Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop P
Sequence Number 10
Notes
Date Text
2009-08-10 17:49:28REVISION DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CAHPTER 11
  
 ****FROM PREVIOUS REVISION REVIEW:+
  
 1. OK
 2. OK
 3. OK (DELETED)
  
 4. SHT P-1 3 INCH SANITARY FROM 2ND FLOOR TO DRYWELL IS
 PROHIBITED. SECTION 301.3.
 ****RESPONSE NOTED, BUT THE PIPING STILL IS INDICATED
 AS SANITARY, NOT CONDENSATE ON SHT P-1.
  
 5. OK
 6. OK
 7. OK
  
 8. SHT P-2B INDICATE WHERE THE WATER HEATER PAN DRAIN
 LINE TERMINATES. SECTION 504.7.2.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 9. SHT P-3A THE SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE.
 PLEASE ADDRESS THE FOLLOWING:
 - THE CLEANOUTS REQUIRED BY SECTIONS 708.3.2 & 708.3.5
 SHOWN ON THE FLOOR PLAN ARE MISSING ON THE RISER.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
 - OK
 - OK
 - OK
 - OK
 PLEASE CORRELATE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  