BEING CONTROLLED. FOR EXAMPLE:
 CIRCUITS SUCH AS HPA-9, EH1A-16, WHICH ARE THROUGH THE
 LIGHTING CONTROL PANEL NEED TO BE * HOT* ALL THE TIME.
  
 4) NOTE: PLEASE PROVIDE HOW THE *D* FIXTURES WILL MEET
 LIFE SAFETY FOR BACK UP POWER. THE PLANS INDICATE THESE
 FIXTURES WILL BE ON TRANSFORMERS HOWEVER THERE ARE NO
 UPS SYSTEM(S)/ UNITS ON PLANS FOR THE BACK UP OF THESE
 FIXTURES.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9,.1.2, .2.2 AND NFPA-70
 700.12A, 700.12C, 700.12F ETC
 THIS WAS GONE OVER WITH THE DESIGNER.
  
 5) NOTE: PLEASE SEE THAT EXIT AREAS LOCATED OUTSIDE
 WHERE STEPS ARE PRESENT NEED TO CONTAIN LIGHTING FOR
 EGRESS. PLEASE SEE ES-1 AND E2-B, THE SOUTHEAST FIRST
 FLOOR EXIT AND THE SOUTH EXIT. THIS WAS GONE OVER ON
 PREVIOUS MEETINGS AND WITH DESIGNER ON PHONE. THESE ARE
 ALSO TO BE CIRCUITED PER 700.12F.
  
 6) NOTE: THE NIGHT-LIGHT CIRCUITS ON PLANS INDICATE
 CIRCUITING THROUGH *EH1B-7*, HOWEVER THERE IS NO EH1B
 PANEL. THESE WERE GONE OVER WITH DESIGNER AND SHOULD BE
 EH1A-15; ALSO PANEL SCHEDULE DESIGNATION STATES ICE
 RINK WHEN ACTUALLY THIS IS FIRST AND SECOND FLOOR NIGHT
 LIGHTS WEST.
 THIS WAS GONE OVER WITH DESIGNER.
 PLEASE ALSO SEE CIRCUIT H1B-7 FOR *D* FIXTURES ABOVE IN
 NOTE #4 WHICH ARE ACTUALLY BLANK ON PANEL SCHEDULE.
 THIS WAS GONE OVER WITH DESIGNER.
  
  
 ** NOTES WERE GONE OVER WITH DESIGNER AND CORRECTIONS
 WILL BE BROUGHT IN THE WEEK OF 8/24.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  