| 2009-08-10 17:49:28 | REVISION DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | FBC-2007 CAHPTER 11 |
| | |
| | ****FROM PREVIOUS REVISION REVIEW:+ |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK (DELETED) |
| | |
| | 4. SHT P-1 3 INCH SANITARY FROM 2ND FLOOR TO DRYWELL IS |
| | PROHIBITED. SECTION 301.3. |
| | ****RESPONSE NOTED, BUT THE PIPING STILL IS INDICATED |
| | AS SANITARY, NOT CONDENSATE ON SHT P-1. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SHT P-2B INDICATE WHERE THE WATER HEATER PAN DRAIN |
| | LINE TERMINATES. SECTION 504.7.2. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | |
| | 9. SHT P-3A THE SANITARY ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE. |
| | PLEASE ADDRESS THE FOLLOWING: |
| | - THE CLEANOUTS REQUIRED BY SECTIONS 708.3.2 & 708.3.5 |
| | SHOWN ON THE FLOOR PLAN ARE MISSING ON THE RISER. |
| | ****RESPONSE NOTED, COMMENT NOT ADDRESSED. |
| | - OK |
| | - OK |
| | - OK |
| | - OK |
| | PLEASE CORRELATE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |