Plan Review Notes
Plan Review Notes For Permit 08090611
Permit Number 08090611
Review Stop B
Sequence Number 10
Notes
Date Text
2009-07-22 10:46:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. EACH PORTION OF A STRUCTURE IS TO BE CLASSIFIED AS
 TO USE, FBC302.1. SHEET T, A4 IS DECLARED, BUT PLAN
 SHOWS STORAGE, ARCADE (FBC302.2.1), CONCESSION
 W/DINING. PLEASE CLARIFY SQUARE FOOT AREA PER OCCUPANCY
 CLASSIFICATION.
  
 2. PLEASE SHOW COMPLIANCE WITH FBC CHAPTER 5. PLAN
 STATES THAT FBC507.2 ALLOWS UNLIMITED AREA; PLEASE SEE
 COMMENT 1. PLEASE DECLARE BUILDING AS SEPARATED OR NON
 SEPARATED USE, FBC302.
  
 3. PLEASE NOTE THAT COMPLIANCE FOR THE ENTIRE BUILDING
 IS TO BE SHOWN ON THE PLAN. SHEET T ACCOUNTS FOR THE
 RINK AREAS ONLY, BUT THIS IS ONLY A PORTION OF THE
 BUILDING. PLEASE REVISE AREA CALCULATIONS TO INCLUDE
 ALL PARTS OF THE BUILDING, UNLESS SEPARATED BY A FIRE
 WALL, FBC502.
  
 4. FBC1024.12, SEATS SHALL BE SECURELY FASTENED TO THE
 FLOOR. THE PLANS NOTE THAT SOME SEATS SHALL BE
 REMOVABLE TO ACCOMMODATE ACCESSIBLE SEATING, SHEET 212.
 PLEASE ADDRESS. ALSO NOTE THAT THIS PAGE IS LABELED
 SECOND FLOOR SEATING PLAN; ISN???T THIS THE FIRST
 FLOOR?
  
 5. PLEASE CLARIFY HOW OCCUPANT LOAD HAS BEEN
 CALCULATED. FOR INSTANCE, FIRST FLOOR STATES THAT
 OCCUPANT LOAD HAS BEEN DETERMINED BY 36,225 SF, 50 SF
 PER OCCUPANT, TOTAL OF 725. THE FIRST FLOOR CONSISTS OF
 THE SKATING RINK (50 SF GROSS), FIXED SEATING (SEE
 FBC1004.7), ARCADE (11 GROSS PER FBC TABLE 1004.1.2),
 ETC. IT APPEARS THAT THE TOTAL OCCUPANT LOAD MAY BE
 CONSERVATIVE, BUT PLEASE PROVIDE CALCULATIONS OF
 OCCUPANTS PER AREA TO CONFIRM COMPLIANCE WITH
 FBC1004.1.
  
 SHEET T DECLARES 271 OCCUPANTS, SHEET 120 SHOWS 268
 TOTAL. PLEASE CONFIRM THAT LIFE SAFETY PLAN CORRELATES
 WITH OTHER SHEETS.
  
 6. AS THE ARCHITECT OF RECORD HAS CHANGED, PLEASE
 EITHER PROVIDE EITHER A LETTER TO CONFIRM THAT
 COMPLIANCE WITH FAC61G1-18.002 HAS BEEN MET IF REUSING
 THE PREVIOUS ARCHITECT???S PLANS, OR PROVIDE NEW SIGNED
 AND SEALED SHEETS FOR ALL SHEETS REQUIRED TO SHOW CODE
 COMPLIANCE.
  
 7. FBC1004.3, OCCUPANT LOAD FOR EVERY ROOM OR SPACE
 SHALL BE POSTED. THIS WILL BE A PROVISO ITEM.
  
 8. FBC11-4.33.3, ACCESSIBLE SEATING CAPACITY IS OVER
 300; WHEELCHAIR SPACES TO BE PROVIDED IN MORE THAN ONE
 LOCATION. ALL ACCESSIBLE SEATING IS SHOWN IN ONE
 MEZZANINE. ARCHITECT ADVISED THAT HE WILL APPLY FOR A
 WAIVER FOR THE EAST MEZZANINE, BUT WHEELCHAIR SEATING
 IS TO BE PROVIDED AT THE FIRST FLOOR ALSO. VERTICAL
 ACCESSIBILITY IS REQUIRED TO THE EAST MEZZANINE,
 FBC11-4.1.3(5), AND ACCESSIBLE SEATING IS REQUIRED IN
 THE EAST MEZZANINE, UNLESS OTHERWISE APPROVED BY
 WAIVER.
  
 9. PLEASE HAVE EOR REVIEW THE DELEGATED ENGINEERING ON
 THIS JOB, FAC61G15-31.
  
 10. FBC1023.6, IT APPEARS THAT THE EXCEPTION APPLIES TO
 THIS PROJECT (SAFE DISPERSAL AREA). THIS WILL BE A
 PROVISO ITEM.
  
 11. SEE FBC106, MINIMUM PLAN REVIEW CRITERIA. PLEASE
 PROVIDE ELEVATIONS OF BUILDING EXTERIOR. IT APPEARS
 THAT THE PROPOSED NEW STAIRS ARE WITHIN 10FT OF
 UNPROTECTED OPENINGS, SEE FBC1019.1.4.
  
 12. PLEASE PROVIDE UPDATED VALUE FOR INCREASED SCOPE OF
 WORK.
  
 13. PLEASE SHOW COMPLIANCE WITH FBC1006.1, MEANS OF
 EGRESS ILLUMINATION. IT IS NOT CLEAR HOW THE STAIRS
 (INCLUDING THE FIXED SEATING) WILL COMPLY.
  
 14. ENERGY CALCS GIVE A SF AREA OF 9600, PLANS STATE
 36,225. PLEASE REVISE OR EXPLAIN.
  
 15. PLEASE CONTACT ME WHEN ALL REVIEWS ARE COMPLETE IF
 ISSUANCE OF THIS REVISION WITH PROVISOS IS DESIRED. THE
 PREFERENCE IS THAT ALL ITEMS BE ADDRESSED PRIOR TO
 ISSUANCE; HOWEVER, TO AVOID FIELD DELAYS, IT IS
 POSSIBLE THAT THIS REVISION MAY BE ISSUED WITH PROVISO.
 PLEASE CONTACT ME WHEN ALL REVIEWS ARE COMPLETE TO
 DISCUSS HOW YOU WISH TO PROCEED.
  
  
  
  