Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop E
Sequence Number 10
Notes
Date Text
2009-08-09 11:35:38 
  
  
  
 ** DENIED REVIEW OF REVISIONS**
  
 ** AT PREVIOUS MEETING HELD WITH ARCHITECT, OWNER
 REPRESENTATIVE, CONTRACTOR, PERMIT EXPEDITOR AND OTHER
 CITY STAFF IT WAS NOTED THAT NO MEP DESIGN TEAM MEMBERS
 WERE PRESENT. AT THIS TIME IT IS STRONGLY RECOMMENDED
 THAT A MEETING BE HELD BEFORE PLANS ARE RESUBMITTED
 ONCE AGAIN.
 SOME OF THE NOTES BELOW WILL HAVE AN AFFECT ON PHASE I
 TCO.
  
 1) NOTE: THE PREVIOUS REVIEW REQUESTED A VALUE UPDATE
 FOR THE PROJECT AS THE COMPLETE SCOPE OF WORK HAS
 SUBSTANTIALLY INCREASED. THE NEW VALUE STATED ON
 RESPONSE IS ACTUALLY LOWER THAN THE ORIGINAL APPLIED
 VALUE. HOW IS THIS POSSIBLE? THE COMPLETE SCOPE OF WORK
 VALUE IS REQUIRED TO INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COSTS. THIS INCLUDES ALL EQUIPMENT
 WHICH MAY BE OWNER PURCHASED OR SUPPLIED.
 FBC 108.3
 COMPLETE CONTRACTS WITH ALL RELEVANT PARTIES INCLUDING
 DETAILED LISTS OF ALL EQUIPMENT AND MATERIALS CAN BE
 REQUESTED.
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS IN
 COMPLIANCE WITH THE FLORIDA BUILDING CODE.
 PLEASE SEE FBC 13-415.AB.2.2, .5 AS THE SUBMITTED
 LIGHTING PERFORMANCE CALCULATIONS ARE NOT COORDINATING
 WITH THE SUBMITTED PLANS FOR THIS PROJECT. THE SEPARATE
 PERMIT SUBMITTED FOR SITE LIGHTING DOES NOT HAVE *ANY*
 LIGHTING PERFORMANCE CALCULATIONS MEETING MINIMUMS. THE
 NEW SUBMITTED REVISED ENERGY CALCULATIONS DO NOT SHOW
 ANY EXTERIOR LIGHTS. THIS IS NOT POSSIBLE WHEN THE SITE
 AS WELL AS THE BUILDING CONTAINS NUMEROUS LIGHT
 FIXTURES AND NONE ARE SHOWN IN THE CALCULATIONS. IN
 FACT THE INPUT DATA REPORT IS ACTUALLY BLANK. THIS IS
 NOT POSSIBLE.
  
 A) THE INTERIOR LIGHTING DOES NOT COORDINATE WITH THE
 SUBMITTED PLANS. THERE ARE MANY MORE FIXTURES ON PLANS
 THAN IN THE IDR.
 13-415.B.1
  
 B) FOR INFORMATION, THE WATTAGE USE ON PLANS IS
 SUBSTANTIALLY HIGHER ON E-1 FOR EXAMPLE.
  
 3) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 LIGHTING FOR EGRESS AREAS UNDER NORMAL AND EMERGENCY
 CONDITIONS AS NOTED PREVIOUSLY.
  
 A) SPECIFICALLY SHEET EP-1, THE STAIRS CHANGED AND
 REVISED PHOTO-METRICS MEETING MINIMUM FOR LIFE SAFETY
 AND NORMAL OR EMERGENCY WAS SUBMITTED IN THE REVISIONS
 FOR PHASE 1. THE REVIEW WAS NOT COMPLETED BY THIS
 REVIEWER HOWEVER AS OF THE REVIEW PREVIOUSLY DONE UNDER
 PHASE II THIS WAS NOTED AS NEEDING TO BE REVISED.
 NFPA- 101 7.8.1.3, 7.9.1.2, .2.2.
  
 B) NO LEVELS SUBMITTED OR SHOWN FOR LEVELS FOR NORMAL
 EXTERIOR STAIRS (EAST). ONE EXAMPLE WOULD BE THESES
 STAIRS. THE SECTIONS OF THE CODES NOTED ABOVE FOR
 MINIMUM LIFE SAFETY REQUIREMENTS REQUIRED 10FT CANDLES,
 PLEASE SUBMITTED ONLY SHOW LEVELS UNDER EMERGENCY. THE
 LEVELS ARE REQUIRED AT EACH STAIR TREAD, NOT ONE, TWO,
 OR THREE POINTS.
  
 C) PLEASE INDICATE WHAT HAPPENED TO LEVELS OF LIGHTS
 DURING PERFORMANCES? PREVIOUS NOTES GAVE INFORMATION AS
 TO THE SPECIFIC SECTIONS OF THE LIFE SAFETY CODE.
 MANY OF THESE LIGHTING LEVELS ARE SHOWN UNDER NORMAL
 CONDITIONS HOWEVER LIGHTING IS ON *DIMMING PANELS*
  
 D) PLACE INFORMATION ON PLANS ON ACTIVATION OF
 EMERGENCY CONDITIONS/FIRE ALARM ACTIVATION AS PLANS ARE
 BEING CORRECTED AT THIS TIME.
  
 E) ANOTHER EXAMPLE: UNDER EMERGENCY CONDITIONS, ONLY
 FIXTURES WHICH CONTAIN THE EMERGENCY BATTERY BACK UP
 MAY BE USED FOR LEVELS. PLEASE SEE FUTURE FRONT
 ENTRANCE FOR EXAMPLE. HOW IT IS POSSIBLE FOR THE
 LIGHTING IN AREAS TO CONTAIN A HIGHER LEVEL OF LIGHT
 WHEN PER THE LIGHTING PLANS THOSE AREAS DO NO CONTAIN
 FIXTURES WHICH ARE BATTERY BACK UP.
  
 F) PLEASE EXPLAIN THE KE FIXTURE LOCATED OUTSIDE. THIS
 IS A FIXTURE NOTED INSIDE HOWEVER THIS IS LOCATED
 OUTSIDE ON FIRST FLOOR IN AREA WHICH WOULD BE A WET
 LOCATION. MANUFACTURE SPECS ON SITE DOES NOT INDICATE
 THIS AS A WET LOCATION FIXTURE.
  
  
 PLEASE SEE NFPA-101 7.8.1.2.2 , FBC 1006.1.2, FOR
 OCCUPANCY SENSORS ON EGRESS LIGHTING AND ALSO LIGHTING
 CONTROLS ON NORMAL LIGHTING FOR EGRESS AREAS.
  
 4) NOTE: PREVIOUS REVIEW NOTES WERE GIVEN WITH RESPECT
 TOP ASME-17 2004 FOR MINIMUM ELEVATOR CODES. HOWEVER
 THERE ARE AREAS IN WHICH MINIMUM LEVELS FOR THE
 REFERENCED CODE WOULD NOT BE MET.
 ** THIS IS ONLY NOTED.
  
 5) NOTE: THE GENERATOR ON THE SUBMITTED RISER IS STILL
 SHOWING GROUND FAULT PROTECTION ON THE GENERATOR
 BREAKER. THE BACK UP SYSTEM WHICH IS AN OPTIONAL
 STAND-BY SYSTEM WILL NOT WORK BASED ON THE SYSTEM
 SUBMITTED WITH THE 3-POLE ATS.
 ** THIS WAS REVISED ON THE GENERATOR SUB PERMIT HOWEVER
 NOT ON THIS RISER. PLEASE CORRECT AT THIS TIME.
  
 6) NOTE: AS NOTED AND GONE OVER IN MEETING HELD BEFORE
 PLANS WERE RESUBMITTED. THE EGRESS PATH ON THE FIRST
 FLOOR WEST AREAS STILL INDICATES THE CONDENSING UNITS
 AND OTHER A/C EQUIPMENT NOT PERMITTED IN EGRESS PATH
 ALONE SIDE WALK.
 THIS WAS NOTED BY THE FIRE MARSHAL YET STILL SHOWN IN
 PATH.
  
 7) NOTE: NO INFORMATION SHOWN FOR LOAD BANK ON
 GENERATOR. THE FRESH AIR MAKE UP IS LOCATED IN REAR OF
 BUILDING. THIS IS A 500KW DIESEL GENERATOR WITH NO LOAD
 BANK INFORMATION. PLEASE PROVIDE THE MANUFACTURE
 RECOMMENDED LOAD TO PREVENT WET STACKING. THIS
 INFORMATION WILL BE FORWARDED TO MECHANICAL AND FIRE
 MARSHAL. ** THIS IS NOTED ONLY BY THIS REVIEWER.
 PLEASE SEE THAT INSTALLATION OF GENERATOR SHALL BE PER
 MANUFACTURES RECOMMENDATIONS PER LISTING.
 110.3, 90.7
  
 8) NOTE: PLEASE COORDINATE RISER. THE LOAD CALCULATION
 FOR TWB STATES MINIMUM SERVICE REQUIRED 200AMPS YET THE
 RISER INDICATES 150AMP.
 THIS COULD HAVE REDLINED HOWEVER COMMENTS FOR OTHER
 ITEMS ON REVIEW.
  
 9) NOTE: REVISIONS TO FUNCTION OF LIGHTING CONTROL
 SYSTEM UNDER PHASE 1 NOT SUBMITTED. SYSTEM FUNCTION
 BEFORE TCO OF PHASE I SYSTEM LIGHTING WILL BE REQUIRED.
 13-415.1.ABC.1.1,.1.2, .1.3 AND .1.4.
  
  
 ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR.
 A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS
 AND CHANGE OUT SHEETS.
  
  
  
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  