| 2009-07-27 07:52:01 | BUILDING PLAN REVIEW |
| | PERMIT: 08090611 |
| | ADD: 1590 FLORIDA MANGO |
| | CONT: SOUTHEAST CERTIFIED |
| | TEL: (561)635-6935 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | PHASE II REVIEW |
| | ACTION: |
| | BUILDING PROVISO: |
| | 7-28-09 |
| | |
| | 1-10) COMPLIED. |
| | |
| | 11) A NEW EXTERIOR STAIR ON THE EAST END OF THE |
| | BUILDING APPEARED TO HAVE UNPROTECTED OPENINGS WITHIN |
| | 10 FT OF THE STAIR AND LANDINGS, INDICATING REVIEWING |
| | 1019.1.4. |
| | |
| | 1019.1.4 VERTICAL ENCLOSURE EXTERIOR WALLS. |
| | EXTERIOR WALLS OF A VERTICAL EXIT ENCLOSURE SHALL |
| | COMPLY WITH THE REQUIREMENTS OF SECTION 704 FOR |
| | EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED |
| | OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE |
| | WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE |
| | BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES (3.14 |
| | RAD), THE BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048 |
| | MM) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED |
| | OPENING SHALL BE CONSTRUCTED AS REQUIRED FOR A MINIMUM |
| | 1-HOUR FIRE-RESISTANCE RATING WITH ??-HOUR OPENING |
| | PROTECTIVES. THIS CONSTRUCTION SHALL EXTEND VERTICALLY |
| | FROM THE GROUND TO A POINT 10 FEET (3048 MM) ABOVE THE |
| | TOPMOST LANDING OF THE STAIRWAY OR TO THE ROOF LINE, |
| | WHICHEVER IS LOWER. |
| | |
| | SHEET 722 THE NEW ELEVATION CLEARLY INDICATES BENEATH |
| | THE STAIR LANDING OF THE MEZZANINE, A ROLL UP DOOR, THE |
| | MEZZANINE LEVEL THE EXTERIOR EXIT DOOR, NEITHER DOOR IS |
| | INDICATED IN THE DOOR SCHEDULE NOR DOES THE ELEVATION |
| | INDICATE ANY FIRE RATING. THE PLANS ALSO FAIL TO |
| | INDICATE FIRE RATINGS ON THE WINDOWS DIRECTLY NEXT TO |
| | THE EXIT DOOR OF THE MEZZANINE LEVEL. IN BOTH CASES THE |
| | OPENING PROTECTIVES WILL NEED TO BE ONE HOUR RATING. |
| | THE OTHER WINDOWS THAT ARE ADJACENT (WITHIN 10 FT OF |
| | THE LANDING) WILL NEED TO BE 45 MINUTE RATED OPENINGS, |
| | THE LOUVER TO THE RIGHT OF THE LANDING. PLEASE PROVIDE |
| | THE VERTICAL DISTANCE FROM THE WINDOWS DIRECTLY OVER |
| | THE LANDING AND LEFT OF THE LANDING, ONCE THIS |
| | DIMENSION IS KNOWN THEY ALSO MAY NEED TO BE FIRE RATED |
| | OPENINGS. |
| | |
| | I SPOKE WITH BOTH ERIC ANDERSON AN CHRIS HAIR ABOURT |
| | THE UNPROTECTED OPENING REQUIREMENTS. THEY WILL BE |
| | WORKING ON THESE REQUIREMENTS AND WILL SUBMIT REVISIONS |
| | TO THIS OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL |
| | BE ISSUED FOR THIS PHASE OF WORK. |
| | |
| | 11-15 COMPLIED. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |