Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop B
Sequence Number 11
Notes
Date Text
2009-07-27 07:52:01BUILDING PLAN REVIEW
 PERMIT: 08090611
 ADD: 1590 FLORIDA MANGO
 CONT: SOUTHEAST CERTIFIED
 TEL: (561)635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 PHASE II REVIEW
 ACTION:
 BUILDING PROVISO:
 7-28-09
  
 1-10) COMPLIED.
  
 11) A NEW EXTERIOR STAIR ON THE EAST END OF THE
 BUILDING APPEARED TO HAVE UNPROTECTED OPENINGS WITHIN
 10 FT OF THE STAIR AND LANDINGS, INDICATING REVIEWING
 1019.1.4.
  
 1019.1.4 VERTICAL ENCLOSURE EXTERIOR WALLS.
 EXTERIOR WALLS OF A VERTICAL EXIT ENCLOSURE SHALL
 COMPLY WITH THE REQUIREMENTS OF SECTION 704 FOR
 EXTERIOR WALLS. WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE
 WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES (3.14
 RAD), THE BUILDING EXTERIOR WALLS WITHIN 10 FEET (3048
 MM) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED
 OPENING SHALL BE CONSTRUCTED AS REQUIRED FOR A MINIMUM
 1-HOUR FIRE-RESISTANCE RATING WITH ??-HOUR OPENING
 PROTECTIVES. THIS CONSTRUCTION SHALL EXTEND VERTICALLY
 FROM THE GROUND TO A POINT 10 FEET (3048 MM) ABOVE THE
 TOPMOST LANDING OF THE STAIRWAY OR TO THE ROOF LINE,
 WHICHEVER IS LOWER.
  
 SHEET 722 THE NEW ELEVATION CLEARLY INDICATES BENEATH
 THE STAIR LANDING OF THE MEZZANINE, A ROLL UP DOOR, THE
 MEZZANINE LEVEL THE EXTERIOR EXIT DOOR, NEITHER DOOR IS
 INDICATED IN THE DOOR SCHEDULE NOR DOES THE ELEVATION
 INDICATE ANY FIRE RATING. THE PLANS ALSO FAIL TO
 INDICATE FIRE RATINGS ON THE WINDOWS DIRECTLY NEXT TO
 THE EXIT DOOR OF THE MEZZANINE LEVEL. IN BOTH CASES THE
 OPENING PROTECTIVES WILL NEED TO BE ONE HOUR RATING.
 THE OTHER WINDOWS THAT ARE ADJACENT (WITHIN 10 FT OF
 THE LANDING) WILL NEED TO BE 45 MINUTE RATED OPENINGS,
 THE LOUVER TO THE RIGHT OF THE LANDING. PLEASE PROVIDE
 THE VERTICAL DISTANCE FROM THE WINDOWS DIRECTLY OVER
 THE LANDING AND LEFT OF THE LANDING, ONCE THIS
 DIMENSION IS KNOWN THEY ALSO MAY NEED TO BE FIRE RATED
 OPENINGS.
  
 I SPOKE WITH BOTH ERIC ANDERSON AN CHRIS HAIR ABOURT
 THE UNPROTECTED OPENING REQUIREMENTS. THEY WILL BE
 WORKING ON THESE REQUIREMENTS AND WILL SUBMIT REVISIONS
 TO THIS OFFICE BEFORE A CERTIFICATE OF OCCUPANCY WILL
 BE ISSUED FOR THIS PHASE OF WORK.
  
 11-15 COMPLIED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.